Honeywell S8921D Installation Instructions Manual Download Page 8

69-0924—2

8

S8921D HOT SURFACE IGNITION MODULE

Fig. 4. S8921D troubleshooting sequence.

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

START

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

YES

YES

YES

YES

M7598

SET THERMOSTAT TO 
CALL FOR HEAT

LED PULSES WITH 
“HEARTBEAT”

IGNITER WARMS UP
 AND GLOWS RED 

COMBUSTION BLOWER 
ENERGIZED

MAIN BURNER LIGHTS

MAIN BURNER REMAINS 
LIT AFTER TRIAL FOR 
IGNITION ENDS

SYSTEM RUNS UNTIL 
CALL FOR HEAT ENDS

END CALL FOR HEAT.  
COMBUSTION AIR BLOWER 
AND GAS CONTROL OFF.

TROUBLESHOOTING ENDS

WARNING

ELECTRICAL SHOCK HAZARD MAY CAUSE SERIOUS INJURY OR DEATH.

Dangerous line voltage is exposed during troubleshooting.  Disconnect power before 
touching control.  Service must be by trained, experienced service technician.

Check for 24 Vac across ignition module 24V and 24V(GND) terminals.

Replace Module.

• Check line voltage power.
• Check low voltage transformer.
• Check limits and safety controls (closed).
• Check thermostat.
• Check system wiring to ignition module.

Check for 120 Vac across 
module HSI terminals.

Check air proving
switch (open)

NO

• Check/replace wiring to igniter.
• Check/replace igniter.

YES

Replace module

Check air proving switch (open).

Replace air proving switch

Replace air proving switch

Check for 120 Vac across module 
CAB terminals.

Replace module

• Check/replace wiring to combustion air blower.
• Check/replace combustion air blower.

Check air proving switch is closed.

• Check for blocked vent.
• Replace air proving switch.

• Remove call for heat.
• Check that external gas shutoff and gas control manual valves are OPEN (ON).
• Check igniter position.
• Connect AC voltmeter across VALVE and VALVE(GND) terminal of module.

• Re-establish call for heat.
• Check for 24 Vac across VALVE and VALVE(GND) terminals during trial for ignition.
   Note:  Voltage present only during trial for ignition after air proving switch confims 
   combustion air flow.

Replace module

• Check/replace wiring to gas control.
• Check/replace gas control.

Note:  Ignition module will continue ignition cycle to lockout (after 5 trials for ignition).  
Troubleshooting may be accomplished best by recycling the call for heat.

• Check continuity of ground wire and ground path from main burner to GND (BURNER) terminal of igniter module.
• Check that burner flame covers flame sensor (see Fig. 3).
• Check insulation on flame sensor leads.
• Check that manifold gas pressure stays at recommended level as burner runs.
• Check flame sensor for contamination or damage.  Replace if necessary.
• Check insulation on sensor leads and check sensor position.
• If checks are okay, replace the igniter module.

   NOTE:  SYSTEM FAILURE AFTER MAIN FLAME HAS LIT HAS A LOW PROBABILITY OF BEING THE 
   IGNITER MODULE.

Note:  If igniter module goes into lockout, reset system.

• Check continuity of ground wire and ground path from main burner to GND (BURNER) terminal.

   Note:  If ground is poor or erratic, shutdowns can occur occasionally even though operation is normal at the time 
   of checkout.

• Check for excessive heat at flame sensor ceramic base (temperature above 1000

°

F (538

°

C) causes short to ground).

• Check for intermittent low manifold gas pressure due to other gas appliances firing, restricted gas piping, or low gas 
   utility gas supply pressure.

   If checks are okay, replace igniter module.

   NOTE:  SYSTEM FAILURE DURING A RUN CYCLE  HAS LIT HAS A LOW PROBABILITY OF BEING THE 
   IGNITER MODULE.

• Check for proper thermostat operation.
• Check gas control, replace if necessary.

Repeat procedure until trouble-free operation is obtained.

Summary of Contents for S8921D

Page 1: ... 60 Hz Contact Rating at 120 Vac Hot Surface Igniter 5A Combustion Air Blower 3 FLA 10 LRA IMPORTANT The S8921D is to be used only in a 60 Hz system Be sure the system is not 50 Hz Hot Surface Igniter Norton Model 271 or equivalent NOTE If an igniter other than a Norton Model 271 is used the igniter must meet the following minimum specifications required over the life of the igniter Igniter must r...

Page 2: ...A 4 enclosure is recommended for the ignition module see the Electronic Ignition Service manual 70 6604 Corrosive Chemicals Corrosive chemicals can attack the module and gas control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the controls Where chemicals are suspended in air as in some industrial or agricultural applications NEMA 4 enclosure is recom ...

Page 3: ...ly before doing any work on the unit Disconnect and tag the wires from the old module Label each wire as it is removed Remove the old module from its mounting location Mount New Ignition Module Mount the new module in the same location as the old module Protect the module from exposure to water moisture corrosive chemicals and excessive dust and grease Make certain that the ambient temperature at ...

Page 4: ...ormer has adequate VA The ignition module requires 0 4A at 24 Vac Add the current draws of all other devices in the control circuit including the pilot and main valves in the gas control and multiply by 24 to determine the total VA requirement of these components Add this total to 9 6 VA for the ignition module The result is the minimum transformer VA rating Use a Class II trans former when replac...

Page 5: ... gas control is energized 5 Gas control is energized for the trial for ignition time This time can be measured by connecting a voltmeter range set to measure approximately 24 Vac across the gas valve terminals 6 After the trial for ignition the between trial delay begins and the combustion air blower is turned off 7 The second trial begins with the hot surface igniter warmup followed by the combus...

Page 6: ...nition The gas control opens for the ignition trial time The hot surface igniter stays powered for the ignition activation period and then the igniter turns off Near the end of the ignition trial time the flame rectification sensing circuit determines if the main burner flame is present If so the gas control remains open and the burner operation phase begins Burner Operation When the main burner i...

Page 7: ...onsiderations are Cycling frequency Appliances that may cycle 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environment Since th...

Page 8: ... of module Re establish call for heat Check for 24 Vac across VALVE and VALVE GND terminals during trial for ignition Note Voltage present only during trial for ignition after air proving switch confims combustion air flow Replace module Check replace wiring to gas control Check replace gas control Note Ignition module will continue ignition cycle to lockout after 5 trials for ignition Troubleshoo...

Page 9: ...em Checks Step 1 Check wiring harness Make sure 1 Connections to the ignition module air proving switch and gas control are clean and tight 2 Hot surface ignition cable provides good electrical continuity Step 2 Check ignition system grounding Nuisance shutdowns are often caused by a poor or erratic ground A common ground is required for the module flame sensor and main burner 1 Check for good met...

Page 10: ...69 0924 2 10 S8921D HOT SURFACE IGNITION MODULE ...

Page 11: ...69 0924 2 11 S8921D HOT SURFACE IGNITION MODULE ...

Page 12: ...ted Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 69 0924 2 J S Rev 6 98 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Reviews: