Honeywell Silent Knight IDP-Monitor-2 Installation And Maintenance Instructions Download Page 2

7 8 

FROM PANEL OR 

(+) 

(–) 

TO NEXT 

(+) 

(–) 

DEVICE 

(+) 

(–) 

MONITOR 

CONNECT MODULES TO LISTED COMPATIBLE 

32 VDC MAX.

SHIELDED-TWISTED PAIR

IS RECOMMENDED

SILENT KNIGHT CONTROL PANELS ONLY 

PREVIOUS DEVICE 

SIGNAL LINE CIRCUIT (SLC)

MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS 
SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9) 
RESPONDS AT NEXT HIGHER ADDRESS. 

ANY NUMBER OF UL LISTED CONTACT CLOSURE 

DEVICES MAY BE USED. DO NOT MIX FIRE 

ALARM INITIATING, SUPERVISORY, OR SECURITY 

 DEVICES ON THE SAME INITIATING DEVICE CIRCUIT. 

INSTALL CONTACT CLOSURE DEVICES PER 

MANUFACTURER'S INSTALLATION INSTRUCTIONS. 

 

47 K EOL  
RESISTOR 
ELR-47K 

MODULE 

47 K EOL  
RESISTOR 
ELR-47K 





TENS 

ONES 

ADDRESS 

LOOP 

TWO INITIATING DEVICE CIRCUITS (L & H), 

EACH POWER LIMITED TO 230  A @ 12VDC MAX. 

 

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED 

K200-13-00 

I56-2730-002

Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B: