Honeywell S89E Quick Start Manual Download Page 8

S89E,F DIRECT SPARK IGNITION CONTROL MODULE

68-0066—4

8

IMPORTANT

1. The following service procedures are provided as a 

general guide. Follow appliance manufacturer ser-

vice instructions, if available.

2. All meter readings must be taken within the trial for 

ignition period. Once the ignition period ends, the 

system must be reset by setting the thermostat down 

for at least 45 seconds before continuing.

3. If any component does not function properly, make 

sure it is correctly installed and wired before 

replacing it.

4. The ignition module cannot be repaired. If it 

malfunctions, it must be replaced.

5. Only trained, experienced service technicians should 

service direct spark ignition systems.

Before beginning troubleshooting, review the normal 

operating sequence of the S89. See the Operation section. 

Then follow the steps in Fig. 5 to identify the source of the 

problem. Some steps are explained in greater detail below. 

Besides standard hand tools, you will need the following to 

complete the troubleshooting:

1.

Honeywell W136 Test Meter or equivalent.

2.

Test lead: a length of ignition cable or other heavily 

insulated wire with both ends stripped 1/2 in. (13 mm).

Check Ignition System Grounding

Nuisance shutdowns are often caused by a poor or erratic 

ground. 

A common ground is required for the module, igniter, flame 

sensor and main burner.

1.

Check for good metal-to-metal contact between the 

igniter bracket and the main burner.

2.

Check the ground lead from the GND (Burner) terminal 

on the module to the igniter bracket. Make sure 

connections are clean and tight. If the wire is damaged 

or deteriorated, replace it with no. 14 to 18 gauge, 

moisture-resistant, thermoplastic insulated wire with a 

221°F (105°C) minimum rating. Use a shield if 

necessary to protect the ground wire from radiant heat.

Check Spark Ignition Circuit

The S89 spark generator relay switches 120 Vac to the 

remote-mounted spark generator, which, in turn, powers the 

spark igniter at the burner. Check as follows:

1.

Shut off gas supply to the gas control.

2.

Disconnect the ignition cable at the spark generator 

stud terminal.

3.

Set the thermostat to call for heat.

4.

Reset the S89 by removing power to the module for 45 

seconds.

WARNING

Electrical Shock Hazard.

Can cause severe injury, death, or property 

damage.

In the next step, 

do not touch

 either the stripped end of 

the test lead or the stud terminal.

5.

Restore power. Before the S89 locks out, touch one end 

of the test lead firmly to the S89 GND terminal. Do not 

remove the existing ground lead.

6.

Slowly move the other end of the test lead toward the 

stud terminal on the spark generator until sparking 

stops.

7.

Slowly pull the wire away from the stud terminal and 

note the size of the gap when sparking stops. 

8.

Follow instructions in Table 3.

Table 3. Spark Ignition Troubleshooting.

Check Flame Sensor and Igniter

1.

Make sure burner flame is capable of providing a good 

rectification signal. See Fig. 7.

2.

Make sure about 3/4 to 1 in. (19 to 25 mm) of the flame 

sensor is continuously immersed in the flame for best 

flame signal. See Fig. 7. Bend the bracket or flame 

sensor, or relocate the sensor as necessary. Do 

not 

relocate the igniter.

3.

Make sure flame does not touch sensor or ignitor 

ceramic insulator and that insulators are below he 

flame. Excessive heat (over 1000°F [538°C]) will cause 

short to ground. Move sensor to cooler location or shield 

insulators if excessive heat is suspected. Do

 not 

relocate the igniter.

4.

Check for cracked igniter or sensor ceramic insulator, 

which can cause short to ground, and replace unit if 

necessary.

5.

Make sure electrical connections are clean and tight. 

6.

Replace damaged wire with moisture-resistant no. 18 

wire rated for continuous duty up to 221°F (105°C).

If the Gap Was:

Then:

1/8 in. (3 mm) or more

Generator output voltage is okay.

Less than 1/8 in. (3 mm) 

or no spark

Check for 120 Vac at the spark 

generator terminals. If okay, 

replace the spark generator.

Summary of Contents for S89E

Page 1: ...alve on delay before ignition Available with 4 or 11 second nominal lockout timing 100 percent shutoff for use with all heating gases Ambient temperature rating is 40 F to 175 F 40 C to 80 C Separate electrodes for spark ignition and flame sensing Uses Honeywell or any other 2A or less dual valve combination gas control designed for Direct Spark Ignition DSI applications Locks out system after tri...

Page 2: ...stem also includes 120 Vac Spark Generator with 1 5A or less current draw Q347 Spark Igniter or equivalent Q354 Flame Sensor or equivalent VR845 VR854 VR8450 or VR8305 Combination Gas Controls or any dual valve rated 2A or less and designed for DSI applications 24 to 30 Vac Thermostat HIgh Temperature Limit Controller 24V Transformer See Table 1 for VA rating Electrical Ratings Power supply Requir...

Page 3: ... off gas supply before starting installation Conduct Gas Leak Test after gas control is installed 3 In an LP gas installation remember that LP gas is heavier than air and will not vent upward naturally Do not operate electric switches lights or appliances until you are sure that work area is free of gas 4 Never install an S89 where water can flood drip or condense on the device It can malfunction ...

Page 4: ...trols may repeatedly set the timer to zero preventing burner start Always disconnect the external timer when using an S89E or F To disconnect the timer a Turn off power b Cut the two leadwires at the external timer c Strip the ends of the wires 1 2 in 13 mm and connect with a solderless connector d Restore power 3 Wire system components and S89 as shown in Fig 2 and 3 Refer to appliance manufactur...

Page 5: ...gas supply 6 Gas control closes 7 The module begins the safe start check S89E 10 seconds maximum or safe start check plus valve on delay 30 seconds minimum after which the igniter starts and gas control opens 8 Time system until gas control closes S89 is now in safety lockout The lockout time should be within the specifications in Table 2 9 Open gas supply System remains off and no gas flows to th...

Page 6: ...rn off power to the appliance for 45 seconds and then turn it on Final Checkout With power and gas supply on set thermostat to call for heat and observe operation through at least one complete cycle to make certain that all controls are operating safely OPERATION The S89 is powered by a 24V transformer It operates in response to a call for heat from the thermostat BLUE WHITE GROUND BURNER IGNITER ...

Page 7: ...se the gas control perform a safe start check and on the S89F valve on delay then return ignition as described above The S89 is reset by turning the thermostat below room temperature or removing power to the system for 45 seconds Fig 4 Normal sequence of operation TROUBLESHOOTING WARNING Fire or Explosion Hazard Can cause severe injury death or property damage Any replacement S89 must have the sam...

Page 8: ...itches 120 Vac to the remote mounted spark generator which in turn powers the spark igniter at the burner Check as follows 1 Shut off gas supply to the gas control 2 Disconnect the ignition cable at the spark generator stud terminal 3 Set the thermostat to call for heat 4 Reset the S89 by removing power to the module for 45 seconds WARNING Electrical Shock Hazard Can cause severe injury death or p...

Page 9: ... SHIELD CABLE IF NECESSARY MAKE SUE BURNER SPARK IGNITER AND S89 GROUND BURNER TERMINAL HAVE EFFECTIVE COMMON GROUND POOR OR ERRATC GROUND WILL CAUSE NUISANCE SHUTDOWNS CHECK FOR CRACKED INSULATOR ON IGNITER OR FLAME SENSOR REPLACE DEVICE WITH CRACKED INSULATOR TO PREVENT SHORT TO GROUND NOTE IF S89 LOCKS OUT RESET BEFORE CONTINUING CHECK FOR 24 VAC ACROSS VALVE AND VALVE GROUND TERMINALS ON S89 I...

Page 10: ...current must be at least 0 8 µA and steady 3 If the meter reads less than 0 8 µA or reading is unsteady recheck points under Check Flame Sensor and Igniter above Fig 6 S89 flame current measurement Fig 7 Check burner flame condition GND BURNER 24V GND 24V VALVE VALVE GND SENSE TO SENSOR BLACK RED M19840 FLAME SENSOR CURRENT CHECK USE µA SCALE 0 8 µA DC MINIMUM AND STEADY DISCONNECT WIRE FROM SENSE...

Page 11: ...24 V THERMOSTAT SAFE START CHECK CIRCUIT ALTERNATE LIMIT ON OFF SWITCH 24 V GND GND BURNER SENSE WHITE FLAME SENSOR SPARK IGNITER RELAY BLUE BLUE BLACK WIRING EXTERNAL TO S89 WIRING INSIDE S89 2K1 1K2 2K2 SPARK IGNITER SPARK GENERATOR VALVE SPARK IGNITER RELAY 1K 2K VALVE GND SENSOR CIRCUIT TIMING CIRCUIT DUAL VALVE L1 HOT L2 ...

Page 12: ...IRECT SPARK IGNITION CONTROL MODULE Fig 9 S89F simplified control system schematic M19843A LIMIT CONTROL AIR PROVING SWITCH COMBUSTION AIR BLOWER 24 V THERMOSTAT SAFE START CHECK VALVE ON DELAY CIRCUIT COMBUSTION AIR BLOWER RELAY ALTERNATE LIMIT ON OFF SWITCH 24 V GND GND BURNER SENSE WHITE FLAME SENSOR SPARK IGNITER RELAY BLUE BLUE BLACK WIRING EXTERNAL TO S89 WIRING INSIDE S89 2K1 1K2 2K2 SPARK ...

Reviews: