Page 1: ...n model max ignition activation periods q S890 provides 30 sec min prepurge on initial trial for ignition 0 Compatible with Norton 201 and 271 or equivalent hot surface igniters 0 S89D H and S890D H require a separate sensor mounted on burner Q354 recommended i Available with leadwires for line voltage connections 0 Available with Molex plug for connecting D80D Vent Damper Cl Modules can be used o...

Page 2: ...fire parts com ...

Page 3: ...s required to complete the system must be ordered separately They include DUAL VALVE COMBINATION GAS CONTROL Any di rect ianition aas control with 2 0 A max main valve Igniter must reach 1000 C 11832 Fj within 34 seconds with 102 Vat applied Igniter must maintain at least 500M ohms insulation resistance between the igniter leadwires and the igniter mounting bracket Igniter must not develop an insu...

Page 4: ...fire parts com ...

Page 5: ... of checkout frequency Any control should be replaced if it does not perform properly on checkout or troubleshooting In addition re place any module if it is wet or looks like it has ever been wet MOUNT IGNITION MODULE Select a location close enough to the burner to allow a short direct cable route to the igniter Ambient tempera ture at the module must be within the range of minus 40 F to plus 175...

Page 6: ... Fig 3 2 Refer to heating appliance manufacturer s instruc tions for wiring auxiliary controls 3 Adjust thermostat heat anticipator to match system current draw The current draw equals the total current required for the ignition module 0 2 A plus the gas control and any other auxiliary equipment in the control circuit Connect Gas Control Use No 18 gauge solid or stranded wire Use 3 l 6 in femalequ...

Page 7: ... NOT BE IN GROUND LEG TO TRANSFORMER M2200 FIG 3 S89D H AND S890D H IN AN ATMOSPHERIC BURNER HEATING SYSTEM DUAL VALVE COMBINATION S99C G JiS89OC G J HOT SURFACE DSOD VENT DAMPER CONTROLLER OR CONTROLLER A 1 POWER SUPPLY PROVIDE DISCONNECT MEANS A REMOVE PLUG ONLY IF USING VENT DAMPER FUSE SLOWS ON AND PROTECTION AS REQUIRED A STARTUP WHEN PLUG IS REMOVED THEN MODULE WILL ALTERNATE LIMIT CONTROLLE...

Page 8: ...AMPER N L1 1 A I Ls A Ll HOT r 7 HOT 4 L2 I b ma L2 b COMSUSTlON COMBUSTION AIR BLOWER AIR SLOWER THERMOSTAT x RELAY OR CONTROLLER MOTOR DUAL VALVE COMBINATION SS9C G JlS89OC G J HOT GAS CONTROL SURFACE IGNITION CONTROL I HOT AIR _I PROVING _t SWITCH T I_ DAMPER PLUG OA 0 II LIMIT CONTROLLER n 1 POWER SUPPLY PROVIDE DISCONNECT MEANS A CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND AND OVERLOAD PROT...

Page 9: ...A LEADWIRE MODEL IS COLOR CODED AS SHOWN M2194 FIG 7 S89C G J AND S890C G J IN A TWO STAGE FAN ASSISTED COMBUSTION HEATlNG SYSTEM MEUSTION AIR HOT SURFACE IGNITER SENSOR A POWER SUPPLY PROVIDE DISCONNECT MEANS A FOR MODULE WITH TH W TERMINAL AND VENT AND OVERLOAD PROTECTION AS REOUIRED DAMPER PLUG JUMPER TH W AND 24V TERMINALS A OPTIONAL LIMITCONTROLLER LOCATION Do NOT REMOVE VENT DAMPER PLUG A A ...

Page 10: ... Ll HOT A CONNECT COLORS OF WIRE AS SHOWN A FOR MOOULE WlTH TH W ERMINAL AND VENT DAMPER PLUG JUMPER TH W AND 24V TERMINAL DO NOT REMOVE VENT DAMPER PLUG A FACTORY TEST TERMINAL DO NOT USE A LEADWIRE MODEL IS COLORCOOEO AS SHOWN A LEAVE TP i AND Z W JUMPERS IN PLACE HOT SURFACE IGNITER SENSOR M2196 FIG 9 S89C J AND S89OC J IN A HYDRONIC HEATING SYSTEM WITH ATMOSPHERIC BURNER 10 fire parts com ...

Page 11: ...nd 5 below on initial installation and any time work is done involving the gas plp ing STEP 1 Perform Visual inspection 0 With power off make sure all wiring connections are clean and tight 0 Turn on power to appliance and ignition module 0 Open manual shutoff valves in the gas line to the appliance 0 Do gas leak test upstream of gas control if piping has been disturbed GAS LEAK TEST Paint pipe jo...

Page 12: ...or heat from the thermostat On proof of airflow the air proving switch closes and energizes the S890 When the S890 is used in an atmospheric system the call for heat energizes the module In either case the S890first initiates a30 sec minimum delay to allow system prepurge After prepurge the S890 energizes the igniter to start the igniter warmup IGNITER WARMUP Following prepurge timing S890 or call...

Page 13: ...e third trial the gas control closes and the module locks out It must be manually reset by removing power or setting the thermo stat below room temperature for at least 45 sec If the burner goes out during the run cycle the gas control closes and the module checks for the number of ignition trials performed during the current call for heat If the number is less than three the module initiates a pu...

Page 14: ...essary to protect the ground wire from radiant heat Check temperature at the igniter ceramic or flame sensor insulator Excessive temperature will permit leakage to ground Provide shield if tempera ture exceeds rating of igniter or sensor lf flame sensor or bracket is bent out of position restore to correct position Replace igniter and sensor or igniter sensor with identical unit if insulator is cr...

Page 15: ...ONTlNWTY OF GROUND WIRE MAKE SURE Ll AND U ARE NOT REVERSED THIS WOULD PREVENT FLAME DETECTION CHECK THAT BURNER FLAME COVERS IGNITEWSENSOR OR SENSOR CHECK INSULATION ON lGNlTEWSENSC43 LEADS C G AND J MCOELS CHECK INSULATION ON SENSOR LEADB AND CHECK SENSOR POSlnON D AND H MODELS IF CHECKS ARE OKAY REPUCE S8Q SBQO MODULE NOTE IF SBQlsaW GOES INTO LOCKOUT RESET SYSTEM CHECK CONTINUITY OF GROUND WIR...

Page 16: ...UAL VALVE GAS CONTROL 2 AMP MAX A SEN TERMINAL REPLACES CONNECTION BEMlEEN HSI TERMINAL AND SENSOR CIRCUIT ON MODELS WITH SEPARATE IGNITER AND SENSOR M2199 FIG 1 89 S890 SIMPLIFIED SCHEMATIC Honeywell Inc 1885 Douglas Drive N Golden Valley MN 55422 4386 International Sales Offices in all principal cities of the world Manufacturing in Australia Canada Finland France Germany Japan Mexico Nethetiands...