TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
11
62-0311—05
Fig. 24. Installer Setup (ISU) mode screen.
M27585
Setup
Table 4. Installer Setup (ISU) Codes and Options.
ISU
Code Code Description
Option
Value
Option Description (Default value shown in
Bold)
Notes
1
Line Voltage
Selection
0
120 Vac power supply (Default)
1
240 Vac power supply
2
System Type
0
Heat only
1
Cool only
2
Two pipes: Heat or Cool; Manual Changeover
3
Two pipes: Heat or Cool; Seasonal Changeover
(requires optional pipe sensor)
4
Four pipes: Manual Changeover
TB6575A, TB8575A only
5
Four pipes: Auto Changeover
TB6575A, TB8575A only
6
Two pipes: Heat or Cool; with Auxiliary Heat
(requires optional pipe sensor).
Allows auxiliary heat to turn
on when pipes have cold
water
(TB6575A, TB8575A only).
7
Four pipes: Manual and Auto Changeover
(Default)
TB6575A, TB8575A only
2.5
Fan On/Off
Selection for Aux
Heat On
0
Fan ON when Auxiliary Heat is on (Default)
Enables or disables the
auto fan operation when
Auxiliary Heat is On
(TB6575A, TB8575A only).
1
Fan OFF when Auxiliary Heat is on
3
Valve Output Type
0
Valve energized on call for heat or cool (Default)
1
Valve de-energized on call for heat or cool
4
Space Sensor Type
0
Onboard Sensor (Default)
1
Remote Sensor (TR21 or other 20K Ohm sensor)
5
Pipe Sensor
Only displays when
value 3 or 6 for the
System Type in ISU
code #2 is selected.
0
Contact Open = Cool mode; Contact Closed = Heat
mode
•
Pipe sensor will flash on
display screen if analog
input (#4) is lost.
•
Pipe sensor status and
water temperature can
be checked in test mode
(see “Installer Test (IT)
details)
1
Contact Open = Heat mode; Contact Closed = Cool
mode
2
Contact Open = Heat mode; Contact Closed = Cool
mode (same as 1)
3
Contact Open = Cool mode; Contact Closed = Heat
mode (same as 0)
4
Analog input (Default).
NTC20K, whose curve is
the same as TR21.
Only displays when system type 3 or 6 is selected.
6
Pipe Sensor
Threshold for
Cooling
50 to
72
Range is 50°F to 72°F.
Default is 60°F.
Changes to Cool when pipe
temperature is below
threshold.
7
Pipe Sensor
Threshold for
Heating
75 to
90
Range is 75°F to 90°F.
Default is 80°F.
Changes to Heat when pipe
sensor temperature is
above threshold.
8
Temperature Scale
0
Degrees Fahrenheit (
°F
); Default.
1
Degrees Celsius
(
°C
).