Configuration & Operation
Item
Operation
Display
Proportional
Band Setting
• Press “SELECT” to choose “P BAND”.
• Press key
S
1 time “ST” will be 1
0
C up. The range is 2-19
0
C. Hold the key 2 seconds up; the temperature
increases continuously until reaches 19
0
C. Press the button again, temperature change stops.
• Press key
T
1 time “ST” will be 1
0
C down. The range is 19-2
0
C. Hold it 2 seconds up, the temperature
decreases continuously until reaches 2
0
C. Press the button again, temperature change stops.
• Press, “ENTER” button to save setting value.
Offset Setting
• Press “SELECT” to choose “OFFSET”.
• Press key
S
1 time “ST” will be 0.5c up; the range is from –3 to 3
0
C. Hold the key in 2 seconds; the
temperature increases continuously until reaches 3
0
C. Press the button again, temperature change stops.
• Press key
T
1 time, “ST” will be 0.5
0
C down; the range is from 3 to-3
0
C. Hold the key in 2 seconds, the
temperature decreases continuously until reaches –3
0
C. Press the button again, temperature change stops.
• Press, “ENTER” button to save setting value.
Mode Setting
• Press “SELECT” to choose “MODE”.
• Press key
S
1 time “ST” will be 1 up, the range is 0-6
0: output1—cooling output2--no function
1: output1--heating output2--no function
2: output1—cooling output2--heating
3: output1--heating output2--cooling
4: output1—cooling output2--low temperature limit
5: output1--heating output2--high
temperature limit
• When the value reaches 5, the setting value will not change.
• Press key
T
1 time “ST” will be 1 down until to 0, then no change if continue to press the key.
• Press, “ENTER” button to save setting value.
Sensor
Setting
• Press “SELECT” to choose “SENSOR”.
• Press key
S
“ST”, the value switches between 0 and 1: 0
Æ
internal sensor
1
Æ
external sensor
• Press key
T
“ST”, the value switches between 1 and 0
• Press, “ENTER” button to save setting value.