background image

GAS LEAK DETECTOR INSTALLATION & USER GUIDE 

3. POWER SUPPLY 

The Power supply is connected at Con 1 (see Fig. 1) 

Green LED on  - shows power connected. 

Pin 1 = 0V, 

Pin 2 = 12 to 24 VAC or 12 to 30VDC, 

Pin 3 = Earth. 

 
The 0V (pin 1) on the power supply terminal block (CON 1) can withstand 50V 
AC or DC with respect to the 0V (Pin 1) on the output terminal block (CON 3). If 
this is likely to be exceeded use an isolated power supply.   

 

On the power supply side 12V is the minimum voltage at the terminals. Power 

consumption is 4W max. It can draw 0.33Amp at 12V, so voltage drop along the 

supply cable should be considered when selecting supply cable, type and length.  For 

example, for cable resistance 10ohm/100m allowing for the flow and return total cable 

resistance for 100m is 20ohm and voltage drop along the cable is 6.6V.  Minimum DC 

supply then should be 19V. 

 

If you need to use a cable of greater diameter that 1.5 mm sq, you can use a terminal 

block at each sensor position capable of taking the larger cable and connect from that 

into the CON1 terminal block using 1mm sq wire.  Alternatively use local power 

supplies to reduce cable runs and voltage loss. 

 

 

4. ANALOGUE OUTPUTS  

Analogue Outputs which indicate the concentration of gas refrigerant in the air, are at 

Con 3 (see Figure 1.) 

A two-core communication cable should be used to connect the outputs to a 

monitoring and control system; a screen is not required.  

 

Pin 1 = 0V 

Pin 2 = 4-20mA.  Load resistance must be less than 400

   

Pin 3 = 0-10V. 

Load resistance must be greater than 100

 

Pin 4 = 0-5 V. 

Load resistance must be greater than 10K

 

 

When connecting the 4-20mA to the control panel, we suggest using Belden 8761, 

22awg single pair shielded or alternatively an alarm type cable of 7/0.2mm, 22awg. 

 

 

 

EN1B-0014UK07 R0404 

4

 

Summary of Contents for SN0500

Page 1: ...SN0500 SN0501 REFRIGERANT GAS LEAK DETECTOR INSTALLATION USER GUIDE Copyright 2004 Honeywell Control Systems Ltd All Rights Reserved EN1B 0014UK07 R0404 ...

Page 2: ...s without notification Honeywell shall not be liable for errors or for incidental or consequential damages directly or indirectly in connection with the furnishing performance or misuse of this product or document All Installation and Commissioning work on Honeywell equipment should be carried out by suitably qualified personnel only Normal safety precautions and good working practice should be ob...

Page 3: ...cable gland inside the enclosure The connectors will accept wire of 0 5 1 5mm sq Note Earth connection must be made when using the vented metal enclosure or Exd enclosure The safety of this equipment is dependent on the integrity of the power supply and the earthing of the enclosure On power up the sensor may take some time minutes up to hours to fully normalize You can monitor this by checking th...

Page 4: ...rop along the cable is 6 6V Minimum DC supply then should be 19V If you need to use a cable of greater diameter that 1 5 mm sq you can use a terminal block at each sensor position capable of taking the larger cable and connect from that into the CON1 terminal block using 1mm sq wire Alternatively use local power supplies to reduce cable runs and voltage loss 4 ANALOGUE OUTPUTS Analogue Outputs whi...

Page 5: ...ed position Default settings are Position 1 No delay Position 2 1 Minute Position 3 5 Minutes Position 4 10 Minutes Note If changing any jumper power must be removed Relay 2 at Con 7 High level alarm Red LED on when in alarm Normally open closed when JP5 link inserted as shown on Fig 1 Latching manual reset by push button located next to CON 7 Not latching automatic reset set by JP7 see Fig 1 for ...

Page 6: ... removed as shown on Fig 1 Latching manual reset by push button located next to CON 7 Not Latching set by JP8 see Fig 1 in Connection Instructions Alarm Threshold level set by RV1 and can be set by putting a meter between TP0 negative and TP2 positive and adjusting RV1 scale is 0 to 5V e g 2 5V is 50 of scale Delayed response time set by JP1 link see Fig 1 in External Connections Position 1 No del...

Page 7: ... not used CON2 10 Display Connection not used CON3 1 Analogue Output 0V CON3 2 Analogue Output 4 20mA load resistance 400Ω CON3 3 Analogue Output 0 10V load resistance 100Ω CON3 4 Analogue Output 0 5V load resistance 10KΩ CON4 1 Plug in detection sensor module CON4 2 Plug in detection sensor module CON4 3 Plug in detection sensor module CON4 4 Plug in detection sensor module CON4 5 Plug in detecti...

Page 8: ...l Solutions Refrigeration Control Newhouse Industrial Estate Motherwell Lanarkshire ML1 5SB Phone 44 01698 481698 Fax 44 01698 481699 www honeywell com refrigeration Subject to change without notice EN1B 0014UK07 R1204 ...

Reviews: