IFP-2000 Installation Manual
4-32
151430
2. Configure the circuit through programming (see Section 9.5))
Figure 4-32 Class B Notification Appliance Circuit Wiring
Maximum voltage drop per Class B notification circuit is 3V. See Table 4-3
Table 4-3 Maximum Impedance Class B
Current
Maximum Impedance
1.0A
3
Ω
1.5A
2
Ω
2.0A
1.5
Ω
2.5A
1.2
Ω
3.0A
1.0
Ω
Alarm Polarity
Shown.
Supervised
Power Limited
Notification Wiring
Regulated 24 VDC
3A per Circuit, 9A max Combined
UL Listed EOL
Model 7628
4.7 k
Ω
firealarmresources.com