3. Drill the detector mounting holes A, B (Ø
3.3mm and minimum 8 mm deep), and
then thread the two holes with a M4 Tap
(6mm at least).
4. Drill the Test Transmitter SC113
mounting hole C (Ø 3.3mm and
minimum 8 mm deep), and then thread
the hole with a M4 Tap (6mm at least).
Notes:
Cool the tools with oil while drilling and
threading.
Skip step 4 if no test transmitter is used.
5. Remove all of the burrs.
6. Attach the Test Transmitter SC113 on the
mounting area (at C) and then use the
M4
×
8mm screw to fix it.
Note:
Skip this step if no Test Transmitter SC113 is
used.
C
7. Attach the detector base on the steel
surface and then use the two M4
×
8mm
screws provided to fix it.
8. Wire and configure the detector (see the
related chapter in this user guide), and after
a successful test use the top screw to fix the
detector cover properly.
Mounting on Stainless Steel or Hardened Steel
When mounting on stainless steel or hardened steel, the Mounting Plate SC110 (
UPSIDE DOWN
)
must be used and should be welded on the mounting surface first.
Figure 6-3 Mounting Plate SC110
UPSIDE
F
G
C
D
E
A
B
This orientation is used for
mounting on
concrete
.
A
,
B
– Detector SC100 mounting holes
C
,
D
, – Test Transmitter SC113 locating hole
E
– Mounting Plate SC110 mounting hole
F
,
G
– Welding Slots
UPSIDE DOWN
F
G
C
D
E
A
B
This orientation is used for
mounting on
stainless
steel
or
hardened steel
.
Refer to the steps below to mount the Detector SC100 on stainless steel or hardened steel.
1. Remove paint from the mounting area
(especially welding area).
2. Attach the Mounting Plate SC110 on the
mounting area, and then mark the
outline.
3. Fix the Mounting Plate SC110 into the
outline marked and ensure it cannot move,
and then along the
INSIDE
of the welding
slots weld the Mounting Plate SC110 on the
mounting surface.
Note:
The welding must be done along the
INSIDE
of
the welding slots, otherwise the Mounting Plate
SC110 may be deformed.
4. Tap off slag and remove weld spatter and make sure the whole mounting surface is still
flat.
5. Attach Test Transmitter SC113 on the mounting plate (at C) and then use the M4
×
8mm
screw to fix it.
Note:
Skip this step if no Test Transmitter SC113 is used.