Honeywell SILENT KNIGHT IDP-Control Installation And Maintenance Instructions Download Page 1

LABEL

J1 UNDER LABEL

BACK OF

MODULE

K200-09-00 

I56-2725-003

IDP-Control Supervised 

Control Module

INSTALLATION AND
MAINTENANCE INSTRUCTIONS

Before Installing

This information is included as a quick reference installa-
tion guide. Refer to the control panel installation manual 
for detailed system information. If the modules will be 
installed in an existing operational system, inform the 
operator and local authority that the system will be tem-
porarily out of service. Disconnect power to the control 
panel before installing the modules.

NOTICE: 

This manual should be left with the owner/

user of this equipment.

General Description

IDP-Control Supervised Control Modules are intended 
for use in intelligent, two-wire systems, where the in-
dividual address of each module is selected using the 
built-in rotary switches. This module is used to switch an 
external power supply to notification appliances. It also 
supervises the wiring to the connected loads and reports 
their status to the panel as NORMAL, OPEN, or SHORT 
CIRCUIT. The IDP-Control has two pairs of output ter-
mination points available for fault-tolerant wiring and a 
panel-controlled LED indicator.

Figure 1A. Controls 

and indicators:

Figure 2A. Module mounting with barrier:

C0219-01

C0217-01

Specifications

Normal Operating Voltage:  15 to 32 VDC
Maximum Current Draw: 

6.5 mA (LED on)

Average Operating Current:  390µA (LED flashing)
Regulated External 
Supply Voltage:  

(between Terminals T3 and T4)

Maximum: 

80 Volts (RMS or DC)

Drain on External Supply: 

2 mA Maximum (using 

 

internal EOL relay)

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10% to 93% non-condensing

Dimensions: 

4

1

/

2

˝ H x 4” W x 1

1

/

4

˝ D  

 

(Mounts to a 4˝ square by  

 

2

1

/

8

˝ deep box.)

Accessories: 

SMB500 Electrical Box

Compatibility Requirements

To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control pan-
els only (list available from Silent Knight).

Mounting

The IDP-Control mounts directly to 4  square electri-
cal boxes (see Figure 2A). The box must have a mini-
mum depth of 2

1

/

8

˝. Surface mounted electrical boxes 

(SMB500) are available.

Wiring

NOTE: All wiring must conform to applicable local  
codes, ordinances, and regulations. When using control 
modules in nonpower limited applications, UL require-
ments for the separation of power-limited and nonpower-
limited terminals and wiring must be met. The barrier 
must be inserted into a 4˝ × 4˝ × 2

1

/

8

˝ junction box, and 

the control module must be placed into the barrier and 
attached to the junction box (Figure 2A). The power-lim-
ited wiring must be placed into the isolated quadrant of 
the module barrier (Figure 2B).

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

10

7 8

6

5

4

3

2

9

ISOLATED

QUADRANT

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

Figure 1B. Jumper location:

C0458-00

Figure 2B: 

C0218-01

Reviews: