Honeywell Spyder BACnet PUB1012S Installation Instructions Manual Download Page 6

SPYDER® BACNET® PROGRAMMABLE CONTROLLERS

62-0310—04

6

NOTES:

For multiple controllers operating from a single 

transformer, the same side of the transformer 

secondary must be connected to the same power 

input terminal in each controller. Controller 

configurations will not necessarily be limited to 

three devices, but the total power draw, including 

accessories, cannot exceed 100 VA when 

powered by the same transformer (U.S. only). The 

earth ground terminal (terminal 3) must be 

connected to a verified earth ground for each 

controller in the group (see Fig. 11 on page 6).

All loads on the controller must be powered by the 

same transformer that powers the controller itself. 

A controller can use separate transformers for 

controller power and output power.

Keep the earth ground connection (terminal 3) 

wire run as short as possible.

Do not connect the universal input COM 

terminals, analog output COM terminals or the 

digital input/output COM terminals to earth 

ground.

The 24 Vac power from an energy limited Class II power 

source must be provided to the controller. To conform to Class 

II restrictions (U.S. only), the transformer must not be larger 

than 100 VA. 

Fig. 10 depicts a single controller using one transformer.

IMPORTANT

Power must be off prior to connecting to or removing 

connections from the 24 Vac power (24 Vac/24 Vac 

COM), earth ground (EGND), and 20 Vdc power (20 

Vdc) terminals.

IMPORTANT

Use the heaviest gauge wire available, up to 14 AWG 

(2.0 sq mm), with a minimum of 18 AWG (1.0 sq 

mm), for all power and earth ground wiring.

Screw-type terminal blocks are designed to accept 

up to one 14 AWG (2.0 sq mm) conductor or up to 

two 18 AWG (1.0 sq mm) conductors. More than two 

wires that are 18 AWG (2.0 sq mm) can be con-

nected with a wire nut. Include a pigtail with this wire 

group and attach the pigtail to the terminal block.

IMPORTANT

Connect terminal 2, (the 24 Vac common [24 VAC 

COM] terminal) to earth ground (see Fig. 10).

Fig. 10. Power wiring details for one controller per transformer.

More than one controller can be powered by a single 

transformer. Fig. 11 shows power wiring details for multiple 

controllers.

NOTE: Controller configurations are not necessarily limited 

to three devices, but the total power draw, including 

accessories, cannot exceed 100 VA when powered 

by the same transformer (U.S. only).

Fig. 11. Power wiring details for two or more controllers per transformer. 

M29684A

TRANSFORMER

OUTPUT

DEVICE

POWER

Δ

P

12345678

1

0

9

2345678 0

9

1

1 1111111 2

1

12345678 0

9

2

2 2222222 3

3

12345678 0

9

3

3

3

3

3

3

3

3 4

EARTH

GROUND

1

LINE VOLTAGE

GREATER

THAN 150 VAC

WHEN CONNECTIONG POWER TO THE SPYDER BACnet 

CONTROLLER, CONNECT THE COM LEG OF THE VAC SECONDARY 

CIRCUIT TO A KNOWN EARTH GROUND.

1

COM

24 VAC

CONNECT POWER TO 

TERMINALS 1 AND 2

M29685A

120/240

VAC

TRANSFORMER OUTPUT

DEVICE

POWER

Δ

P

12345678

1

0

9

2345678 0

9

1

1 1111111 2

1

12345678 0

9

2

2 2222222 3

3

12345678 0

9

3

3

3

3

3

3

3

3 4

COM

24 VAC

Δ

P

12345678

1

0

9

2345678 0

9

1

1 1111111 2

1

12345678 0

9

2

2 2222222 3

3

12345678 0

9

3

3

3

3

3

3

3

3 4

Δ

P

12345678

1

0

9

2345678 0

9

1

1 1111111 2

1

12345678 0

9

2

2 2222222 3

3

12345678 0

9

3

3

3

3

3

3

3

3 4

CONNECT POWER TO 

TERMINALS 1 AND 2

EARTH

GROUND

Summary of Contents for Spyder BACnet PUB1012S

Page 1: ...cations Rated Voltage 20 30 Vac 50 60 Hz Power Consumption 100 VA for controller and all connected loads including the actuator on models models PVL0000AS PVL4022AS and PVL6436AS Controller Only Load 5 VA maximum models PUB1012S PUB4024S PUB6438S PVB4024NS and PVB6438NS Controller and Actuator Load 9 VA maximum models PVL0000AS PVL4022AS and PVL6436AS External Sensors Power Output 20 Vdc 10 75 mA ...

Page 2: ...es to fully close on page 3 to begin the installation Mount Actuator onto Damper Shaft PVB0000AS PVB4022AS and PVB6436AS PVB0000AS PVB4022AS and PVB6436AS controllers include the direct coupled actuator with Declutch mechanism which is shipped hard wired to the controller The actuator mounts directly onto the VAV box damper shaft and has up to 44 lb in 5 Nm torque 90 degree stroke and 90 second ti...

Page 3: ...degrees Adjust the two mechanical end limit set screws to provide the desired amount of rotation Adjust the two set screws closer together to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 26 5 31 lb in 3 0 3 5 Nm torque d Using the Declutch button rotate the universal shaft adapter fully clockwise e Mount the actuator to the VAV damper box and shaf...

Page 4: ...NTATION M33229 8 9 32 211 1 15 16 49 6 9 32 159 3 16 4 5 PANEL MOUNTING HOLE 4X 27 32 21 4 1 8 105 6 1 4 159 5 7 8 149 DEPTH IS 2 1 4 57 1 1 1 1 1 1 1 1 1 1 2 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 1 0 9 2 3 4 5 6 7 1 1 1 1 1 1 1 1 1 2 3 4 5 6 7 8 0 9 2 2 2 2 2 2 2 2 2 3 3 1 2 3 4 5 6 7 8 0 9 3 3 3 3 3 3 3 3 4 5 3 4 146 10 5 16 262 NOTE CONTROLLER CAN BE MOUNTED IN ANY ...

Page 5: ...mm outside diameter with a 0 040 in 1 mm wall thickness plenum rated 1219 FR 94V 2 tubing Always use a fresh cut on the end of the tubing that connects to the air flow pickups and the restrictor ports on the controller Connect the high pressure or upstream tube to the plastic restrictor port labeled and the low pressure or down stream tube to the restrictor port labeled See labeling in Fig 9 When ...

Page 6: ...or all power and earth ground wiring Screw type terminal blocks are designed to accept up to one 14 AWG 2 0 sq mm conductor or up to two 18 AWG 1 0 sq mm conductors More than two wires that are 18 AWG 2 0 sq mm can be con nected with a wire nut Include a pigtail with this wire group and attach the pigtail to the terminal block IMPORTANT Connect terminal 2 the 24 Vac common 24 VAC COM terminal to e...

Page 7: ...led the MAC address would be 85 1 4 16 64 85 Setting the Device Instance Number The Device Instance Number must be unique across the entire BACnet system network because it is used to uniquely identify the BACnet devices It may be used to conveniently identify the BACnet device from other devices during installation The Spyder BACnet Controllers Device Instance Number is automatically set when it ...

Page 8: ...erminal blocks 4 Remove the old controller and actuator assembly from its mounting Loosen the two bolts on the actuator clamp to release the actuator from the shaft Remove the controller s mounting screws Gently pull the controller and actuator assembly straight out until the assembly is clear of the actuator shaft AO 1 COM AO 2 AO 3 COM UI 1 COM UI 2 UI 3 COM UI 4 UI 5 COM UI 6 DI 1 DI 2 COM DI 3...

Page 9: ...the bottom flex connectors see Fig 8 on page 5 5 Mount the new controller See Installation on page 2 6 Reconnect the two air flow pickup tubes to the pressure sensor See Piping PVB0000AS PVB4022AS PVB4024NS PVB6436AS and PVB6438NS on page 4 7 Replace the terminal blocks Insert each terminal block onto its alignment pins Press straight down to firmly seat it Repeat for each terminal block 8 Restore...

Page 10: ...SPYDER BACNET PROGRAMMABLE CONTROLLERS 62 0310 04 10 ...

Page 11: ...SPYDER BACNET PROGRAMMABLE CONTROLLERS 11 62 0310 04 ...

Page 12: ... Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 62 0310 04 S B Rev 12 11 Printed in United States ...

Reviews: