INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the
four holes provided in the back surface of the cabinet
(Figure 2).
Backbox
Mounting
Holes
Figure 2: Typical mounting hole locations
2. Module Installation
There are two methods for installing a module in the
rear position of a chassis. Method one is for installa-
tion of a rear module only, when no module will be in-
stalled in front of it. Refer to Figure 3 for instructions.
Method two is for installation of a rear module when
another module will be installed in the chassis position
in front of it. Refer to Figures 4a and 4b for method
two. All necessary screws and standoffs are supplied
with the modules.
2
3
1
Figure 3: Installation of rear module only, method one
Step 1: Insert the bottom of the IDP-Zone-6 module
down into a rear slot on the chassis.
Step 2: Carefully swing the upper edge of the board
back towards the back of the chassis until it
touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs
and tighten.
Step 4: Address and wire the modules according to the
instructions in this manual.
Included:
(5) 1 x 4 Terminal Blocks (2) 1
1
/
4
˝ Stand offs (3) Shunts
(4) Machine Screws (1) Long Power Supply Jumper
(2) Nuts
(6) 3.9k Ohm
End of Line Resistors
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control panel
(list available from Silent Knight).
COMPONENTS
The following is a description of the IDP-Zone-6 mount-
ing framework:
• One or two IDP-Zone-6 modules can be installed in a
IDP-ACB cabinet
Figure 1: IDP-ACB Cabinet
The IDP-ACB cabinet has a built-in chassis that will ac-
commodate one or two IDP-Zone-6 modules. For cabinet
dimensions refer to the IDP-ACB instruction manual.
The front IDP-Zone-6 module positions of each chassis
are offset below the rear IDP-Zone-6 module positions so
that all of the status indicators are visible.
K200-16-00
2
I56-2733-003
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
101
1
12
13
14
15
BASE
ADDRESS
ADDRESS
DISABL
E
N
O
N
E
O
N
E
TW
O
TH
R
EE
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
BASE
ADDRESS
ADDRESS
DISABLE
NONE
ONE
TW
O
THREE
C0234-04
C0235-00
C0237-00