background image

Checking communication of system

1.  Check the 

R8810A

 is powered by looking at the 

LED.  It will blink red once per second.

2.  Check  that  there  is  sufficient  signal  strength 

from  the 

Wireless  Programmable  Room 

Thermostat

 by performing the following check:

  Hold  the 

Wireless  Programmable  Room 

Thermostat

 about 2-3 metres from the installed 

R8810A

.  Switch  the 

Wireless  Programmable 

Room Thermostat

 to the 

OFF

 mode then press 

the   and   buttons together with the   button for 

3 seconds. The 

Wireless Programmable Room 

Thermostat

 will send test signals to the 

R8810A

flashing  the  green  LED  on  every  6  seconds 

(relay output will remain off) for a maximum of 10 

minutes. When the green LED flashes on every 6 

seconds proceed to the next step.

Binding a new wireless component

1.  Switch  the 

Wireless  Programmable  Room 

Thermostat

 to the 

OFF

 mode.

2.  Hold  button  on  R8810A  for  5  seconds.    Red 

light will blink 1/2 second on and 1/2 second off 

when the device is in binding mode.

3.  Hold    ,   and program down buttons for 2 

seconds.    Display  will  show  “InSt  CO”,  with  a 

line  of  text  “CONTROL  BINDING”.    The  boiler 

and RF signal icons will be displayed.

4.  Press green   button.

5.  When Red LED on 

R8810A

 goes off, the devices 

are bound.

  If  binding  is  unsuccessful,  then  the  LED  will 

stay  on.  In  this  case,  move  the 

Wireless 

Programmable Room Thermostat

 and repeat 

the binding procedure from the beginning.

6.  Once binding is complete, switch the 

Wireless 

Programmable Room Thermostat

 back to the 

AuTO

 mode, the LED on the 

R8810A

 will flash 

green  every  10  seconds  to  indicate  that  the 

device is live.

Communications Loss

If the communication is lost for a period of 1 hour 

the red LED will flash to indicate that no messages 

have been received during the last hour.

In  the  event  of  a  communication  loss  signal, 

then  please  check  the  following  and  remedy  as 

necessary:

1.  Check the wiring between the 

W6560C system 

controller

 and correct if a fault is found.

2.  Check  the  RF  communication  between  the 

Wireless  Programmable  Room  Thermostat

 

using the method described above, and follow 

the check and binding procedure.

NB:  If a wireless outdoor temperature sensor type 

HB85 is installed, check the batteries and replace 

as necessary before following the communication 

loss procedure.

Electrical Guidance and Safety

•  The 

R8810A

  has  been  manufactured  in 

accordance with the following standards:

   

EN60730-1, EN60730-9

•  When  performing  any  work  with  this  product 

(installation, mounting, start-up), all instructions 

given by the manufacturer and in particular the 

safety  instructions  provided  in  the  Installation 

instructions must be followed.

•  Ensure  that  the 

R8810A

  wireless  receiver  is 

installed by a competent person.

•  Ensure  that  the 

R8810A

  wireless  receiver 

is  installed  according  to  local  electrical 

regulations.

•  Ensure that low voltage signal cables are kept 

as far apart as possible from AC mains voltage 

cables.

•  If  the 

R8810A

  is  modified  in  any  way,  except 

by the manufacturer, all warranties concerning 

operation and safety are invalidated.

50034666-001 B
© 2009 Honeywell International Inc.