2

TECHNICAL FEATURES

1. Flame detection

The following types of flame detectors are suitable:
- Ionisation probe, temperature resistant material, well

insulated (material and insulation same as for ignition
electrode).

- IRD 1020.1 infra-red flicker detector

Flame detection using an ionisation probe is only possible
in conjunction with mains supplies which provide a neu-
tral earth connection.

The ionisation rod has to be installed in a way that
the distance to the ignition electrode is big enough
to prevent the spark to jump to the ionisation rod.

2. Safety

In terms of design/construction and programme sequence,
the TFI 812 control boxes conform to the presently appli-
cable European standards and regulations.

3. Installation

At the baseplate:
– 3 earth terminals with additional terminal for burner

earthing

– 3 neutral terminals with internal permanent connection to

neutral terminal 8

– 2 independant spare terminals (S1 and S2)
– extra terminals A, B and C are standard (wiring base S98

12-pin)

– 2 slide-in plates and 2 easy knock out holes plus 2 knock

out holes in the base bottom faciliate the base wiring

Please note
To assist trouble-free operation the main neutral
connection terminal 8 in the wiring base must be
fully tightened. The terminal screws are already in
the undone position. To connect a wire to the
terminal, the screw only needs to be fastened.

General:
- Can be mounted in any position, insulated as per IP 44

standard (unaffected by water spray).
The control box and detector probe should not, however,
be subjected to excessive vibration.

- The applicable installation regulations must be observed

during installation.

COMMISSIONING AND MAINTENANCE

1. Important notes

- The wiring must be checked exactly when commissioning

the installation. Incorrect wiring could damage the con-
trol box, putting the safety of the burner system at risk.

- The chosen fuse rating must not, on any account, be

higher than the value given in the technical data. Failure to
observe this instruction could, in the case of a short circuit,
have serious consequences for the control box or burner
system.

- For safety reasons, it must be ensured that the control box

performs at least one normal shut-down during every
24 hour period.

- Switch off or disconnect the power before plugging in or

unplugging the unit.

- Burner control boxes are responsible for the safety of the

system and should not be opened.

2. Routine checks

On commissioning or after servicing the burner system, or
if the system has not been in operation for a long period, a
check of the safety-relevant control box functions must be
made.

a) Attempt to start with gas valve closed:

-   At the end of the safety interval
-> Lockout

b) After a normal start, with the burner in operation, close

the gas valve:
-   At the end of the safety interval, system attempts to

restart

-> Lockout

3. Possible faults

Burner does not start:
- Fault in electrical supply, thermostat OFF
- Mains voltage too low

Switches to lockout after attempted start without establishing
flame:
- No ignition or no fuel reaching burner
- Flame signal during the pre-purge phase
- Mains voltage more than 15% below nominal value

Burner starts, flame is established but control box switches
to lockout after elapse of safety interval:
- No flame signal or signal too weak
- Flame detector dirty or defective

TFI 812

Summary of Contents for Satronic TFI 812 Series

Page 1: ...type plastic housing which encloses the thermo mechanical temperature compensated timing unit the flame monitoring unit and the reset device The reset button which incorporates an indicator lamp and the central screw fastening are situated on the upper part of the control box The baseplate which can be equipped with additional terminals together with the various optional cable entry points makes u...

Page 2: ...The applicable installation regulations must be observed during installation COMMISSIONING AND MAINTENANCE 1 Important notes The wiring must be checked exactly when commissioning the installation Incorrect wiring could damage the con trol box putting the safety of the burner system at risk The chosen fuse rating must not on any account be higher than the value given in the technical data Failure t...

Page 3: ...ST Safety thermostat RT Controlling thermostat IS Ionisation probe Z Ignition V1 Solenoid valve 1st stage V2 Solenoid valve 2nd stage SA remote lockout indicator M Auxiliary blower tw Pre ignition time approx 15 sec mod 5 approx 10 sec mod 10 ts Safety time nominal 5 sec mod 5 10 sec mod 10 tv2 2nd stage delay approx 20 sec blue black brown Kl 8 Kl 1 Kl 9 IRD 1020 1 TFI 812 RF R26 1 Ion 9 RT ST HS...

Page 4: ... no longer available Control box TFI 812 2 B mod 10 no longer available Socket Wiring base S98 9 pin 75300 Socket Wiring base S98 12 pin 75310 Insert plate PG plate 70502 optionally Cable entry plate 70503 Flame detector IRD 1020 1 end on viewing 16532 Flame detector IRD 1020 1 side on left 16533 Flame detector IRD 1020 1 side on right 16531 IRD mounting flange IRD Holder M93 59093 Flame detector ...

Reviews: