Honeywell SLATE R8001S9001 Installation Instructions Manual Download Page 4

4

 32-00025—01

Terminal

Description

Rating

4

B (Remote Bus 
RS485)

Used for Remote mount-
ed flame amplifiers

5

A (Remote Bus 
RS485)

Used for Remote mount-
ed flame amplifiers

Table 1. Terminal Ratings.

Environmental Ratings

Ambient Temperature:

Operating: -20°F to +150°F (-29°C to +66°C).
Shipping: -40°F to +150°F (-40°C to +66°C)

Humidity: 95% continuous, noncondensing.
Vibration: 0.5G environment

Dimensions: 

 See Fig. 1.

Weight

:  5 oz (136 g)

Approvals

Underwriters Laboratories Inc. Listed, File: MP286
IRI acceptable.
Federal Communications Commission: Part 15, Class A 
Emissions.

Mounting

DIN Rail (See Fig. 3)

Required Components

R8001A1001 SLATE Base Module
Any other SLATE modules
Optional 5-position terminal block for remote flame amplifier or 
remote reset button connections (Phoenix Contact p/n 1754504 
or equivalent). See Fig. 2.

Summary of Contents for SLATE R8001S9001

Page 1: ...SLATE Sub Base Module R8001S9001 INSTALLATION INSTRUCTIONS ...

Page 2: ...Scan for more information ...

Page 3: ... a panel All SLATE modules need this sub base except for the SLATE Base Module Features Quick mount to standard DIN Rail Locking mechanism Provides bus connectivity to all modules Connections for remote mounted flame amplifiers remote bus and remote pushbutton reset Specifications Electrical Ratings Voltage and Frequency from the Base 18 VDC 1 VDC Maximum Total Connected Load 2 5A Terminal Ratings...

Page 4: ...0 C to 66 C Humidity 95 continuous noncondensing Vibration 0 5G environment Dimensions See Fig 1 Weight 5 oz 136 g Approvals Underwriters Laboratories Inc Listed File MP286 IRI acceptable Federal Communications Commission Part 15 Class A Emissions Mounting DIN Rail See Fig 3 Required Components R8001A1001 SLATE Base Module Any other SLATE modules Optional 5 position terminal block for remote flame...

Page 5: ...SLATE Sub Base Module 5 R8001S9001 Fig 1 M35384 1 5 32 29 7 3 32 180 2 21 32 67 3 13 32 86 Dimensions in in mm ...

Page 6: ...2 00025 01 Fig 2 M35430 TERMINAL DESCRIPTION 1 18V POWER 2 18V GROUND 3 REMOTE RESET BURNERCONTROLAND LIMIT MODULES ONLY 4 B REMOTE BUS RS485 5 A REMOTE BUS RS485 1 2 3 4 5 Sub base module wiring terminals ...

Page 7: ...ation When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application Mounting 1 The sub base module can be mounted on type C 20 DIN rail 2 Mount the sub base module first The sub base has locking ...

Page 8: ...O DIN RAIL Sub base locking mechanisms 3 Slide sub base on the DIN rail and lock into place 4 When securing subsequent sub base modules make sure communication ports are aligned and locked into place See Fig 4 Fig 4 M35386 Connecting additional sub base modules ...

Page 9: ...EC Class 1 Line Voltage wiring Application Recommended Wire Size Recommended Part Numbers Communication Lines 22 AWG two wire twisted pair with ground or five wire Belden 8723 shielded cable or equivalent Other terminals 18 AWG wire insulat ed for voltages and temperatures for given application TTW60C THW75C THHN90C Table 2 Recommended Wire Sizes and Part Numbers IMPORTANT This equipment generates...

Page 10: ...o provide a connection between the base and the control panel of the equipment Earth ground must be capable of conducting enough current to blow the breaker in the event of an internal short circuit 2 Use wide straps or brackets to provide minimum length maximum surface area ground conductors If a leadwire is required use 14 AWG copper wire 3 Verify that mechanically tightened joints along the gro...

Page 11: ...ical enclosure When mounting in an electrical enclosure provide adequate clearance for servicing installation and removal of SLATE modules Maximum Wire Length The maximum leadwire length is 300 feet to terminal inputs Control Running Lockout Interlock For remote reset leadwires maximum length to remote pushbutton is 1000 feet For remote bus data lines maximum cable length depends on the number of ...

Page 12: ...2 customer honeywell com U S Registered Trademark 2014 Honeywell International Inc 32 00025 01 M S 11 14 Printed in U S A For more information and detailed instructions on the SLATE display please refer to the SLATE User Guide document located on our website at http combustion honeywell com SLATE 32 00025 01 ...

Reviews: