background image

SPYDER® BACNET® PROGRAMMABLE, VAV/UNITARY CONTROLLERS

62-0310—01

6

NOTE: Controller configurations are not necessarily limited 

to three devices, but the total power draw, including 

accessories, cannot exceed 100 VA when powered 

by the same transformer (U.S. only).

Fig. 9. Power wiring details for two or more controllers per transformer. 

Communications

Each controller uses a BACnet MS/TP communications port. 

The controller’s data is presented to other controllers over a 

twisted-pair MS/TP network, which uses the EIA-485 signaling 

standard capable of the following baud rates: 9.6, 19.2, 38.4, 

76.8 or 115.2 Kilobits per second (configured at global 

controller). The Spyder BACnet controllers are master devices 

on the MS/TP network. Each Spyder BACnet controller uses a 

high-quality EIA-485 transceiver and exerts 1/4 unit load on 

the MS/TP network.

Cabling should be selected that meets or exceeds the BACnet 

Standard which specifies the following: An MS/TP EIA-485 

network shall use shielded, twisted-pair cable with 

characteristic impedance between 100 and 130 ohms. 

Distributed capacitance between conductors shall be less 

than 100 pF per meter (30 pF per foot). Distributed 

capacitance between conductors and shield shall be less that 

200 pF per meter (60 pF per foot). Foil or braided shields are 

acceptable. The Honeywell tested and recommended MS/TP 

cable is Honeywell Cable 3322 (18 AWG, 1-Pair, Shielded, 

Plenum cable), alternatively Honeywell Cable 3251 (22 AWG, 

1-Pair, Shielded, Plenum cable) is available and meets the 

BACnet Standard requirements (www.honeywellcable.com).

The maximum BACnet MS/TP network Bus segment length is 

4,000 ft. (1,071 m) using recommended wire. Repeaters must 

be used when making runs longer than 4,000 ft. (1,071 m). A 

maximum of three repeaters can be used between any two 

devices.

Setting the MS/TP MAC address

The MS/TP MAC address for each device must be set to a 

unique value in the range of 0-127 on an MS/TP network 

segment (address 0, 1, 2, & 3 should be avoided as they are 

commonly used for the router, diagnostic tools, and as spare 

addresses). DIP switches on the Spyder BACnet controller 

are used to set the controller's MAC address.

To set the MS/TP MAC address of a Spyder BACnet 

controller:

1.

Find an unused MAC address on the MS/TP network to 

which the Spyder BACnet controller connects.

2.

Locate the DIP switch bank on the Spyder BACnet for 

addressing. This is labeled MAC Address

3.

With the Spyder BACnet Controller powered down, set 

the DIP switches for the MAC Address you want. Add 

the value of DIP switches set to ON to determine the 

MAC address. See Table 2. Example, if only DIP 

switches 1, 3, 5, and 7 are enabled the MAC address 

would be 85 (1 + 4 + 16 + 64 = 85).

Setting the Device Instance Number

The Device Instance Number must be unique across the 

entire BACnet system network because it is used to uniquely 

identify the BACnet devices. It may be used to conveniently 

identify the BACnet device from other devices during 

installation. The Spyder BACnet Controllers Device Instance 

Number is automatically set when it is added to a 

WEBStation-AX project. The Device Instance Number can be 

changed by the user, which may be necessary when 

integrating with a third party or when attempting to replace an 

existing controller and it is desired to maintain the existing 

Device Instance Number.

To edit the Device Instance Number using WEBs AX:

1.

Identify an unused Device Instance Number on the 

BACnet Network, in the range of 0 - 4194302.

2.

Open the Spyder Bacnet Device Mgr View

a. Double click on the BacnetNetwork located in the 

Nav tree.

b. Select the Spyder Controller to be modified.

c. Click on the Edit button.

d. Enter an unused value in the Device Id field.

M29685

120/240 

VAC 

TRANSFORMER OUTPUT 

DEVICE 

POWER 

Δ

1 2 3 4 5 6 7 8 

2 3 4 5 6 7 8  0 

1  1 1 1 1 1 1 1  2 

1 2 3 4 5 6 7 8  0 

2 2 

2 2 2 2 2 2  3 

1 2 3 4 5 6 7 8  0 

3 3 

3 3 

3 4 

COM 

24 VAC 

Δ

1 2 3 4 5 6 7 8 

2 3 4 5 6 7 8  0 

1  1 1 1 1 1 1 1  2 

1 2 3 4 5 6 7 8  0 

2 2 

2 2 2 2 2 2  3 

1 2 3 4 5 6 7 8  0 

3 3 

3 3 

3 4 

EARTH

GROUND (TERMINAL 3)

Δ

1 2 3 4 5 6 7 8 

2 3 4 5 6 7 8  0 

1  1 1 1 1 1 1 1  2 

1 2 3 4 5 6 7 8  0 

2 2 

2 2 2 2 2 2  3 

1 2 3 4 5 6 7 8  0 

3 3 

3 3 

3 4 

EARTH 

GROUND (TERMINAL 3) 

EARTH

GROUND (TERMINAL 3)

CONNECT POWER TO  

TERMINALS 1 AND 2 

EARTH

GROUND

Table 2. DIP Switch Values For MS/TP MAC Address.

DIP

7

6

5

4

3

2

1

VALUE

64

32

16

8

4

2

1

Summary of Contents for Spyder PUB6438S

Page 1: ...485 BACnet MS TP network communications network capable of baud rates between 9 6 and 115 2 kilobits Controllers are field mountable to either a panel or a DIN rail SPECIFICATIONS General Specifications Rated Voltage 20 30 Vac 50 60 Hz Power Consumption 100 VA for controller and all connected loads including the actuator on model PVB6436AS Controller Only Load 5 VA maximum models PUB6438S and PVB6...

Page 2: ...includes the direct coupled actuator with Declutch mechanism which is shipped hard wired to the controller The actuator mounts directly onto the VAV box damper shaft and has up to 44 lb in 5 Nm torque 90 degree stroke and 90 second timing at 60 Hz The actuator is suitable for mounting onto a 3 8 to 1 2 in 10 to 13 mm square or round VAV box damper shaft The minimum VAV box damper shaft length is 1...

Page 3: ...ise e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts on the centering clamp 8 mm wrench 70 8 88 5 lb in 8 10 Nm torque g When the actuator closes the damper rotates CCW either 45 or 60 degrees to fully close 3 If the damper rotates counterclockwise CCW to open and the angle of the damper open to closed is 90 degrees a Manually open the damper fully rotate counter clockw...

Page 4: ...nd pull the controller down and away from the DIN rail to release the bottom flex connectors Fig 6 Controller DIN rail mounting models PUB6438S and PVB6438NS Piping PVB6436AS and PVB6438NS Air flow Pickup For PVB6436AS and PVB6438NS connect the air flow pickup to the two restrictor ports on the controller see Fig 7 NOTES Use 1 4 inch 6 mm outside diameter with a 0 040 in 1 mm wall thickness plenum...

Page 5: ... short as possible Do not connect the universal input COM terminals analog output COM terminals or the digital input output COM terminals to earth ground The 24 Vac power from an energy limited Class II power source must be provided to the controller To conform to Class II restrictions U S only the transformer must not be larger than 100 VA Fig 8 depicts a single controller using one transformer I...

Page 6: ... controller are used to set the controller s MAC address To set the MS TP MAC address of a Spyder BACnet controller 1 Find an unused MAC address on the MS TP network to which the Spyder BACnet controller connects 2 Locate the DIP switch bank on the Spyder BACnet for addressing This is labeled MAC Address 3 With the Spyder BACnet Controller powered down set the DIP switches for the MAC Address you ...

Page 7: ...e to twist them together Deviation from this rule can result in improper electrical contact see Fig 11 Each terminal can accommodate the following gauges of wire Single wire from 22 AWG to 14 AWG solid or stranded Multiple wires up to two 18 AWG stranded with 1 4 watt wire wound resistor Prepare wiring for the terminal blocks as follows 1 Strip 1 2 in 13 mm insulation from the conductor 2 Cut a si...

Page 8: ... power from the controller 2 Remove the two air flow pickup connections from the pressure sensor 3 Remove the terminal blocks 4 Remove the old controller from its mounting IMPORTANT FOR CONTROLLERS MOUNTED TO A DIN RAIL 1 Push straight up from the bottom to release the top pins 2 Rotate the top of the controller outwards to release the bottom flex connectors see Fig 6 on page 4 5 Mount the new con...

Reviews: