Honeywell RV284 Installation Instructions Manual Download Page 6

Honeywell GmbH

4

MU1H-1204GE23 R0212

GB

1. Safety Guidelines

1. Follow the installation instructions.
2. Use the appliance

• according to its intended use
• in good condition
• with due regard to safety and risk of danger.

3. Note that the appliance is exclusively for use in the appli-

cations detailed in these installation instructions. Any 
other use will not be considered to comply with require-
ments and would invalidate the warranty.

4. Please take note that any assembly, commissioning, 

servicing and adjustment work may only be carried out by 
authorized persons.

5. Immediately rectify any malfunctions which may influence 

safety.

2. Description of function

Spring loaded check valves have a moving seal disc which is 
lifted off the seat by a greater or lesser amount depending on 
the flow rate through the valve. If the flow falls towards zero, 
then the spring pushes the disc back onto the seat and seals 
the waterway.
To ensure continuing correct function it is recommended that 
check valves be regularly checked and maintained (as speci-
fied in EN 1717).

3. Application

4. Technical data

5. Scope of delivery

The check valve comprises:
• Housing
• Check valve insert (DVGW-certified)
• Test plug with seal ring

6. Options

7. Assembly

7.1. Installations Guidelines

• Install in horizontal pipework with test and drain plug down-

wards
- This position is best for draining

• Install shutoff valves

- Shutoff valves provide optimal serviceability

• Ensure good access

- Simplifies maintenance and inspection

• Install right after water meter if applicable

- Protects against backflow from water systems

7.2. Assembly instructions

1. Thoroughly flush pipework
2. Close shutoff valve on inlet
3. Release pressure on outlet side (e.g. through water tap)
4. Close shutoff valve on outlet
5. Fit check valve for example between water meter and 

pressure reducing valve, filter or filter combination
• Note flow direction
• Install without tension or bending stresses

6. Slowly open shut off valves on inlet and outlet

8. Maintenance

8.1. Inspection

8.1.1. Check valve

1. Close shutoff valve on inlet
2. Open test valve

• Until the pressure is released, some water will flow out 

of the test valve. After a short period of time the water 
flow should stop. If the water continues to drip or run, 
then the check valve must be replaced - see servicing 
of check valve

3. Close test valve again
4. Slowly open shutoff valve on inlet

Medium

Water

Operating temperature
accord. DIN EN 13959

max. 65 °C
(short term operation up to 90°C)

Max. inlet pressure

25.0 bar

Opening pressure

0.05 bar

Connection size

With internal thread 

1

/

2

" - 2"

RV284-... A =

With internal thread

Connection size

Interval: once a year

Summary of Contents for RV284

Page 1: ...n instructions Anleitung zum späteren Gebrauch aufbewahren Keep instructions for later use Rückflussverhinderer Check valve EBA RV284 Rev A Strandvejen 42 Saksild 8300 Odder 86 62 63 64 www automatikcentret dk info automatikcentret dk ...

Page 2: ... 5 Lieferumfang 2 6 Varianten 2 7 Montage 2 8 Instandhaltung 2 9 Entsorgung 3 10 Störungen Fehlersuche 3 11 Serviceteile 3 GB 1 Safety Guidelines 4 2 Description of function 4 3 Application 4 4 Technical data 4 5 Scope of delivery 4 6 Options 4 7 Assembly 4 8 Maintenance 4 9 Disposal 5 10 Troubleshooting 5 11 Spare Parts 5 ...

Page 3: ...MU1H 1204GE23 R0212 Honeywell GmbH bar 6 8 10 4 2 0 7 2 6 4 5 2 6 bar 6 8 10 4 2 0 1 4 3 2 8 1 1 11 1 2 3 ...

Page 4: ... ein optimaler Service gewährlei stet Auf gute Zugänglichkeit achten Vereinfacht Wartung und Inspektion Bei Hausanschluss direkt nach der Wasserzähleranlage einbauen Schutz gegen Rückfließen von Wasser aus Verbrauchsanlagen 7 2 Montageanleitung 1 Rohrleitung gut durchspülen 2 Absperrarmatur eingangsseitig schließen 3 Ausgangsseite druckentlasten z B durch Wasser zapfen 4 Absperrarmatur ausgangssei...

Page 5: ...erhinderer nicht ganz geöffnet Absperrventile öffnen Ventilkegel klemmt in Führung Ventilkegel austauschen Druckanstieg im Vordruckbereich Schließt im Vordruckbereich nicht dicht abVentilkegel und Lippendichtring austau schen Dichtflächen verschmutzt oder verschlissen Dichtelemente reinigen ggf austauschen Schlagende Geräusche Rückflussverhinderer zu groß dimensio niert Technische Kundenberatung a...

Page 6: ...sembly 7 1 Installations Guidelines Install in horizontal pipework with test and drain plug down wards This position is best for draining Install shutoff valves Shutoff valves provide optimal serviceability Ensure good access Simplifies maintenance and inspection Install right after water meter if applicable Protects against backflow from water systems 7 2 Assembly instructions 1 Thoroughly flush ...

Page 7: ...cycling disposal 10 Troubleshooting Disturbance Cause Remedy No or too small water flow rate Stop valve in front of or below the check valve is not fully opened Open shutoff valves Valve cone jams in the guide Replace the valve cone Rise in pressure in the prepressure sectionNot sealing properly in the prepressure section Replace the valve cone and the lip sealing ring Sealing surfaces soiled or w...

Page 8: ...0 Fax 49 6261 81309 www honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland by its Authorised Represen tative Honeywell GmbH MU1H 1204GE23 R0212 Subject to change 2012 Honeywell GmbH ...

Reviews: