Model SK-5208 Fire Control/Communicator Installation and Operation Manual
4-20
P/N 151204
Relay Options
Silence Relay
_ _ _ _
No Relays
selected
If a relay is selected, that relay can be silenced for
Trouble and Supervisory conditions only. (This
includes relays programmed for AC Trbl.)
Fire Relay
1 _ _ _
Relay 1
selected
If a relay is selected, that relay will activate for fire
alarm conditions.
Prealarm Relay
_ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
prealarm conditions.
Aux Relay
_ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
Auxiliary conditions.
Waterflow Relay
_ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
waterflow conditions.
Superv Relay
_ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
supervisory conditions.
Crossalert A Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
crossalarm conditions.
Release A Relay
_ _ _ _
No Relays
selected
If selected will activate for releasing group “A”.
Crossalert B Relay _ _ _ _
No Relays
selected
If a relay is selected, that relay will activate for
crossalarm conditions.
Release B Relay
_ _ _ _
No Relays
selected
If selected will activate for releasing group “B”.
Trouble Relay
_ _ _ 4
4
Relay will be activated when no troubles exist and
will deactivate when a trouble condition occurs.
Fire Drill Relay
1 _ _ _
Relay 1
selected
If a relay is selected, that relay will activate for fire
drills.
AC Trbl
_ _ _ _
No Relays
selected
If a relay is selected, that relay will be activated
when AC is normal and will deactivate when a
Low AC condition exists.
User (1-10) #
Code
Code # Type
Installers
5208 and
123456
Operators
1111
Not Used
User # Code
Enter 3 to 6 digit
number
Enter any value from 001 to 999999.
Table 4-4: Programming Options
Programming
Option
Menu Item
Choices
Default
Comments
firealarmresources.com
Summary of Contents for SILENT KNIGHT SK-5208
Page 2: ...firealarmresources com ...
Page 8: ...Installation Manual iv firealarmresources com ...
Page 9: ...Contents v firealarmresources com ...
Page 10: ...Installation Manual vi firealarmresources com ...
Page 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Page 118: ...firealarmresources com ...
Page 120: ...Cut Along the Dotted Line firealarmresources com ...
Page 121: ...firealarmresources com ...