background image

S9201A1010 INTEGRATED FURNACE CONTROL

APPLICATION

The S9201A1010 Integrated Furnace Control is used in

high efficiency gas fired warm air furnaces with an induced
draft blower and a combination hot surface igniter/flame
sensor. The S9201 provides:

sequencing of ignition and burner operation,

up to 5 trials for ignition before lockout, if initial lightoff
is unsuccessful,

ignition return if established flame fails during the run
cycle.

control of indoor blower motor operation, including
heating and cooling speeds,

control of the induced draft blower motor,

control of the humidifier, and

control of the electronic air cleaner.

The S9201 cannot be used with a vent damper.
The S9201 Integrated Furnace Control is intended for

residential furnaces only. Other applications require Hon-
eywell Residential Design Engineering review and written
approval. Contact your Honeywell Sales Representative for
assistance.
VOLTAGE: 24 Vac.
CURRENT DRAW: Inrush—0.32 A plus gas control current;

running—0.10 A plus gas control current.

POWER CONSUMPTION: Inrush—7.7 VA plus gas control

VA; running—2.4 VA plus gas control VA.

THERMOSTAT ANTICIPATOR SETTING: 0.10 A plus gas

control load. For VR8204 and VR8205, set anticipator to
0.6 A.

PREPURGE TIMING: 30 sec., nominal.
WARM UP TIMING: 36 sec.
TRIAL FOR IGNITION: 9 sec., nominal. Igniter is off 1 sec.

before end of ignition trial.

FLAME FAILURE RESPONSE TIME: 2.3 sec. max. with 5

µ

A flame signal.

FLAME CURRENT: 0.8 

µ

A DC, min.

IGNITION TRIALS: Five, with 30 sec. purge between trials.
INDOOR FAN ON DELAY: 30 sec., fixed.
INDOOR FAN OFF DELAY: 90 sec., factory set; selectable

to 45, 60 or 75 sec.

GAS CONTROL: Any 24 Vac redundant gas control rated at

1 A or less. Honeywell VR8204 or VR8205 recommended.

COOLING CONTACTOR: Any 24 Vac contactor rated at 1 A

or less.

HOT SURFACE IGNITER: Norton Model 201 or equivalent.
NOTE: Igniter must meet the following minimum specifica-

tions throughout its life:

Igniter must reach 1000

°

 C [1832

°

 F] within 36 seconds

with 102 Vac applied.

Igniter must maintain at least 500M ohms insulation
resistance between the igniter leadwires and the ig-
niter mounting bracket.

Igniter must not develop an insulating layer on its
surface (over time) which would prevent flame sensing.

Igniter surface area immersed in flame must not ex-
ceed 1/4 of the grounded area immersed in flame. This
would prevent flame sensing.

Igniter current draw at 132 Vac must not exceed 5 A.

2. Check the ratings given in these instructions to make

sure the integrated furnace control is suitable for your appli-
cation.

3. Installer must be a trained, experienced service techni-

cian.

4. After installation is complete, check out operation as

provided in these instructions.

WARNING

FIRE OR EXPLOSION HAZARD.
MAY CAUSE PROPERTY DAMAGE, SEVERE
INJURY OR DEATH.

1. The integrated furnace control can malfunction

if it gets wet, leading to accumulation of explo-
sive gas.

Never install where water can flood, drip
or condense on control.

Never try to use an integrated furnace
control that has been wet—replace it.

2. Liquefied petroleum (LP) gas is heavier than air

and will not vent upward naturally.

Do not operate electric switches, lights,
or appliances until you are sure the ap-
pliance area is free of gas.

CAUTION

1. Disconnect power supply before beginning wiring

to prevent electrical shock or equipment damage.

2. If furnace control must be mounted near moisture or

water, provide suitable waterproof enclosure.

LOCATION

The integrated furnace control is mounted inside the

furnace wiring compartment. The location must provide:

Access to the field wiring terminals.

Operating  ambient  temperature  between  minus  40

°

F and plus 150

°

 F [minus 40

°

 C and plus 66

°

 C], except

temperatures to 170

°

 F [77

°

 C] are acceptable for

occasional brief periods.

Relative humidity below 95% non-condensing.

Protection from water, steam or corrosive chemicals
that might be used to clean the appliance.

Protection from dripping water, such as from an over-
filled humidifier or from condensation.

Protection from dust or grease accumulation.

A barrier between line and low voltage field wiring
terminals.

MOUNTING

Select a location close enough to the burner to allow a

short, direct cable route to the igniter. The integrated furnace
control can be mounted in any position. Line voltage wiring
terminals must be in an enclosure separate from low voltage
field wiring terminals. The unit is designed to snap in to
predrilled holes in the mounting surface.

INSTALLATION

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous condition.

G.G.

Form Number 69-0685

9-91

©Honeywell Inc. 1991

Summary of Contents for S9201A1010

Page 1: ...ing Igniter surface area immersed in flame must not ex ceed1 4ofthegroundedareaimmersedinflame This would prevent flame sensing Igniter current draw at 132 Vac must not exceed 5 A 2 Check the ratings given in these instructions to make sure the integrated furnace control is suitable for your appli cation 3 Installer must be a trained experienced service techni cian 4 After installation is complete...

Page 2: ...en burner and S9201 1 4 in male Transformer secondary quick connects Field 120 Vac Screw terminals Humidifier and electronic air cleaner 24 Vac Screw terminals Thermostat WIRING CAUTION 1 Check the wiring diagram furnished by the appli ance manufacturer if available for circuits differing from the general hookup shown Carefully follow anyspecialinstructionsaffectingthegeneralproce dures outlined b...

Page 3: ...roubleshooting Check Safety Shutoff Operation Shut off gas supply at manual gas valve ahead of appli ance Set thermostat to call for heat System should operate as indicated in Table 4 Following lockout open manual gas valve and make sure no gas is flowing to burner TABLE 4 S9201A1010 SEQUENCE ON FAILURE TO LIGHT FIG 2 LADDER DIAGRAM OF S9201 INTEGRATED FURNACE CONTROL 1 POWER SUPPLY PROVIDE DISCON...

Page 4: ...neral guide Follow appliance manufacturer s service in structions if available 2 All meter readings must be taken within the trial for ignition period Once the ignition period ends the system must be reset by setting the thermostat down for at least 45 sec before continuing 3 If any component does not function properly make sure it is correctly installed and wired before replac ing it 4 Staticdisc...

Page 5: ...NS POWERED AND LIT YES YES YES YES NO NO INDOOR BLOWER MOTOR STARTS AFTER 30 SECONDS CHECK FOR 120 VAC ACROSS BLOWER MOTOR AND BLOWER MOTOR TERMINALS ON IFC REPLACE IFC IF WIRING TO BLOWER MOTOR IS OK M890 NOTE If IFC goes into lockout wait 30 seconds then reset system CHECK CONTINUITY OF GROUND WIRE NOTE IF GROUND IS POOR OR ERRATIC SHUTDOWN MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL ...

Page 6: ...ng You Control Your World Building Controls Division Building Controls Division Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 QUALITY IS KEY ...

Reviews: