IFP-2000 Installation Manual
4-20
151430
4.8
5824 Serial/Parallel Interface Module
Installation
The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you
can print a real-time log of system events. Instructions for installing the 5824 appear below.
The 5824 is for ancillary use only.
5824 installation involves the following steps:
1. Make sure power is off at the panel.
2. Connect the 5824 to the panel as shown in Figure 4-20.
Note: Two 5824s per panel maximum.
3. Use the DIP switches on the 5824 board to assign an ID# to the 5824 (see Section 4.5.1).
4. Configure the 5824 device through programming. See Section 4.8.1.
5. Connect a printer to the 5824 as shown in Figure 4-21.
Figure 4-20 5824 Connection to the Panel
Supervised
Power Limited
Model 5824 Board
Parallel
Serial
Cable
Connectors
for Connection
to Printer
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...