Honeywell Silent Knight SK-Monitor Installation And Maintenance Instructions Download Page 2

figure 3. typical 2-Wire initiating circuit configuration, nfpa Style B or Security SyStemS:

NOTE: For UL Listed security installations, the SK-Monitor must be mounted within the control panel enclosure. 

(+)

(–)

(+)

(–)

(+)

(–)

MONITOR 

MODULE

ANY NUMBER OF UL LISTED CONTACT 

CLOSURE DEVICES MAY BE USED. DO NOT MIX 

FIRE ALARM INTIATING, SUPERVISORY, OR 

SECURITY DEVICES ON THE SAME MODULE.

TO NEXT 

DEVICE

FROM PANEL OR 

PREVIOUS DEVICE

47K EOL 

RESISTOR 

ELR-47K

CONNECT MODULES TO LISTED COMPATIBLE  

CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMENDED

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B 

POWER LIMITED: 450µA MAX. @ 11 VDC MAX

INSTALL CONTACT CLOSURE DEVICES PER 

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

C0918-00

figure 4. typical 4-Wire fault tolerant initiating circuit configuration, nfpa Style D:

(+)

(-)

(+)

(–)

(+)

(–)

TO NEXT 

DEVICE

ANY NUMBER OF UL LISTED CONTACT 

CLOSURE DEVICES MAY BE USED. DO NOT MIX 

FIRE ALARM INTIATING, SUPERVISORY, OR 

SECURITY DEVICES ON THE SAME MODULE.

MONITOR 

MODULE

FROM PANEL OR 

PREVIOUS DEVICE

CONNECT MODULES TO LISTED COMPATIBLE 

CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMENDED

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

INSTALL CONTACT CLOSURE DEVICES PER 

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

EOL RESISTOR IS 

INTERNAL AT 

TERMINALS 8 & 9

C0919-00

SK-460-013 

I56-3442-000 

 

 

©2009 Silent Knight