SiX
TM
Series
SiXGB
Installation Instructions
The SiXGB is a wireless glassbreak detector intended for use with Honeywell controls that support SiX™ Series
devices.
Mounting Guidelines
The SiXGB can be mounted on the
wall or on the ceiling:
•
within 7.6 m (25 feet) of the
protected glass
•
within clear view of the protected
glass
•
at least 2 m (6.5 feet) from the floor
•
at least 1 m (3.3 feet) from forced
air ducts
•
at least 1 m (3.3 feet) from sirens or
bells greater than 5 cm (2 inches) in
diameter
•
between the protected glass and
any heavy window coverings
•
when heavy window coverings are
present, the detector can be
mounted on the window frame
•
Avoid mounting the detector on the
same wall as the protected glass,
on free-standing posts or pillars, or
in rooms with noisy equipment (air
compressors, bells, power tools,
etc.), if this equipment is operated
when the detector is armed.
> 2.0m (6.5')
Optimal
Satisfactory
No
> 1m
(3.3')
< 7.6m (25')
> 1m
(3.3')
> 5 cm
(2”) Diameter
R
F
6
G
B-
W
a
ll
M
o
u
n
t
W all Mount
( To pView)
Do NOT mo unt o n
c o lumns, po sts o r po le s.
Glass
Ceiling Mount
( Side View)
RF6GB-Ceiling Mo unt
Ceiling
Glass
Flo o r
To remove the mounting bracket:
Turn the top of the detector 15 degrees counter-
clockwise and separate the mounting bracket.
NOTE
: Before mounting the device permanently,
conduct Go/No Go tests (see controller’s
instructions) to verify adequate signal strength and
adjust the device location and orientation as
necessary.
The rear tamper plate MUST be mounted to a stud,
solid wood, or with a robust wall anchor.
3.5 mm x 25 mm
(#6 x 1")
[2]