background image

2

ST6008A,B,C ENERGY MANAGEMENT TIMERS

68-3002

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not
include normal manufacturing tolerances; therefore,
an individual unit may not exactly match the listed
specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed.

Models:

ST6008A1006: 24-hour time-based switching with

synchronous drive.

ST6008B1005: 7-day time-based switching with

synchronous drive.

ST6008C1004: 7-day time-based switching with quartz

drive and battery backup.

Model

Type

Input Voltage

Relay Output

Battery Reserve  

ST6008A1006

24-hour synchronous

120V, 60 Hz

1 spdt

N/A

ST6008B1005

7-day synchronous

120V, 50 Hz

1 spdt

N/A

ST6008C1004

7-day quartz

120V, 50/60 Hz

1 spdt

7-day

Supply Voltage:

Synchronous: 120V, 60 Hz.
Quartz: 120V, 50/60 Hz.

Switch Type:
spdt.

Switch Rating:

21A, 250V resistive.
1350W tungsten.
1 hp at 120V.
2 hp at 240V.
16 FLA, 96 LRA, 120V inductive.
12 FLA, 72 LRA, 240V inductive.

Power Consumption:
0.5 VA.

Ambient Temperature Range:

-40

°

F (4

°

C) to 180

°

F (82

°

C), synchronous units.

-14

°

F (26

°

C)  to 131

°

F (55

°

C), quartz units.

Reserve Carryover:
150 hours for quartz units.

Dimensions:
See Fig. 1.

Fig. 1. ST6008A,B,C dimensions in in. (mm).

12

6

9

2-1/4 (57)

2-15/16 (75)

4-1/4
(108)

1-1/2 (38)

2-5/8 (67)

12

11

10

OUTER RING

TRIPPERS

INNER RING

DETACHABLE 
TERMINAL 
COVER

CLEAR POLYCARBONATE 
COVER

M11336

ST6008A,B,C

Summary of Contents for ST6008A

Page 1: ...s for the 7 day timer APPLICATION Time based control of lighting ventilation heating and cooling or other electrical loads in commercial and industrial applications The ST6008 time switches are available with 24 hour or 7 day program dial and a single pole double pole switch The ST6008 series is intended for surface or DIN rail mounting The control is completely enclosed in a plastic housing and i...

Page 2: ...Model Type Input Voltage Relay Output Battery Reserve ST6008A1006 24 hour synchronous 120V 60 Hz 1 spdt N A ST6008B1005 7 day synchronous 120V 50 Hz 1 spdt N A ST6008C1004 7 day quartz 120V 50 60 Hz 1 spdt 7 day Supply Voltage Synchronous 120V 60 Hz Quartz 120V 50 60 Hz Switch Type spdt Switch Rating 21A 250V resistive 1350W tungsten 1 hp at 120V 2 hp at 240V 16 FLA 96 LRA 120V inductive 12 FLA 72...

Page 3: ... the triangle on the inner dial The hour and the minute hand show 10 30 AM ST6008A 24 hour Timer The 24 hour dial is marked in quarter hour and AM and PM indications Set the Time Switch NOTE Each tripper represents 15 minutes A Push the desired number of trippers to the outer ring position for the entire period the load is on This places the switch in the on position B Push the desired number of t...

Page 4: ... Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Honeywell Latin American Division Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016 Helping You Control Your World 68 3002 J S 2 97 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least ...