INSTALLATION INSTRUCTIONS

62-0310-01

Spyder

®

 BACnet

®

Programmable, VAV/Unitary Controllers

 

PRODUCT DESCRIPTION

The PUB6438S, PVB6436AS and PVB6438NS controllers are 

part of the Spyder family. The three controllers are BACnet 

MS/TP network devices designed to control HVAC equipment. 

These controllers provide many options and advanced system 

features that allow state-of-the-art commercial building 

control. Each controller is programmable and configurable 

through software.

These controllers are for use in VAV (Variable Air Volume) and 

Unitary HVAC control applications. Each controller contains a 

host micro controller to run the main HVAC application and a 

second micro controller for BACnet MS/TP network 

communications. Each controller has flexible, universal inputs 

for external sensors, digital inputs, and a combination of 

analog and digital Triac outputs. The three models are 

described in Table 1. The photo to the left is the model 

PVB6436AS, which includes the actuator.

Table 1. Controller configurations.

Each controller communicates via an EIA-485 BACnet MS/TP network communications network, capable of baud rates between 

9.6 and 115.2 kilobits.
Controllers are field-mountable to either a panel or a DIN rail. 

SPECIFICATIONS

General Specifications

Rated Voltage:

 20–30 Vac; 50/60 Hz

Power Consumption:

 

100 VA for controller and all connected loads (including the 

actuator on model PVB6436AS).

Controller Only Load: 

5 VA maximum; models PUB6438S 

and PVB6438NS.

Controller and Actuator Load:

 9 VA maximum; model 

PVB6436AS.

External Sensors Power Output:

 20 Vdc ±10% @ 75 mA 

maximum.

VAV Operating & Storage Temperature Ambient Rating 

(models PVB6436AS and PVB6438NS):

Minimum 32 ºF (0 ºC); Maximum 122 ºF (50 ºC)

Unitary Operating & Storage Temperature Ambient Rating 

(model PUB6438S):

Minimum -40 ºF (-40 ºC); Maximum 150 ºF (65.5 ºC)

Relative Humidity:

 5% to 95% non-condensing

LED: 

Provides status for normal operation, controller down-

load process, alarms, manual mode, and error conditions

BEFORE INSTALLATION

The controller is available in three models (see Table 1).

Controller

Model

Programmable

Type

Universal

Inputs

(UI)

Digital

Inputs

(DI)

Analog

Outputs

(AO)

Digital

Outputs

(DO)

Velocity

Pressure

Sensor

(Microbridge)

Series 60

Floating

Actuator

PUB6438S

Unitary

6

4

3

8

NO

NO

PVB6436AS

VAV

6

4

3

6

YES

YES

PVB6438NS

VAV

6

4

3

8

YES

NO

Summary of Contents for Spyder PUB6438S

Page 1: ...485 BACnet MS TP network communications network capable of baud rates between 9 6 and 115 2 kilobits Controllers are field mountable to either a panel or a DIN rail SPECIFICATIONS General Specifications Rated Voltage 20 30 Vac 50 60 Hz Power Consumption 100 VA for controller and all connected loads including the actuator on model PVB6436AS Controller Only Load 5 VA maximum models PUB6438S and PVB6...

Page 2: ...includes the direct coupled actuator with Declutch mechanism which is shipped hard wired to the controller The actuator mounts directly onto the VAV box damper shaft and has up to 44 lb in 5 Nm torque 90 degree stroke and 90 second timing at 60 Hz The actuator is suitable for mounting onto a 3 8 to 1 2 in 10 to 13 mm square or round VAV box damper shaft The minimum VAV box damper shaft length is 1...

Page 3: ...ise e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts on the centering clamp 8 mm wrench 70 8 88 5 lb in 8 10 Nm torque g When the actuator closes the damper rotates CCW either 45 or 60 degrees to fully close 3 If the damper rotates counterclockwise CCW to open and the angle of the damper open to closed is 90 degrees a Manually open the damper fully rotate counter clockw...

Page 4: ...nd pull the controller down and away from the DIN rail to release the bottom flex connectors Fig 6 Controller DIN rail mounting models PUB6438S and PVB6438NS Piping PVB6436AS and PVB6438NS Air flow Pickup For PVB6436AS and PVB6438NS connect the air flow pickup to the two restrictor ports on the controller see Fig 7 NOTES Use 1 4 inch 6 mm outside diameter with a 0 040 in 1 mm wall thickness plenum...

Page 5: ... short as possible Do not connect the universal input COM terminals analog output COM terminals or the digital input output COM terminals to earth ground The 24 Vac power from an energy limited Class II power source must be provided to the controller To conform to Class II restrictions U S only the transformer must not be larger than 100 VA Fig 8 depicts a single controller using one transformer I...

Page 6: ... controller are used to set the controller s MAC address To set the MS TP MAC address of a Spyder BACnet controller 1 Find an unused MAC address on the MS TP network to which the Spyder BACnet controller connects 2 Locate the DIP switch bank on the Spyder BACnet for addressing This is labeled MAC Address 3 With the Spyder BACnet Controller powered down set the DIP switches for the MAC Address you ...

Page 7: ...e to twist them together Deviation from this rule can result in improper electrical contact see Fig 11 Each terminal can accommodate the following gauges of wire Single wire from 22 AWG to 14 AWG solid or stranded Multiple wires up to two 18 AWG stranded with 1 4 watt wire wound resistor Prepare wiring for the terminal blocks as follows 1 Strip 1 2 in 13 mm insulation from the conductor 2 Cut a si...

Page 8: ... power from the controller 2 Remove the two air flow pickup connections from the pressure sensor 3 Remove the terminal blocks 4 Remove the old controller from its mounting IMPORTANT FOR CONTROLLERS MOUNTED TO A DIN RAIL 1 Push straight up from the bottom to release the top pins 2 Rotate the top of the controller outwards to release the bottom flex connectors see Fig 6 on page 4 5 Mount the new con...