Honeywell Satronic DMG 973 Manual Download Page 4

4

DMG 973

INSTALLATION INSTRUCTIONS AND MAINTENANCE

1. Important notes

– The controls must be installed by qualified personnel

only. The relevant national regulations have to be
observed.

– On commissioning the wiring has to be carefully check-

ed according the appropriate diagram, Incorrect wiring
can damage the unit and endanger the installation.

– The fuse rating has to ensure that the limits specified in

TECHNICAL DATA will not be exceeded. If these precau-
tions are not observed, the effect of a short circuit can
cause severe damage to the control and installation.

– For safety reasons a minimum of one control shutdown

per 24 hours has to be observed.

– Disconnect the mains before the control box is plugged

in or out.

– The control box is a safety device and must not be

opened!

2. Function control

For safety reasons the flame detection system should be
tested on commissioning the installation as well as after a
service or longer shut-down.

a) Start-up with closed gas valve

– After lock out safety time is over the unit has to go into

lock out mode!

b) Normal start-up, when burner is running, close gas valve

– After loss of flame, the control box has to go into

lockout mode

c) Normal start-up, during pre-purge or operation, interrupt

the air proving switch
– The control box has to perform a lockout immediatly

d) Bridged air proving switch before start

– the fan motor switches on for approx. 2 - 3 secs,

followed by a lockout. After 10 secs., this quick
lockout is resetted by the control box and a second
start attempt follows (fan motor switches on for approx.
2 - 3 secs.). A standard lockout appears if the air
proving switch (LW) contact is still in it’s closed
position (e.g. welded contacts). Has the air proving
switch (LW) changed to it’s open position in the
meantime (e.g. by a run down motor), a normal start
sequence follows.

3. Fault finding

The built-in information system facilitates the trouble shoot-
ing in the case of problems occurring during start-up or
during operation.
A list of possible lock out messages can be found in
APPLICATION FEATURES chapter 1.2.

Please note:
The control box is locked in lock out mode
and the reasen for the lock out is displayed
until the control box is reset, either by an
internal or external reset (see also subject “3.
Lock out and reset").

Removing the control box from its wiring base or by
interrupting the supply line may 

not

 reset a lock out. There-

fore, by applying power, the fan motor switches on for 2-3
secs. before the control box goes to lock out again and the
cause of the last lock out.

Error

Possible fault

Burner not working

- Thermostat circuit open
- Faulty electrical wiring
- Mains voltage < 187 V (< 80 V)
- Terminal A continuously on

power (e.g. terminal A is used as
a support terminal)

Fan motor starts for a short

- Control box has not been reset

period of time, control box

- Air proving switch not in open

goes to lock out

position

Control box locks out

- Air proving switch has not

during pre-purge

closed within 60 secs.

- Air proving switch has re-opened

Control box locks out

- Air proving switch open

at the end of pre-purge

- Flame signal (stray light)

Burner starts,

- No ignition or no fuel

flame 

not

 established

after safety time,
lock out
Burner starts,

- No or too low flame signal (flame

flame established,

does not stick, bad insulation of

after safety time,

the ionisation probe, bad connec-

lock out

tion to frame ground)

- Insufficient light on IRD
- Sensitivity adjustment

too low on IRD

Summary of Contents for Satronic DMG 973

Page 1: ...a variety of cable entry points utmost flexibility of electrical wiring The DMG 973 is funstionally compatible to MMI 813 and MMI 813 1 Please note Is the DMG 973 to be used to replace the MMI 813 or 813 1 care has to be taken to make sure the air proving switch LW is wired between terminals 4 and 7 and not like on the MMI between 5 and 7 DMG 973 Gas Burner Safety Control For 2 stage forced draugh...

Page 2: ... short pulse long pulse short pause _ long pause 1 2 Lock out diagnoses In case of a failure the LED is permanently illuminated Every 10 seconds the illumination is interrupted by a flash code whichindicatesthecauseoftheerror Thereforethefollowing sequence is performed which is repeated as long as the unit is not reset Sequence illuminated phase dark phase Flash Code dark phase for 10 sec for 0 6 ...

Page 3: ...trol box proceed to safety shut down and goes into a waiting status If the voltage rises again the control box performs automatically a start up as soon as the mains voltage is 187 Veff 94 Veff 5 Safety The design and control sequence of the DMG 970 controls will comply with the currently applicable standards and regulations see also TECHNICAL DATA 6 Burner with an air damper motor The position of...

Page 4: ...switch LW contact is still in it s closed position e g welded contacts Has the air proving switch LW changed to it s open position in the meantime e g by a run down motor a normal start sequence follows 3 Fault finding The built in information system facilitates the trouble shoot ing in the case of problems occurring during start up or during operation A list of possible lock out messages can be f...

Page 5: ...er motor tlw max reaction time for air proving switch tv1 Supervised pre purge time tlk LK open command during pre purge tr LK close movement tf Stray light monitoring tvz Pre ignition time tn Post ignition time ts Safety time tv2 Delay terminal 6 C rv1 rs 2 C 6 5 7 4 3 B 8 9 A rz rv2 Flame amplifier Reset µC Reset and lock out Power supply monitoring RZ RV1 RV2 RS Fault display Information system...

Page 6: ...IRD Holder M93 for IRD 1020 59093 Support for UVD Holder M74 for UVD 59074 Connection cable Plug type 3 core cable 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice VARIATION IRD right left axial 62 5 4 5 38 5 24 86 60 24 30 30 44 M4 Earth Reset butto...

Reviews: