Honeywell SILEN KNIGHT IDP-Zone-6 Installation And Maintenance Instructions Manual Download Page 1

K200-16-00 

I56-2733-003

INSTALLATION AND 

MAINTENANCE INSTRUCTIONS

IDP-Zone-6 

Six Zone Interface Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

2 mA

Alarm Current: 

40 mA (assumes all six    

 

LEDs solid on)

Temperature Range: 

32ºF to 120ºF ( 0ºC to 49ºC)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8˝ H x 5.8˝ W x 1.0˝ D

Accessories: 

IDP-ACB Cabinet and chassis

Wire Gauge: 

12-18 AWG 

Max. IDC Wiring Resistance: 

25 ohms

External Supply Voltage

 

DC Voltage: 

18-28 volts power limited

 

Ripple Voltage: 

0.1 volts RMS maximum

 

Current: 

90mA per module

 

IDC: 

Supervised and power limited

Compatible Two-wire System Sensor Smoke Detectors for use with IDP-Zone-6 

  DET.  

 

DETECTOR  

 MODEL 

DET. ID 

MANUFACTURER 

BASE MODEL 

MAX DET.

  1151 

SYSTEM SENSOR 

B110LP, B401 

20

  1451 

SYSTEM SENSOR 

B401, B401B 

20

 1451DH 

SYSTEM SENSOR 

DH400 

20

  2151 

SYSTEM SENSOR 

B110LP, B401 

20

  2451 

SYSTEM SENSOR 

DH400, B401B, B401 

20

 2451TH 

SYSTEM SENSOR 

B401, B401B 

20

  5451 

SYSTEM SENSOR 

B401 

20

  1100 

SYSTEM SENSOR 

N/A 

20

  1400 

SYSTEM SENSOR 

N/A 

20

** 2100AT 

SYSTEM SENSOR 

N/A 

20

  2100B 

SYSTEM SENSOR 

N/A 

20

  2100D 

SYSTEM SENSOR 

N/A 

20

  2100S 

SYSTEM SENSOR 

N/A 

20

 2100TB 

SYSTEM SENSOR 

N/A 

20

 2100TD 

SYSTEM SENSOR 

N/A 

20

 2100TS 

SYSTEM SENSOR 

N/A 

20

  2300B 

SYSTEM SENSOR 

N/A 

20

 2300TB 

SYSTEM SENSOR 

N/A 

20

  2400 

SYSTEM SENSOR 

N/A 

20

 2400TH 

SYSTEM SENSOR 

N/A 

20

*  2W-B 

SYSTEM SENSOR 

N/A 

20

* 2W-TB 

SYSTEM SENSOR 

N/A 

20

 DH100LP 

SYSTEM SENSOR 

N/A 

20

* Class B, Style B only
** No Accessory will be supported by 2100AT

BEFORE INSTALLING

If the modules will be installed in an existing operational 
system, inform the operator and local authority that the 
system will be temporarily out of service. Disconnect the 
power to the control panel before installing the modules. 
This system contains static sensitive components. Always 
ground yourself with a proper wrist strap before handling 
any circuits so that static charges are removed from the 
body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user  
of this equipment.

GENERAL DESCRIPTION

The IDP-Zone-6 Six Zone Interface Module is intended 
for use in an intelligent alarm system. Each module pro-

vides an interface between the intelligent alarm system 
and a conventional alarm system loop. A common SLC 
input is used for all modules, and the initiating device 
loops share a common supervisory supply and ground. 
Otherwise, each monitor operates independently from the 
others. Each module has its own unique address.
A pair of rotary code switches is used to set the address 
of the first module from 01 to 94. The remaining modules 
are automatically assigned to the next five higher ad-
dresses. Provisions are included for disabling a maximum 
of two unused modules to release the addresses to be 
used elsewhere. Each module also has panel controlled 
bicolor LED indicators. The panel can cause the LEDs to 
blink, latch on, or latch off.

Summary of Contents for SILEN KNIGHT IDP-Zone-6

Page 1: ...0 2W B A SYSTEM SENSOR N A 20 2W TB A SYSTEM SENSOR N A 20 DH100LP A SYSTEM SENSOR N A 20 Class B Style B only No Accessory will be supported by 2100AT BEFORE INSTALLING If the modules will be installed in an existing operational system inform the operator and local authority that the system will be temporarily out of service Disconnect the power to the control panel before installing the modules ...

Page 2: ...and wire the modules according to the instructions in this manual Included 5 1 x 4 Terminal Blocks 2 11 4 Stand offs 3 Shunts 4 Machine Screws 1 Long Power Supply Jumper 2 Nuts 6 3 9k Ohm End of Line Resistors Shipped on Board 2 Shunts in Class A B position Shipped in Class B position remove shunts for Class A COMPATIBILITY REQUIREMENTS To ensure proper operation this module shall be con nected to...

Page 3: ...n Class B operation the remaining modules are automati cally assigned to the next five higher addresses For ex ample if the base address switch is set to 28 the next five modules will be addressed to 29 30 31 32 and 33 The module is shipped in Class B position remove shunts for Class A When operating in Class A alternate modules are paired together 0 1 2 3 4 5 re sulting in a total of three module...

Page 4: ...long power supply jumper from T5 or T6 to T5 or T6 on the adjacent IDP Zone 6 module 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY SIGNAL LINE CIRCUIT SLC 32 VDC MAX SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS CLASS A ID...

Page 5: ... 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC A B SELECT A B SELECT DISABLE 1 DISABLE 2 T6 T5 0 1 IDC ADDRESS 2 3 IDC ADDRESS 4 5 IDC ADDRESS SLC A B SELECT A B SELECT DISABLE 1 DISABLE 2 T6 T5 IN OUT EXTERNAL SUPPLY IN OUT EXTERNAL SUPPLY EXTERNAL POWER SUPPLY PCB 1 PCB 2 VIEW A A 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 BASE ADDRESS 0 1 2 3 4 5 6 7 8 9 Figu...

Page 6: ...tructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures R...

Reviews: