Honeywell RV181 Installation Instructions Manual Download Page 6

MU1H-1228GE23 R1215

4

Honeywell GmbH

GB

1. Safety Guidelines

1. Follow the installation instructions.
2. Use the appliance

• according to its intended use
• in good condition
• with due regard to safety and risk of danger.

3. Note that the appliance is exclusively for use in the appli-

cations detailed in these installation instructions. Any 
other use will not be considered to comply with require-
ments and would invalidate the warranty.

4. Please take note that any assembly, commissioning, 

servicing and adjustment work may only be carried out by 
authorized persons.

5. Immediately rectify any malfunctions which may influence 

safety.

2. Description of function

The check valve protected the service pipe.
Spring loaded check valves have a moving seal disc which is 
lifted off the seat by a greater or lesser amount depending on 
the flow rate through the valve. If the flow falls towards zero, 
then the spring pushes the disc back onto the seat and seals 
the waterway.
To ensure continuing correct function it is recommended that 
check valves be regularly checked and maintained (as speci-
fied in EN 1717).

3. Application

4. Technical data

5. Scope of delivery

The check valve comprises:
• Housing
• Connections (Design B and K)
• Check valve insert (DVGW-certified)
• Test plugs with seal ring

6. Options

7. Assembly

7.1. Installations Guidelines

• In a drinking water supply the check valves are fitted 

immediately after the water meter.
- This position ensures optimum protection for the drin-

king water supply.

• Install in horizontal pipework with test plugs directed down-

wards.
- This position ensures optimum protection efficiency.
- This position is best for testing the valve

• Shut off valves should be fitted on each side of the check 

valve.
- Shut off valves enables fast testing

• The installation location should be protected against frost 

and be easily accessible

7.2. Assembly instructions

1. Thoroughly flush pipework
2. Close shutoff valve on inlet
3. Release pressure on outlet side (e.g. through water tap)
4. Close shutoff valve on outlet
5. Fit check valve for example between water meter and 

pressure reducing valve, filter or filter combination
• Note flow direction
• Install without tension or bending stresses

6. Slowly open shut off valves on inlet and outlet

8. Maintenance

8.1. Inspection

8.1.1. Check valve

1. Close shutoff valve on inlet
2. Open test valve

• Until the pressure is released, some water will flow out 

of the test valve. After a short period of time the water 
flow should stop. If the water continues to drip or run, 
then the check valve must be replaced - see mainte-
nance of check valve

3. Close test valve again
4. Slowly open shutoff valve on inlet

Medium

Water

Liquid category

2 (no hazardous materials)

Installation position

horizontal pipework with test plugs 
directed downwards

Operating pressure

max. 16 bar

Operating temperature
accord. DIN EN 13959

Water up to 65 °C 
(short term up to 90 °C)

Connection size

1

/

2

" to 2" (threaded and soldering 

connections)
ø15 and ø22 (compression connec-
tion)

RV181-...B =

External threaded connection set

RV181-...K =

Compression connection set

Connection size

Interval: once a year

Summary of Contents for RV181

Page 1: ...RV181 Einbauanleitung Installation instructions Anleitung zum späteren Gebrauch aufbewahren Keep instructions for later use Rückflussverhinderer Check valve EBA RV181 Rev C ...

Page 2: ...echnische Daten 2 5 Lieferumfang 2 6 Varianten 2 7 Montage 2 8 Instandhaltung 2 9 Entsorgung 3 10 Störungen Fehlersuche 3 GB 1 Safety Guidelines 4 2 Description of function 4 3 Application 4 4 Technical data 4 5 Scope of delivery 4 6 Options 4 7 Assembly 4 8 Maintenance 4 9 Disposal 5 10 Troubleshooting 5 ...

Page 3: ...MU1H 1228GE23 R1215 Honeywell GmbH bar 6 8 10 4 2 0 7 2 6 4 5 2 6 bar 6 8 10 4 2 0 1 4 3 2 8 1 1 ...

Page 4: ...n optimaler Schutz für das Trinkwasserversorgungsnetz gewährleistet Einbau in waagrechte Rohrleitung mit Prüfstopfen nach unten In dieser Einbaulage ist ein optimaler Schutz gewährlei stet In dieser Einbaulage ist eine optimale Prüfmöglichkeit gewährleistet Absperrarmaturen vor und nach dem Rückflussverhin derer einbauen Mit Absperrarmaturen ist eine schnelle Prüfung möglich Der Einbauort muss fro...

Page 5: ...ssverhinderer aus hochwertigem Kunst stoff Schließfeder aus rostfreiem Federstahl Prüfschrauben aus hochwertigem Kunststoff Dichtring aus NBR Durchführung durch ein Installationsunternehmen Die örtlichen Vorschriften zur ordnungsgemäßen Abfall verwertung bzw Beseitigung beachten 10 Störungen Fehlersuche Störung Ursache Behebung Kein oder zu wenig Durchfluss Absp1215errventil vor oder hinter dem Rü...

Page 6: ...tection for the drin king water supply Install in horizontal pipework with test plugs directed down wards This position ensures optimum protection efficiency This position is best for testing the valve Shut off valves should be fitted on each side of the check valve Shut off valves enables fast testing The installation location should be protected against frost and be easily accessible 7 2 Assembl...

Page 7: ...nthetic material check valve cartridge Closing spring made of stainless spring steel Test plugs in high grade synthetic material NBR seal ring To be carried out by an installation company Observe the local requirements regarding correct waste recycling disposal 10 Troubleshooting Disturbance Cause Remedy No or too small water flow rate Stop valve in front of or below the check valve is not fully o...

Page 8: ... 49 6261 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland by its Authorised Represen tative Honeywell GmbH MU1H 1228GE23 R1215 Subject to change 2015 Honeywell GmbH ...

Reviews: