
Conversion Wiring Diagrams
for RM7838A
B. M. • 7-92 • © Honeywell Inc. 1992 • Form Number 65-0129
The diagrams and instructions contained in this booklet are for converting the following model
semi-automatic controls to RM7838 microprocessor based integrated burner control.
TABLE OF CONTENTS
Page
Product Section Matrix ..................................................................................................................................................... 3
Section I .............................................................................................................................................................................. 5
R4138A,B,C,D
Section II ............................................................................................................................................................................ 6
Honeywell W124
Section III ........................................................................................................................................................................... 8
Fireye 26SJ5 6000, 6052, 6152
WARNING
Improper configuration jumper selection could cause a fire or explosion hazard that could lead to property
damage, severe injury or death.
CAUTION
1. Installer must be a trained, experienced, flame safeguard control service technician.
2. Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. More
than one power supply disconnect may be involved.
3. All wiring must comply with applicable local electrical codes, ordinances, and regulations.
4. All line voltage terminal wiring shall be no. 14, 16 or 18 copper conductor TTW (60C) or THW (75C) or THHN
(90C) 600 volt insulation wire. A maximum of two conductors can be wired to each Q7800 Subbase terminal.
5. Voltage and frequency of the power supply and flame detector(s) connected to this control must agree with those
marked on the device.
6. Loads connected to the control terminals must not exceed ratings listed in the Specification, form 65-0108, or on
the RM7838A label.
7. All external timers must be listed or component recognized by authorities having jurisdiction for the specific purpose
for which they are used.
8. Perform all required checkout tests after installation is complete.