INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-3443-000

7550 Meridian Circle, Maple Grove, MN 55369-4927

763.493.6455, 800.328.0103; Fax: 763.493.6475

http://www.silentknight.com

SK-Mon-10 Ten Input Monitor Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

3.5 mA

Alarm Current: 

55 mA (assumes all ten LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% Non-condensing 

Dimensions: 

6.8˝ H x 5.8˝ W x 1.25˝ D 

Accessories: 

IDP-ACB Cabinet and Chassis

Wire Gauge: 

12-18 AWG

Maximum IDC

Wiring Resistance: 

1500 Ohms

Maximum IDC Voltage: 

10.2 VDC

Maximum IDC Current: 

240 µA (each circuit)

BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably 
grounded.

NOTICE:

 This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The SK-Mon-10 Ten Input Monitor Module is intended for use in an intelligent 
alarm system. Each monitor module is intended to interface between a control 
panel and normally open contact devices, such as pull stations. A common 
SLC  input  is  used  for  all  modules,  and  the  initiating  device  loops  share  a 
common supervisory supply and ground. Otherwise, each monitor operates 
independently from the others. Each module has its own unique address.

A  pair  of  rotary  code  switches  is  used  to  set  the  address  of  the  first  mod-
ule  from  01  to  150  (01  to  90  on  panels  that  support  up  to  99  addresses). 
The  remaining  modules  are  automatically  assigned  to  the  next  nine  higher 
addresses. Provisions are included for disabling a maximum of two unused 
modules to release the addresses to be used elsewhere. Each module also has 
panel controlled green LED indicators. The panel can cause the LEDs to blink, 
latch on, or latch off.

C0202-00

ShIPPED ON BOARD:

(1)  Shunt in Class A/B position
 

(Shipped in Class B position, remove shunt for Class A

)

INCLUDED:

(6) 1 x 4 Terminal Blocks    (2) 1

1

/

4

˝ (32mm) Stand offs

(4) Machine Screws    (3) Shunts       (10) 47k Ohm
 

 

 

 

 

 

 

 

End of Line Resistors

(2) Nuts

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Silent Knight system control panel.  

COMPONENTS

The following is a description of the SK-Mon-10 mounting framework:

One  or  two  SK-Mon-10  modules  can  be  installed  in  an  IDP-ACB  cabi-

• 

net.

The IDP-ACB cabinet has a built-in chassis that will accommodate one or two 
SK-Mon-10 modules.

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

BASE 

ADDRESS

ADDRESS

DISABLE

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

BASE 

ADDRESS

ADDRESS

DISABLE

10

11

12

13

14

15

C0234-05

FIGURE 1: IDP-ACB CABINET

The front SK-Mon-10 module positions of each chassis are offset below the 
rear SK-Mon-10 module positions so that all of the status indicators are visible. 
For cabinet dimensions refer to the IDP-ACB instruction manual.