SLATE
™
FUEL AIR RATIO MODULE
13
R8001C6001
Specifications based on worst case over ambient temperatures.
Complex Functions
Min
Typical Max
Units
Thermocouple
T2 &
T3
Type J
Range
-200.0
1025.0 °C
Resolution -
0.1
-
°C
Accuracy -5.0
-
5.0
°C
Type K
Range
-150.0 -
1000.0 °C
Resolution -
0.1
-
°C
Accuracy -5.0
-
5.0
°C
RTD
T2 &
T3 &
T4
Type PT100
a
Range
-135.0 -
250.0
°C
3 wire, 100 Ω
Resolution -
0.5
-
°C
Accuracy -2.0
-
2.0
°C
Type PT1000 Range
-135.0 -
250.0
°C
3 wire, 1000 Ω
Resolution
0.5
°C
Accuracy -2.0
-
2.0
°C
NTC
T1-
T3,
T1-
T4
Type 10K
Range
-40.0
b
-
175.0
°C
T4 rated to 0 °C
Resolution -
0.1
-
°C
Accuracy
c
-2.0
-
2.0
°C
-40 °C to 25 °C
-1.0
-
1.0
°C
25 °C to 125 °C
-1.5
-
1.5
%
-3.0
-
3.0
°C
125 °C to 175 °C
T1-
T3,
T1-
T4
Type 12K
Range
-20.0
-
125.0
°C
T4 rated to 0 °C
Resolution -
0.1
-
°C
Accuracy
c
-2.0
-
2.0
°C
-20 °C to 30 °C
-1.0
-
1.0
°C
30 °C to 120 °C
-1.5
-
1.5
%
-3.0
-
3.0
°C
120 °C to 125 °C
T1-
T3,
T1-
T4
Type 20K
Range
-25.0
-
150.0
°C
T4 rated to 0 °C
Resolution -
0.1
-
°C
Accuracy
c
-2.0
-
2.0
°C
-25 °C to 50 °C
-1.0
-
1.0
°C
50 °C to 135 °C
-1.5
-
1.5
%
-3.0
-
3.0
°C
135 °C to 150 °C
a
Shielded cable required for reliable operation in noisy environment.
b
NTC on terminal T4 is rated down to 0 °C.
c
Temperatures refer to sense range.
Table 5. Specifications Cell Complex Functions.