Honeywell S437A Product Data Download Page 3

S437A,B, S637A SAIL SWITCHES

3

60-2186—2

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Disconnect power supply before connecting wiring 

to prevent electrical shock and equipment damage.

Mounting

Plan the location so that the sail will be in the direct path of an 

unrestricted air stream. A horizontal duct run is best because 

the sail will then move horizontally. In a vertical duct, the effect 

of gravity on the linkage changes the operating characteristics 

somewhat.

1.

At the desired location, cut a rectangle hole 1-1/2 x 2 in. 

See dotted lines in dimension drawing.

2.

Note direction of air stream and position chassis as a 

template to make the two mounting hole locations.

3.

Center punch and drill mounting holes. Secure device 

with sheet metal screws.

WIRING

Disconnect power supply before making wiring connections to 

avoid possible electrical shock or equipment damage. All 

wiring must agree with local codes and ordinances.

Wire the sail switch in series with the load to act as an air 

velocity limit switch.

Fig. 2. S437 Schematic and Typical Connections

Fig. 3. S637 Schematic and Typical Connections.

Set Differential

The knurled wheel at the base of the switch is marked with the 

letters A, B, C, D to indicate relative differentials from minimum 

to maximum. Follow instructions of system manufacturer, if 

available, or adjust to suit actual operation.

A minimum differential setting (position A) of approximately 

550 fpm (2.8 m/s) results in a make velocity of approximately 

1900 fpm (9.7 m/s). The break velocity is 1350 fpm (6.9 m/s) 

for any setting of the differential.

Sail Size

All velocities given above are for a standard size sail. The large 

sail operates the switch at reduced velocities.

To control at higher velocities, the size of the sail must be 

reduced in inverse proportion.

Example: 2 x velocity = 1/2 sail size.

CHECKOUT

Operate the system through at least one complete cycle to 

make certain all equipment is controlled properly.

1 SWITCH MAKES ON INCREASING AIR VELOCITY.

1

M27087

TO 

LOAD

S437A, B

NC

NC

C

TO 

SIGNAL

COMMON

TO 

LOAD

S637A

1 SWITCH MAKES C TO NO ON INCREASING AIR VELOCITY.

M27088

Summary of Contents for S437A

Page 1: ...required to close the snap switch contacts Switch differential can be manually adjusted by turning a knurled knob on the snap switch A conduit knockout is located on each end of the case for wiring convenience SPECIFICATIONS Mounting Position Velocity characteristics listed apply when standard size sail is inserted in a horizontal air stream with the sail pivot in a vertical position Vertical moun...

Page 2: ... 5 11 59 Guide No MFHX S437B File No MP2168 Vo 2 dated 5 11 59 Guide No MFHX2 Component Recognized Canadian Standards Association Certification Listed S File No LR95329 Class 481302 Fig 1 S437 Dimensions in in mm in Brackets MODEL NO INCLUDES CASE AND COVER SWITCHING ACTION ON INCREASING VELOCITY SWITCHING ACTION ON DECREASING VELOCITY SWITCH DIFFERENTIAL S437A YES Spst Normally open contacts clos...

Page 3: ...crews WIRING Disconnect power supply before making wiring connections to avoid possible electrical shock or equipment damage All wiring must agree with local codes and ordinances Wire the sail switch in series with the load to act as an air velocity limit switch Fig 2 S437 Schematic and Typical Connections Fig 3 S637 Schematic and Typical Connections Set Differential The knurled wheel at the base ...

Page 4: ...tered Trademark 2007 Honeywell International Inc 60 2186 2 J I Rev 10 07 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resultin...

Reviews: