33
Commissioning
NOTE:
If you select WIPE Config, the panel will return to the factory settings and all the existing settings will
be deleted automatically.
Panel Description
Blank
20 character
text
Configure text for Pane Description to
be used.
Phone Number
Blank
20 character
text
Configure phone number of service/
maintenance provider.
Service Date
01 Jan 2000
Date
Set service date based on agreed main
-
tenance schedule. User can view this
information along with the Site Name
Reference and phone number of the
service provider.
No. of Fault Polls
4
4,5,6
Number of consecutive polls required
before device faults are reported.
This setting applies to: DEVICE LEVEL
FAULT, DOUBLE ADDRESS FAULT, NO
REPLY FROM DEVICE, BAD DEVICE
REPLY, DEVICE ADDED, DEVICE NOT
SUPPORTED, DEVICE TYPE CHANGED.
Device Blinking
ON
ON / OFF
Determines if the detector’s LED flashes
when the device is polled by the panel.
Access Timeout
10 Mins 00
Sec
0 - 60 Mins
After Access Timeout period, screen
automatically logout and navigated
back to the main screen.
Log Diagnostic
OFF
ON / OFF
When set as ON, false alarm suppres
-
sion algorithms are by-passed for faster
reporting of events.
Printer
ON
ON / OFF
Allows printing of the events reported in
the panel via an external printer, which
can be connected to the RS232 port of
the panel.
Table 6: Default Panel Settings
Option Title
Default
Setting
Options
Description