Honeywell SILEN KNIGHT IDP-Relay-6 Installation And Maintenance Instructions Download Page 1

K200-15-00 

I56-2732-003

INSTALLATION AND 

MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING

If the modules will be installed in an existing operational 
system, inform the operator and local authority that the 
system will be temporarily out of service. Disconnect the 
power to the control panel before installing the modules. 
This system contains static sensitive components. Always 

IDP-Relay-6 

Six Relay Control Module

SPECIFICATIONS

Normal Operating Voltage:  15-32 VDC Stand-By 
Current: 

1.45 mA

Alarm Current: 

32 mA (assumes all six relays  

 

have been switched once and  

 

all six LEDs solid on) 

Temperature Range: 

32°F to 120°F (0°C to 49°C) 

Humidity: 

10 to 85% Non-condensing 

Dimensions: 

6.8˝ H × 5.8˝ W × 1.0˝ D 

Maximum IDC

Wiring Resistance: 

40 ohms

Accessories: 

IDP-ACB cabinet and chassis

Wire Gauge: 

12-18 AWG

Relay Current: 

30 mA/Relay Pulse (15.6  

 

mS pulse duration) pulse  

 

under panel control

ground yourself with a proper wrist strap before handling 
any circuits so that static charges are removed from the 
body. The housing cabinet should be metallic and suit-
ably grounded.

NOTICE:

 This manual should be left with the owner/

user of this equipment.  

GENERAL DESCRIPTION

The IDP-Relay-6 Six Relay Control Module is intended 
for use in an intelligent alarm system. Each module is 
intended for Form-C switching applications, which do 
not require wiring supervision for the load circuit. A 
single isolated set of dry relay contacts is provided for 
each module, which is capable of being wired for either 
normally open or normally closed for each operation. 
Each module has its own address. A pair of rotary code 
switches is used to set the address of the first module 
from 01 to 94. The remaining modules are automatically 
assigned to the next five higher addresses. Provisions are 
included for disabling a maximum of three unused mod-
ules to release the addresses to be used elsewhere. Each 
IDP-Relay-6 module also has panel controlled green LED 
indicators. The panel can cause the LEDs to blink, latch 
on, or latch off.
Contents include:    
(6) 1 × 3 Terminal Blocks 
(1) 1 × 4 Terminal Blocks
(2) 1

1

/

4

˝ (32mm) Stand offs

(4) Machine Screws
(2) Nuts
(1) Shunt (

NOTE:

  For the disable position, not more  

than one shunt shall be installed at the same time)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected 
to a compatible Silent Knight system control panel.  

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

.9 A

110 VDC

Resistive

Non-coded

.9 A

125 VDC

Resistive

Non-coded

.5 A

30 VDC

Inductive (L/R=5ms)

Coded

1 A

30 VDC

Inductive (L/R=2ms)

Coded

.3 A

125 VAC

Inductive (PF=.35)

Non-coded

1.5 A

25 VAC

Inductive (PF = .35)

Non-coded

.7 A

70.7 VAC

Inductive (PF=.35)

Non-coded

2 A

25 VAC

Inductive (PF=.35)

Non-coded

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) 
state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communi-
cate with the panel before connecting circuits controlled by the module.

Summary of Contents for SILEN KNIGHT IDP-Relay-6

Page 1: ...ule which is capable of being wired for either normally open or normally closed for each operation Each module has its own address A pair of rotary code switches is used to set the address of the first module from 01 to 94 The remaining modules are automatically assigned to the next five higher addresses Provisions are included for disabling a maximum of three unused mod ules to release the addres...

Page 2: ... two IDP Relay 6 modules can be installed in a IDP ACB cabinet The IDP ACB cabinet has a built in chassis that will ac commodate one or two IDP Relay 6 modules 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 10 11 12 13 14 15 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THREE 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 2 1 9 BASE ADDRESS ADDRESS DISABLE NONE ONE TWO THREE Figure 1 IDP ACB Cabinet The front IDP Relay 6...

Page 3: ... For example if the base address switch is set to 28 the next five modules will be addressed to 29 30 31 32 and 33 DO NOT set the lowest address above 94 as the other modules will be assigned to nonexistent addresses 4 A shunt is provided to disable a maximum of three unused modules Modules are disabled from the high est address and work downward If two modules are disabled the lowest four address...

Page 4: ...o radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Co...

Reviews: