System Operation
54711
6-5
6.3 JumpStart Operation
The JumpStart
®
feature will attempt to locate all SLC Mini-Monitor devices installed in
the system, indicate all devices found on the FFT and all FFT-24 Active LED's and
allow the user to accept the configuration, repeat the JumpStart or allow the
configuration to be discarded.
1. To perform the FFT Jumpstart press and hold the JumpStart button for 2 seconds.
2. The FFT will search for installed SLC devices and activate the Active LED’s of all
zone/point addresses found.
3. When the Jumpstart is complete, the first four status LED’s will blink. The user can
now press the ACCEPT key causing the FFT to save the configuration and
restart.
4. The user presses the JumpStart key again to repeat the SLC search process.
5. If the user does not press the Accept key within one minute after the JumpStart is
complete, its configuration will be discarded and the FFT will be restarted.