System Operation
151430
10-11
to begin communication.
5. The panel will attempt to communicate with the computer. If communication was estab-
lished, the upload task you created will be placed in the SKSS-2 job queue, awaiting pro-
cessing. When processing is completed, an “Unsolicited Upload” task will appear in the
queue.
10.5 Operation Mode Behavior
The control panel can be in one or more of seven conditions at any given moment: Normal,
Alarm, Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 10-1 describes the
behavior of the panel in each of these modes.
Table 10-1 Operation Mode Behavior
Operation
Mode
Occurs When
System Behavior
In This Mode You Can
Normal
No alarm or
trouble
condition exists
and menus are
not in use.
SYSTEM POWER LED is on.
The All Systems Normal display indicates
that the system is in normal mode.
The current date and time display on the
last line of the LCD.
Enter the appropriate code to activate the User or
Installer Menu.
Alarm
A smoke
detector goes
into alarm or a
pull station is
activated.
The dialer seizes control of the phone line
and calls the central station.
The on-board annunciator sounds a loud,
steady beep (any notification devices
attached to the system will also sound).
GENERAL ALARM LED is on.
The LCD displays a screen similar to this
one.
Press the down arrow to view the alarm. A screen
similar to this one displays.
Press
to silence the annunciator (and any
notification devices attached to the system).
When the alarm condition clears, press
to
restore the panel to normal.
firealarmresources.com
Summary of Contents for Silent Knight IFP-2000 Module 3
Page 2: ...firealarmresources com ...
Page 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Page 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Page 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Page 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Page 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Page 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Page 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Page 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Page 236: ...firealarmresources com ...
Page 237: ...firealarmresources com ...