Honeywell RM7830A Series Installation Instructions Manual Download Page 10

10

EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES

66-1092—2

Table 3D. EC7850A Terminal Ratings.

a

See Table 2.

b

2000 VA maximum connected load to relay module.

c

Total load current, excluding Burner/Boiler Motor and Firing Rate Outputs cannot exceed 5A, 25A inrush for 250,000 cycles.

d

Can also be 24 Vac, 3A at PF = 0.5.

e

220/240 Vac to 120 Vac, 10 VA stepdown transformer (not provided) must be used to drive the shutter.

Mounting EC/RM7830A;
EC/RM7850A Relay Module

1. Mount the relay module vertically on the Q7800

Subbase, or mount horizontally with the knife blade
terminals pointing down. When mounted on the
Q7800A, the relay module must be in an electrical
enclosure.

2. When mounting in an electrical enclosure, provide

adequate clearance for servicing, installation and
removal of the relay module, KDM, flame amplifier,
flame amplifier signal voltage probes, electrical signal
voltage probes and electrical connections.

a.

Allow an additional 2 in. (51 mm) below the relay
module for the flame amplifier mounting.

b.

Allow an optional 3 in. (76 mm) minimum on both
sides of the relay module for electrical signal
voltage probes.

3. Make sure no subbase wiring is projecting beyond the

terminal blocks. Tuck in wiring against the back of the
subbase so it does not interfere with the knife blade
terminals or bifurcated contacts.

IMPORTANT

Install the relay module with a plug-in motion rather
than a hinge action.

4. Mount the relay module by aligning the four L shaped

corner guides and knife blade terminals with the
bifurcated contacts on the wiring subbase and securely
tightening the two screws without deforming the plastic.

STATIC CHECKOUT

After checking all wiring, perform this checkout before
installing the relay module on the wiring subbase. These tests
verify that the Q7800 Wiring Subbase is wired correctly and
the external controllers, limits, interlocks, actuators, valves,
transformers, motors and other devices are operating
properly.

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
Close all manual fuel shutoff valves before starting
this test to prevent an explosion.

Terminal No.

Abbreviation

Description

Ratings

G

Flame Sensor Ground

a

Earth G

Earth Ground

a

N

Line Voltage Common(Neutral)

3

AL

Alarm (Normally Open)

220/230/240 Vac, 1A, 10A inrush for 5000 cycles.

4

L1

Line Voltage Supply (L1)

220 to 240 Vac (+10/-15%), 50/60 Hz (

±

10%).

b

5

FAN

Burner/Blower Motor

220/230/240 Vac, 4A at PF = 0.5, 20A inrush.

6

RT

Limits and Burner Control

220/230/240 Vac, 1 mA.

7

LD2

Airflow Switch Input

220/230/240 Vac, 5A.

8

PV1

Pilot Valve 1 (Interrupted)

220/230/240 Vac, 4A at PF = 0.5, 20A inrush.

c

9

M V

Main Fuel Valve

220/230/240 Vac, 4A at PF = 0.5, 20A inrush.

c

10

IGN

Ignition

220/230/240 Vac, 2A at PF = 0.2.

c

F(11)

Flame Signal

136 to 220 Vac, current limited.

12

HI

Firing Rate High Fire

220/230/240 Vac, 0.5A at PF = 0.5.

d

13

COM

Firing Rate Common

220/230/240 Vac, 0.5A at PF = 0.5.

d

14

MOD

Firing Rate Modulate

220/230/240 Vac, 0.5A at PF = 0.5.

d

15

LO

Firing Rate Low Fire

220/230/240 Vac, 0.5A at PF = 0.5.

d

16

Alarm (normally closed)

220/230/240 Vac, 1A, 10A inrush for 6000 cycles;
carry 5A for 250,000 cycles.

17

ES2

Preignition  Interlock  Input

220/230/240 Vac, 1 mA.

18

ES1

Low Fire Switch Input

220/230/240 Vac, 1 mA.

19

ES3

High Fire Switch Input

220/230/240 Vac, 1 mA.

20

LOS

Lockout Input

220/230/240 Vac, 1 mA.

21

PV2

Pilot Valve 2 (Intermittent)

220/230/240 Vac, 4A at PF = 0.5, 20A inrush.

c

22

SHTR

Shutter

Shutter drive for dynamic self-check flame sensor.

e

Summary of Contents for RM7830A Series

Page 1: ...ES Relay Modules Checkout and Troubleshooting Product Data SPECIFICATIONS Electrical Ratings See Tables 3A 3B 3C and 3D Voltage and Frequency RM7830A and RM7850A 120 Vac 10 15 50 60 Hz 10 EC7830A and EC7850A 220 240 Vac 10 15 50 60 Hz 10 Power Dissipation 10W maximum Maximum Total Connected Load 2000 VA Fusing Total Connected Load 20A maximum type FRN or equivalent Environmental Ratings Ambient Te...

Page 2: ...nd if not installed and used in accordance with the instructions can cause interference with radio communications It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area can ca...

Page 3: ... Voltage wiring 5 For recommended wire size and type see Table 1 6 For recommended grounding practices see Table 2 Fig 1 Internal block diagram of EC RM7830A see Fig 3 for detailed wiring instructions L1 HOT N 1 5 2 CONFIGURATION JUMPERS PLUG IN PURGE TIMER CARD F G 22 PLUG IN FLAME AMPLIFIER MICROCOMPUTER RUN TEST SWITCH RESET PUSHBUTTON FLAME SIGNAL TEST JACK RELAY DRIVE CIRCUIT 1K 2K 3K 4K 5K 6...

Page 4: ...LAY MODULE RS485 16 1K1 2K2 5K1 4K1 7K1 2K1 PV1 PV2 MV 3K1 6K1 7 ES1 ES3 ES2 3K2 SAFETY RELAY CIRCUIT 20 6 FAN AL IGN AL DDL 13 15 14 12 HIGH FIRE COMMON LOW FIRE MODULATE REMOTE RESET 8K1 8K2 9K2 9K1 INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLTAGE INPUTS RELAY CONTACT OPEN INTERNAL WIRING FIELD WIRING RELAY COIL RELAY CONTACT CLOSED DDL COMMUNICATIONS 1 2 3 5 F G 22 USER TERMI...

Page 5: ...ER PILOT FLAME MAIN ALARM STANDBY RUN STANDBY PRE IGNITION PILOT STABIL MAIN STABIL IGNITION BURNER POSTPURGE MAIN VALVE LIMITS AND BURNER CONTROL CLOSED LOCKOUT INPUT 10 sec AIRFLOW SWITCH CHECK PILOT VALVE V2 PREIGNITION INTERLOCK OPTIONS SAFE START CHECK FLAME PROVING 3 sec 5 sec 5 sec 1 IF ON AT CALL FOR HEAT HOLD 120 sec LOCK OUT IF STILL ON 3 or 5 sec 3 or 5 sec SAFE START CHECK IF OFF AFTER...

Page 6: ...OWER PILOT FLAME MAIN ALARM STANDBY RUN STANDBY PURGE OR WAITING PRE IGNITION PILOT STABIL MAIN STABIL IGNITION BURNER POSTPURGE MAIN VALVE LIMITS AND BURNER CONTROL CLOSED LOCKOUT INPUT 10 sec AIRFLOW SWITCH CHECK PILOT VALVE V2 PREIGNITION INTERLOCK OPTIONS SAFE START CHECK FLAME PROVING 3 sec 5 sec 5 sec 1 IF ON AT CALL FOR HEAT HOLD 120 SEC LOCK OUT IF STILL ON IF OFF AFTER 10 SEC OF FAN LOCK ...

Page 7: ...ength of all Data ControlBus Module interconnecting wire is 4000 feet 1219 meters 10 Be sure loads do not exceed the terminal ratings Refer to the label on the relay module or to the terminal ratings in Tables 3A 3B 3C and 3D Final Wiring Check 1 Check the power supply circuit The voltage and frequency tolerance must match those of the relay module A separate power supply circuit can be required f...

Page 8: ... at PF 0 5 20A inrush d 10 IGN Ignition 120 Vac 2A at PF 0 2 d F 11 Flame Signal 60 to 220 Vac current limited 16 Control Voltage 120 Vac 10 15 17 ES2 Preignition Interlock Input 120 Vac 1A 10A inrush for 5000 cycles Carry 5A for 250 000 cycles 20 LOS Lockout Input 120 Vac 1 mA 21 PV2 Pilot Valve 2 Intermittent 120 Vac 4A at PF 0 5 20A inrush d 22 SHTR Shutter Shutter drive for dynamic self check ...

Page 9: ...PF 0 5 20A inrush c 6 RT Limits and Burner Control 120 Vac 1 mA 7 LD2 Airflow Switch Input 120 Vac 5A 8 PV1 Pilot Valve 1 Interrupted 120 Vac 4A at PF 0 5 20A inrush d 9 M V Main Fuel Valve 120 Vac 4A at PF 0 5 20A inrush d 10 IGN Ignition 120 Vac 2A ignition d F 11 Flame Signal 60 to 220 Vac current limited 12 HI Firing Rate High Fire 120 Vac 0 5A at PF 0 5 e 13 COM Firing Rate Common 120 Vac 0 5...

Page 10: ...ATIC CHECKOUT After checking all wiring perform this checkout before installing the relay module on the wiring subbase These tests verify that the Q7800 Wiring Subbase is wired correctly and the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Close ...

Page 11: ...for correct connections tight terminal screws correct wire and proper wiring techniques 8 Replace all damaged or incorrectly sized wires 9 Replace faulty controllers limits interlocks actuators valves transformers motors and other devices as required 10 Make sure normal operation is obtained for each required test before continuing the checkout 11 After completing each test be sure to open the mas...

Page 12: ... 1 Recycle limits 2 Burner control 6 4 16 5 4 2 7 1 Fan Burner Motor or Blower starts 2 Line voltage at terminal 7 1 Fan circuit a Manual fan switch b Fan power supply overload protection and starter c Fan 2 Running limits of Airflow Switch LD2 input NOTE Remove jumpers and re connect alarm if used 7 4 10 Ignition spark if ignition transformer is connected to terminal 10 1 Watch for spark or liste...

Page 13: ...abled and the Airflow Switch is closed for 120 seconds with Limits and Burner Control closed d Ignition pilot valve intermittent pilot valve terminal is energized e Main valve terminal is energized f Internal system fault g Purge card is not installed or removed h Purge card is defective i Lockout Input opens during STANDBY 3 PURGE Period a Preignition Interlock opens anytime during purge b Flame ...

Page 14: ... detection b AC line noise that can prevent a sufficient reading of the line voltage inputs c Low line voltage brownouts The INITIATE sequence also delays the burner motor starter from being energized and de energized from an intermittent AC line input or control input Standby The relay module is ready to start an operating sequence when the operating control input determines a call for heat is pr...

Page 15: ...releases to modulation 2 The relay module is now in RUN and remains in RUN until the controller input terminal 6 opens indicating that the demand is satisfied or a limit has opened Postpurge The relay module model specific provides a two 15 or 30 second POSTPURGE following the completion of the RUN period The blower motor output is powered to drive all combustion products and any unburned fuel fro...

Page 16: ...umpers The relay module has three site configurable jumper options see Fig 6 and Table 6 If necessary clip the site configurable jumpers with side cutters and remove the resistors from the relay module The relay module reads the settings of these configuration jumpers at startup After 200 hours of main valve operation the relay module locks the jumper settings into internal memory If these jumpers...

Reviews: