background image

10

 32-00009—01

Terminal

Description

Rating

1

Cell A (T1)

See Tables Table 4-Table 7 for configuration 
options

2

Cell A (T2)

See Tables Table 4-Table 7 for configuration 
options

3

Cell A (T3)

See Tables Table 4-Table 7 for configuration 
options

4

Cell A (T4)

See Tables Table 4-Table 7 for configuration 
options

5

Cell B (T5)

See Tables Table 4-Table 7 for configuration 
options

6

Cell B (T6)

See Tables Table 4-Table 7 for configuration 
options

7

Cell B (T7)

See Tables Table 4-Table 7 for configuration 
options

8

Cell B (T8)

See Tables Table 4-Table 7 for configuration 
options

9

Cell C (T9)

See Tables Table 4-Table 7 for configuration 
options

10

Cell C (T10)

See Tables Table 4-Table 7 for configuration 
options

11

Cell C (T11)

See Tables Table 4-Table 7 for configuration 
options

12

Cell C (T12)

See Tables Table 4-Table 7 for configuration 
options

13

Cell D (T13)

See Tables Table 4-Table 7 for configuration 
options

14

Cell D (T14)

See Tables Table 4-Table 7 for configuration 
options

15

Cell D (T15)

See Tables Table 4-Table 7 for configuration 
options

16

Cell D (T16)

See Tables Table 4-Table 7 for configuration 
options

17

Unused

---

18

Unused

---

19

Unused

---

20

Unused

---

21

Unused

---

22

Unused

---

Table 3. Terminal Ratings.

Summary of Contents for SLATE R8001U3001

Page 1: ...SLATE Analog I O Module R8001U3001 INSTALLATION INSTRUCTIONS ...

Page 2: ...Scan for more information ...

Page 3: ...res 4 analog cells per module Multiple combination of analog functionality for each cell Supported sensors include voltage current PWM tach RTD NTC and thermocouple Specifications Electrical Ratings See Table 3 Table 7 Environmental Ratings Ambient Temperature Operating 20 F to 150 F 29 C to 66 C Shipping 40 F to 150 F 40 C to 66 C Humidity 95 continuous noncondensing Vibration 0 5G environment Di...

Page 4: ...01 Mounting DIN Rail See Fig 2 Required Components R8001A1001 SLATE Base Controller R8001S9001 SLATE Sub Base Module Fig 1 M35382 4 19 32 117 7 3 32 181 2 11 16 68 Mounting dimensions of analog I O module in in mm ...

Page 5: ...le module s There are also four banks of LEDs for the analog cells See Table 1 for descriptions LED Color Description Power No light System does not have power Green System has power CPU Red No wire sheet or problem with the wire sheet Green Running Fault Red Fault No light Running Table 1 LED Descriptions LED Display The SLATE system modules have a seven segment three position LED display used fo...

Page 6: ...When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 After installation is complete check out the product operation as provided in these instructions 4 The SLATE module must be mounted...

Page 7: ...stalled and used in accordance with these instructions may cause interference for radio communications It has been tested and found to comply with the limits of a Class A computing device of part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area may cause interfer...

Page 8: ...s 3 Cable shield must be terminated to ground at both ends If shielded cable is NOT used use three wire twisted cable Wiring WARNING Electrical Shock Hazard Can cause severe injury death or equipment damage Disconnect the power supply from the main disconnect before beginning installation to prevent electrical shock and equipment damage More than one disconnect can be required ...

Page 9: ...3 M35287 ANALOG INPUT OUTPUT MODULE 4 CELLS A UNIVERSAL LOW VOLTAGE CELL _ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 _ _ _ B UNIVERSAL LOW VOLTAGE CELL C UNIVERSAL LOW VOLTAGE CELL D UNIVERSAL LOW VOLTAGE CELL Wiring diagram for Analog I O Module ...

Page 10: ...options 8 Cell B T8 See Tables Table 4 Table 7 for configuration options 9 Cell C T9 See Tables Table 4 Table 7 for configuration options 10 Cell C T10 See Tables Table 4 Table 7 for configuration options 11 Cell C T11 See Tables Table 4 Table 7 for configuration options 12 Cell C T12 See Tables Table 4 Table 7 for configuration options 13 Cell D T13 See Tables Table 4 Table 7 for configuration op...

Page 11: ...x Load 500 Ω Resolution 4 0 mA Ω Null 0 5 0 5 mA DC Accuracy 300 0 300 0 uA DC 0 to 25 mA 50 0 50 0 uA DC 4 to 20 mA T2 Voltage In Amplitude 0 0 15 0 VDC Trip Point 3 0 VDC Comparator Only Hysteresis 0 25 VDC Resolution 0 37 mV DC Null 25 0 25 0 mV DC Accuracy 25 0 25 0 mV DC T3 Voltage In Range 0 0 15 0 VDC Resolution 0 37 mV DC Null 25 0 25 0 mV DC Accuracy 25 0 25 0 mV DC Current In Range 0 2 2...

Page 12: ...5 0 C RTD T3 T4 PT100 Range 135 0 250 0 C 3 wire 100 Ω Resolution 0 5 C Accuracy 2 0 2 0 C Type PT1000 Range 135 0 250 0 C 3 wire 1000 Ω Resolution 0 5 C Accuracy 2 0 2 0 C NTC T3 T4 Type 10K Range 40 0 175 0 C Resolution 0 1 C Accuracya 2 0 2 0 C 40 C to 25 C 1 0 1 0 C 25 C to 125 C 1 5 1 5 3 0 3 0 C 40 C to 175 C a Temperatures refer to sense range Table 5 Specifications Cell Complex Functions ...

Page 13: ...V amplitude Min off pulse width high DC 130 0 usec 10V amplitude Duty Cycle 2 100 Hz 2 0 98 0 DC 10V amplitude 1000 Hz 5 0 85 0 DC 10V amplitude Resolution 1 Hz Accuracy 5 0 0 Whichever is greater 1 0 Hz PWM In T2 Amplitude 5 0 10 0 15 0 VDC Frequency 125 500 Hz Min on pulse width low DC 50 0 usec 10V amplitude Min off pulse width high DC 130 0 usec 10V amplitude Duty Cycle 125 500 Hz 5 0 90 0 DC ...

Page 14: ...s and Part Numbers Recommended Grounding Practices Use an Earth ground or a signal ground as described below Earth ground Base Rectification Flame Amp Module other modules optional 1 Use to provide a connection between the base and the control panel of the equipment Earth ground must be capable of conducting enough current to blow the breaker in the event of an internal short circuit 2 Use wide st...

Page 15: ...e connected to earth ground Be sure loads do not exceed the terminal ratings Refer to the labels or terminal ratings in Table 3 The SLATE system must be mounted in an electrical enclosure When mounting in an electrical enclosure provide adequate clearance for servicing installation and removal of SLATE modules The maximum leadwire length is 300 feet to terminal inputs Control Running Lockout Inter...

Page 16: ...2 customer honeywell com U S Registered Trademark 2014 Honeywell International Inc 32 00009 01 M S 12 14 Printed in U S A 32 00009 01 For more information on the R8001U3001 and the entire SLATE system please refer to the SLATE User Guide document located on our website at http combustion honeywell com SLATE ...