69-0780

LIGHT-EMITTING DIODE (LED) INDICATIONS:

LED flashing dim-bright indicates normal operation.
LED off when control is powered indicates defective

control.

LED on continuously when control is powered indicates

defective control.

LED flashing in a cycle with LED on  followed by one

or more off pulses indicates the following system
errors.

Number

of Off
 Flash

Pulses

System Condition

1

Burner limit circuit is open.

2

Primary limit circuit is open.

3

Pressure switch circuit is improp-
erly closed.

4

Control is in lockout due to air
not circulating (overheating).

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous condi-
tion.

2. Check the ratings and specifications given in the

instructions and on the product to ensure the product is
suitable for your application.

3. Installer must be a trained, experienced service

 technician.

4. After installation is complete, check out the product

operation as provided in these instructions.

CAUTION

Disconnect power supply before wiring to pre-
vent electrical shock or equipment damage.

Location and Mounting

The ST9141A1002 is mounted in the appliance wiring

compartment using four No. 6 screws (obtained locally)
through holes on the corners of the enclosure.

Wiring

All wiring must comply with local codes and ordi-

nances. Disconnect power before making wiring connec-
tions. Refer to Fig. 1 for standard wiring connections. Refer
to Fig. 2 for an internal schematic.

C.H.  •  6-93  •  ©Honeywell Inc. 1993  •  Form Number 69-0780

ST9141A1002 Electronic Fan Timer

Application

The ST9141A1002 Electronic Fan Timer integrates con-

trol of all combustion blower and circulating fan operations
in a gas warm air appliance. This control is the central
wiring point for most of the electrical components in the
furnace. The basic purposes of the ST9141A1002 are to
monitor the thermostat for heat, cool, and fan demands and
run the induced draft blower motor and up to a two-speed
circulating fan as required. The ST9141A1002 monitors an
spdt pressure switch, burner limit and primary limit. A
Honeywell SV9500 Hot Surface Pilot Ignition System
Control manages the burner, which is energized through
the pressure switch. A light-emitting diode (LED) indicates
system status.

In addition, this model includes electronic air cleaner

and humidifier convenience terminal connections.

NOTE: Use this control to replace an identical ST9141A1002

Electronic Fan Timer only. This control is not for use in
general applications.

Specifications

ELECTRICAL RATINGS:

Power Requirements:

Voltage: 18-30 Vac, 60 Hz.

Contact Ratings:

Combustion Blower:

1.5A Full Load, 10A Locked Rotor at 115 Vac.
.75A Full Load, 5A Locked Rotor at 230 Vac.
Reduce full load rating by humidifier load.

Circulating Fan (Heat-Cool Speed):

15A Full Load, 30A Locked Rotor at 115 Vac.
7.5A Full Load, 15A Locked Rotor at 230 Vac.
Reduce full load rating by electronic air cleaner

load.

Thermostat Load: 0.06A plus ignition system current

draw.

ON/OFF DELAY SETTINGS:

Heat Speed:

Delay On: 30 seconds, fixed.
Delay Off: 60, 100, 140 or 180 seconds, field

adjustable.

Cool Speed:

Delay On: 6 seconds, fixed.
Delay Off: 60 seconds, fixed.

Timing Tolerance: Larger of 

±

5% or 

±

2 seconds.

POSTPURGE TIMING: 5 seconds.
ENVIRONMENTAL RATINGS

Temperature: -40

°

 to +175

°

 F [-40

°

 to +79

°

 C].

Humidity: 5 to 95%, noncondensing.

!

Summary of Contents for ST9141A1002

Page 1: ...002 Electronic Fan Timer Application TheST9141A1002ElectronicFanTimerintegratescon trol of all combustion blower and circulating fan operations in a gas warm air appliance This control is the central wiring point for most of the electrical components in the furnace The basic purposes of the ST9141A1002 are to monitor the thermostat for heat cool and fan demands and run the induced draft blower mot...

Page 2: ...OT PROVIDED THERMOSTAT L2 N L1 H TO 120 VAC POWER SUPPLY COOLING CONTACTOR Y G R W C Y 1 2 UP SPEED DELAY OFF Z1 Z2 1 2 3 DI 1 2 3 4 N MOTOR LEADS C X XFMR SEC X EAC N HUM N CIR BLWR CONT COOL HEAT SV9500 HOT SURFACE PILOT IGNITION SYSTEM CONTROL 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTAT OR PRESSURE SWITCH COMBUSTION BLOWER HUMIDIFIER DENOTES LINE VOLTAGE CONNECTIONS DENOTES LOW VOL...

Page 3: ...BUSTION AIR BLOWER MED LOW HIGH LOW FUSE INTERLOCK N1 K2 HEAT K1 MED HIGH X SV9500 HOT SURFACE PILOT IGNITION SYSTEM CONTROL GND 24V EAC S EAC N L1 1 HUMIDIFIER HUM S HUM N N3 DI K3A 24 VAC 120 VAC N4 PRESSURE SWITCH N O N C COM TSTAT FT CN1 1 X OT 6 R OT 8 PS1 3 7 PS2 C 2 4 5 FT K3B M2 M1 L1 2 COOLING CONTACTOR 24V BURNER LIMIT PRIMARY LIMIT L1 H L2 N TRANSFORMER Fig 2 ST9141A1002 internal schema...

Page 4: ...t speed If a call for cool occurs circulating fan switches to cool speed after four second delay Thermostat ends call for fan Circulating fan is de energized G terminal is de energized Primary limit switch string opens Thermostat and ignition system are de energized and gas valve closes Combustion air blower is de energized Circulating fan is energized at heat speed LED flashes twice If there is a...

Page 5: ...eration resumes Burner limit opens Thermostat and ignition system are de energized and gas valve closes Combustion air blower and circulating fan heat speed are energized LED flashes once Burner limit closes Combustion air blower remains energized for postpurge timing The circulating fan remains energized for the selected delay off timing LED stops flashing Normal operation resumes Electronic air ...

Page 6: ...me and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: