Specifications  

Physical:  Width:   2-1/8” (53mm)   
Height:  3-1/4” (84mm)   Depth:   1” (25mm) 

Electrical: 

Polling loop input voltage range:   8-12VDC 
Polling loop current draw:   7mA (continuous) 
Relay contact rating:   2A @ 28VAC/VDC, resistive loads 

Aux Zone:

 

   10k EOLR (internal when white jumper intact; external 

when white jumper cut 

  300 ohm max zone resistance (excluding EOLR) 

  Responds to open or short circuit faults having 250mSec 

or longer duration 

  Class B (style B when used with panels providing earth 

ground fault detection) 

  For UL Commercial Fire Applications, must be used as 

N.O. zone and white jumper must be cut

 

 

Agency Listings  

  UL864 Commercial Fire 

  UL985 Household Fire 

  UL1023 Household Burglary 

  UL609 Commercial Burglary 

  CSFM  

  FM 

  MEA  

Warranty 

For the latest warranty information, please go to: 

http://www.honeywell.com/security/hsc/resources/wa/

TAMPER SWITCH

MOUNTING SCREW
HOLES (IN CASE BACK) 

4101SN

TERM. ASSIGNMENT

1 (+) POLLING LOOP

POLLING LOOP

(+)


3 (+) AUX ZONE (+)

RELAY N.O.

5

RELAY N.C.

RELAY C

+

+

POLLING LOOP - CLASS B, STYLE 4
MAX WIRING IMPEDANCE 25 OHMS

+

POLLING LOOP
TERMINALS ON
CONTROL

1  2  3 

4  5  6 

RELAY C CONTACT
RELAY N.C. CONTACT
RELAY N.O. CONTACT

10K EOLR

(USE ONLY IF WHITE

JUMPER IS CUT)

N.O. N.C.C

MOUNTING

CASE BACK

TERMINAL

BLOCK TB1

(SUITABLE FOR

14-22 AWG WIRE)

COVER SCREW HOLE

WHITE JUMPER 

WIRING ACCESS
HOLES (SLOTS)

MOUNTING SCREW HOLE
(IN CASE BACK) 

N.C.

N.O.

AUX.

ZONE

OTHER

V-PLEX  MODULES

TM

4101SN-001-V5

(  )

(  )

Always Observe Polarity.

V-Plex and Aux Circuits are supervised
and power-limited.

See Panel's I.I. Text For Wire Gauge
And Wire Length Requirements.

Always Connect In Parallel.

If switching power through a
relay, the power must be from
a power-limited source.

Relays are programmable but
outputs are not supervised.

 

Figure 1. 4101SN V-Plex

 

Single Output Relay Module 

 

 

SEE THE CONTROL PANEL’S INSTALLATION INSTRUCTIONS FOR COMPLETE INFORMATION 

REGARDING LIMITATIONS OF THE ENTIRE SECURITY SYSTEM. 

 
 
 
 
 
 
 

 

 

Corporate Center Drive, Suite 100 

P.O. Box 9040, Melville, NY  11747 

© 2020 Resideo Technologies, Inc.  

www.resideo.com 

 

ÊK3166V3B>Š 

K3166V3B  10/12  Rev. B 