R7120D BURNER CONTROL MODULES

15

66-1196EF—01

c. When the first stage burner flame is established, 

watch for the automatic second stage fuel valve(s) 

to open. Observe that the second stage lights off 

properly.

d. Make burner adjustments for flame stability and 

input rating. 

e. Shut down the system by lowering the setpoint of 

the operating controller. Make sure the burner flame 

goes out and all automatic fuel valves close. 

f. Go to step 19. 

19.

Restart the system by closing the burner switch and/or rais-

ing the setpoint of the operating controller. Observe that the 

burner flame is established during PILOT IGN, within the nor-

mal lightoff time specified by the equipment manufacturer. 

20.

Measure the flame signal. Continue to check for the proper 

signal through the RUN period. Check the signal at both 

high and low firing rate positions and while modulating. Any 

pulsating or unsteady readings require further attention. 

21.

Make sure all readings are in the required ranges

before proceeding.

NOTE: On completing these tests, open the master switch 

and remove all test jumpers from the subbase termi-

nals, limits/controls or switches. 

22.

Return the system to normal operation. 

Pilot Turndown Test 
(All Installations Using a Pilot)

Perform this check on all installations that use a pilot. The 

purpose of this test is to verify that the main burner can be lit 

by the smallest pilot flame that can hold in the flame amplifier 

and energize the FLAME LED. Clean the flame detector(s) to 

make sure that it detects the smallest acceptable pilot flame. 

If using AMPLI-CHECK™ or self-checking amplifier and 

1M ohm/voltmeter, the flame signal fluctuates every time the 

amplifier does a self-check or a shutter check. 

NOTE: Low fuel pressure limits, if used, could be open. If so, 

bypass them with jumpers during this test. 

1.

Open the master switch. 

2.

Close the manual main fuel shutoff valve(s). 

3.

Connect a manometer (or pressure gauge) to measure 

pilot gas pressure during the turndown test. 

4.

Open the manual pilot shutoff valve(s). 

5.

Close the master switch and start the system with a call 

for heat. Raise the setpoint of the operating controller. 

The R7120D sequence should start, and PREPURGE 

should begin.

6.

After the PILOT LED turns on in interrupted pilot appli-

cations, set the Run/Test Switch to the TEST position to 

stop the sequence. The FLAME LED comes on when 

the pilot ignites. 

NOTE: If the sequence does not stop, reset the system and 

make sure you set the Run/Test Switch to TEST 

within the first eight seconds of the PILOT IGN 

sequence. 

IMPORTANT

You have 0.8 second or three seconds, depending 

on PFEP selected, to position the Run/Test Switch to 

the TEST position to stop the sequence after the 

start of the PILOT IGN period. 

7.

Turn down the pilot pressure very slowly, reading the 

manometer (or pressure gauge) as it drops. Stop 

instantly when the FLAME LED goes out. Note the pres-

sure. The pilot is at the minimum turndown position. 

Immediately turn up the pilot pressure until the FLAME 

LED comes on again or the flame signal increases to 

1.25 Vdc. 

NOTE:

If there is no flame for 15 seconds with the Run/Test 

switch in the TEST position, the relay module locks out.

8.

Repeat step 7 to verify the pilot gas pressure reading at 

the exact point the FLAME LED light goes out. 

9.

Increase the pilot pressure immediately until the FLAME 

LED comes on, and then turn it down slowly to obtain a 

pressure reading just above the dropout point or until 

the flame signal increases to 1.25 Vdc. 

10.

Set the Run/Test Switch in the RUN position (if used) 

and let the sequence proceed. When the MAIN LED 

turns on, make sure the automatic main fuel valve(s) 

opens; then smoothly open the manual main fuel shutoff 

valve(s) (or any other manually-opened safety shutoff 

valve(s), if used) and watch for main burner ignition. If 

the main burner flame is established, go to step 18. 

NOTE: This step requires two people, one to open the man-

ual valve(s) and one to watch for ignition. 

11.

If the main burner flame is not established within five 

seconds, or within the normal lightoff time specified by 

the equipment manufacturer, close the manual main 

fuel shutoff valve(s) and open the master switch. If the 

lightoff is rough, the pilot flame size is too small. 

12.

Close the master switch to recycle the burner and stop 

the sequence in the PILOT period by using the 

Run/Test Switch. 

13.

Increase the pilot flame size by increasing its fuel flow 

until a smooth main flame is accomplished. 

14.

Reposition the flame scanner sight tube or use orifices 

until the pilot flame signal voltage is in the range of 1.25 

to 1.50 Vdc. 

15.

When the main burner lights reliably with the pilot at 

turndown, disconnect the manometer (or pressure 

gauge) and turn up the pilot gas flow to that recom-

mended by the equipment manufacturer.

16.

If used, remove the bypass jumpers from the subbase 

terminals, limits/controls, or switches. 

17.

Run the system through another cycle to check for

normal operation.

18.

Return the system to normal operation. 

Ignition Interference Test 
(All Flame Rods)

Ignition interference can subtract from (decrease) or add to 

(increase) the flame signal. If it decreases the flame signal 

enough, it causes a safety shutdown. If it increases the flame 

signal, it could cause the FLAME LED to come on when the 

true flame signal is below the minimum acceptable value. 

Start the burner and measure the flame signal with both 

ignition and pilot (or main burner) on, and then with only the 

pilot (or main burner) on. Any significant difference (greater 

than 0.5 Vdc) indicates ignition interference. 

Summary of Contents for R7120D

Page 1: ...eye D30 or E3XX SPECIFICATIONS Electrical Ratings See Table 2 Voltage and Frequency 120 Vac 10 15 50 60 Hz 10 Power Dissipation 10W maximum Maximum Total Connected Load 2000 VA Fusing Total Connected Load 15A Fast Blow type SC or equivalent Environmental Ratings Ambient Temperature Operating 40 F to 140 F 40 C to 60 C Storage 40 F to 150 F 40 C to 66 C Humidity 85 relative humidity continuous nonc...

Page 2: ...ge or failure Do not perform a dielectric test with the relay module installed Internal surge protectors can break down allowing relay module to fail the dielectric test and destroy the internal lightning and high current protection WARNING Electrical Shock Hazard Can cause serious injury death or equipment damage Disconnect power supply before beginning installation More than one disconnect may b...

Page 3: ... an electrical panel be sure there is ade quate clearance behind the closed door of the panel so there is no interference with the R7120 Mounting Other System Components Refer to Fig 9 for exploded view of installation or the applicable specification sheet for mounting other system components WARNING Fire or Explosion Hazard Can cause severe injury death or property damage Follow applicable safety...

Page 4: ...T JACK REMOTE RESET DDL DDL COMMUNICATIONS INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLT INPUTS FIELD WIRING INTERNAL WIRING PILOT PILOT V2 MAIN VALVE 1K 9K RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS 1K1 8K1 8K2 9K1 9K2 120 Vac 50 60 Hz FLAME SIGNAL TEST LOW FIRE SWITCH PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED R7120D2000 DOES NOT HAVE A PURGE INTERLOCK RS4...

Page 5: ...0 25 00 15 20 SWITCHING MOTOR ACTION BURNER BLOWER MOTOR LIMITS AND BURNER CONTROLLER CLOSED LOCKOUT INTERLOCKS CLOSED PII CLOSED LOW FIRE SW SAFE START CHECK FLAME PROVING 10 SEC IGN PILOT 5 M 13 TO 3 TO 3 TO M D TO 10 11 TO 10 X TO M32637 HIGH FIRE SW 8 TO 10 12 TO 10 12 TO M 13 P L1 MAIN VALVE 7 TIMED PREPURGE POWER FLAME MAIN PILOT ALARM POWER FLAME MAIN PILOT ALARM ALARM ALARM ALARM 00 SSC LE...

Page 6: ...ATE MOTOR 4 20mA CONTROLLER 135 OHM CONTROLLER AUTO LO COM HI AUTO LO COM HI LIMIT OPERATING SWITCHES BURNER SWITCH RUNNING INTERLOCK D10 EP100 OR D20 EP200 TYPICAL WIRING LOW FIRE START INTERLOCK PURGE INTERLOCK MASTER SWITCH LOCKOUT ALARM MAIN FUEL VALVE S PILOT VALVE S IGNITION TRANSFORMER 1 1 1 1 1 1 1 2 3 3 2 2 USED ONLY ON D10 OR EP100 SERIES PROGRAMMERS LOCATE THE PURGE INTERLOCK WIRE CONNE...

Page 7: ...PER MOTOR INITIATE INITIAL POWERUP ONLY POWER STANDBY PREPURGE HOLD DRIVE TO LOW FIRE POWER PILOT FLAME MAIN POWER PFEP 10 SEC 4 SEC IF JR1 CLIPPED PILOT FLAME MAIN POWER MFEP PILOT FLAME MAIN RUN POWER POSTPURGE POWER STANDBY 00 00 10 25 00 15 20 MOTOR ACTION BURNER BLOWER MOTOR INTERMITTENT PILOT VALVE LIMITS AND BURNER CONTROLLER CLOSED RUNNING INTERLOCKS CLOSED PII CLOSED LOW FIRE SW SAFE STAR...

Page 8: ...equired 250 VA pilot duty or 65 VA pilot duty in parallel with motorized valve s using a total of 1150 VA locked rotor inrush 460 VA to open and 250 VA to hold or motorized valve s using a total of 1500 VA locked rotor inrush 600 VA to open and 250 VA to hold L1 L2 S2 S1 A 8 7 6 5 13 12 X P D M 3 L2 N L1 L 11 10 FLAME DETECTOR UV BURNER BLOWER MOTOR VALVE PROOF OF CLOSURE LIMIT OPERATING SWITCHES ...

Page 9: ...iming Interlock Circuits Firing Rate Circuit Energy Saving Pre Purge Approval Code Bodies Pilot Main R7120D 2000 10 sec 4 or 10 sec 10 15 sec a or intermittent 15 sec Pre Ignition Running Low Fire 4 wire modulating No UL CSA Modulating R7120D 1002 10 or 15 sec Pre Ignition Lockout High and Low Fire FM IRI Modulating R7120D 3007 10 sec or intermittent Pre Ignition Running isolated Low Fire 2 wire i...

Page 10: ...LAME ESTABLISHING Period MFEP a Low Fire Switch Opens b Lockout Interlock opens R7120D1002 c Ignition pilot valve intermittent pilot valve terminal is not energized d Main valve terminal is not energized e No flame is present at the end of MFEP f Internal system fault occurs g Purge card is removed h Purge card is bad 6 RUN Period a No flame is present b Lockout Interlock opens R7120D1002 c Interr...

Page 11: ...ty shutdown occurs 3 The Pre Ignition Interlock input is ignored throughout the Ignition Trial state b Flame must be proven by the end of the 10 second PFEP four if JR1 is clipped to allow the sequence to continue If flame is not proven by the end of PFEP a safety shutdown occurs 2 Main Flame Establishing Period MFEP a Terminal 7 is energized when the presence of flame is verified at the end of th...

Page 12: ...osition drives the firing rate motor to the Low Fire position NOTE When R7120 is switched to the Test mode it stops and holds at the next Run Test Switch point in the operating sequence Make sure that the Run Test Switch is in the RUN position before leaving the installation SETTINGS AND ADJUSTMENTS Selectable Site Configurable Jumpers The R7120 has site configurable jumper options see Fig 10 and ...

Page 13: ...esent is in RUN position 10 System is in STANDBY condition STANDBY message is displayed in the S7800 Keyboard Display Module 11 All limits and interlocks are reset Flame Signal Measurement See instructions provided with the amplifier Initial Lightoff Checks Proved Pilot Systems Perform this check on all installations that use a pilot It should immediately follow the preliminary inspection NOTE Low...

Page 14: ...light the main flame Ignition of main flame should be smooth 21 Make sure all readings are in the required ranges before proceeding 22 Return the system to normal operation NOTE After completing these tests open the master switch and remove all test jumpers from the subbase termi nals limits controls or switches Direct Spark Ignition Systems This check applies to gas and oil burners not using a pi...

Page 15: ... the sequence after the start of the PILOT IGN period 7 Turn down the pilot pressure very slowly reading the manometer or pressure gauge as it drops Stop instantly when the FLAME LED goes out Note the pres sure The pilot is at the minimum turndown position Immediately turn up the pilot pressure until the FLAME LED comes on again or the flame signal increases to 1 25 Vdc NOTE If there is no flame f...

Page 16: ...ot open the master switch NOTE Some burners continue to purge oil lines between the valves and nozzles even though the fuel valves are closed Terminating the firing cycle instead of opening the master switch allows purging the com bustion chamber This reduces a buildup of fuel vapors in the combustion chamber caused by oil line purging 5 If the detector is sensing hot refractory correct the con di...

Page 17: ...nds depending on the jumper configuration selection for Pilot Flame Establishing Period PFEP after the pilot valve s is energized to denote the fault e Safety shutdown occurs 3 Failure to ignite main only interrupted pilot application a Open the manual pilot valve s leave the main fuel manual shutoff valve s closed b Depress the RESET button c Start the system d The pilot should ignite and the fla...

Page 18: ...R7120D BURNER CONTROL MODULES 66 1196EF 01 18 ...

Page 19: ...R7120D BURNER CONTROL MODULES 19 66 1196EF 01 ...

Page 20: ... Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 66 1196EF 01 M S 07 11 Printed in U S A ...

Page 21: ...nnage Modèles R7120D disponibles R7120D1002 pour Fireye D10 ou E1XX R7120D2000 pour Fireye D20 ou E2XX R7120D3007 pour Fireye D30 ou E3XX CARACTÉRISTIQUES TECHNIQUES Caractéristiques électriques voir tableau 2 Tension et fréquence 120 V c a 10 15 50 60 Hz 10 Dissipation d énergie 10 W maximum Charge connectée totale maximum 2000 VA Fusible pour charge connectée totale 15 A à fusion rapide type SC ...

Page 22: ...ûleur MISE EN GARDE Risque de choc électrique Peut endommager ou causer une défaillance de l équipement Ne pas effectuer de test diélectrique lorsque le module de relais est installé Le suppresseur de surtension interne peut tomber en panne causant l échec du test diélectrique par le module du relais et la destruction de la protection contre la foudre et les hautes intensités AVERTISSEMENT Risque ...

Page 23: ...uffisant derrière la porte fermée du tableau pour qu il n y ait pas d interférence avec le R7120 Montage des autres composants du système Consulter la Fig 9 pour la vue éclatée de l installation ou la notice technique applicable pour le montage des autres composants du système AVERTISSEMENT Risque d incendie ou d explosion Peut causer des dégâts et des blessures graves voire mortelles Respecter to...

Page 24: ...PRISE DE TEST RÉARMEMENT À DISTANCE DDL COMMUNICATIONS DDL INDIQUE UNE DÉTECTION DE SIGNAL DE RETOUR DU STATUT DES CONTACTS DU RELAIS ET DES ENTRÉES DE TENSION SECTEUR CÂBLAGE SUR SITE CÂBLAGE INTERNE VEILLEUSE VEILLEUSE V2 VANNE PRINCIPALE 1K 9K RETOUR ÉTAT RELAIS ET ENTRÉES SECTEUR 1K1 8K1 8K2 9K1 9K2 120 V c a 50 60 Hz SIGNAL DE FLAMME TEST INTERRUPTEUR COMBUSTION BASSE PLACER SI NÉCESSAIRE UN ...

Page 25: ...TION VÉRIFICATION DE DÉMARRAGE DE SÉCURITÉ VÉRIFICATION DE FLAMME ALL VEILLEUSE 10 s5 M 13 À 3 À 3 À M D À 10 11 À 10 X À MF32637 INTERRUPTEUR HAUTE COMBUSTION 8 À 10 12 À 10 12 À M 13 P L1 VANNE PRINCIPALE 7 PRÉBALAYAGE TEMPORISÉ ALIMEN TATION FLAMME PRINCIPAL VEILLEUSE ALARME ALIMEN TATION FLAMME PRINCIPAL VEILLEUSE ALARME ALARME ALARME ALARME 00 VÉRIFICATION DE DÉMARRAGE DE SÉCURITÉ AFFICHAGE D...

Page 26: ...OM HAUT AUTO BAS COM HAUT INTERRUPTEURS DE LIMITEURS INTERRUPTEUR DU BRÛLEUR VERROUILLAGE DE MARCHE CÂBLAGE TYPE DU D10 EP100 OU DU D20 EP200 VERROUILLAGE DE DÉMARRAGE BASSE COMBUSTION INTERRUPTEUR BALAYAGE INTERRUPTEUR PRINCIPAL ALARME DE VERROUILLAGE VANNE S DE COMBUSTIBLE PRINCIPALE S VANNE S À VEILLEUSE TRANSFORMATEUR D ALLUMAGE 1 1 1 1 1 1 1 2 3 3 2 2 UTILISÉ UNIQUEMENT SUR LES PROGRAMMEURS S...

Page 27: ...ERNES MF32639 CAVALIERS DE CONFIGURATION TEMPORISATEUR DE BALAYAGE AMPLIFICATEUR DE FLAMME ALARME SOUFFLANTE VEILLEUSE INTERMITTENTET 1R1 3K1 6K1 A M 6 VANNE PRINCIPALE 7 LF D F G 17 L1 L1 L2 L2 VANNE DE VEILLEUSE INTERMITTENTE 15 S 5 4K1 7K1 2K2 1K1 P DÉBIT D AIR 3 13 LIMITEURS RÉGULATEUR 1R1 X 10 PRÉALLUMAGE 11 8K2 9K1 12 9K2 ...

Page 28: ...T DE FLAMME PRINCIPALE VEILLEUSE FLAMME PRINCIPAL MARCHE ALIMEN TATION POSTBALAYAGE ALIMEN TATION VEILLE 00 00 10 25 00 15 20 ACTION DU MOTEUR MOTEUR DE BRÛLEUR SOUFFLANTE VANNE VEILLEUSE INTERMITTENTE LIMITEURS ET RÉGULATEUR DE BRÛLEUR FERMÉS VERROUILLAGES DE MARCHE FERMÉS VPA FERMÉ INTERRUPTEUR BASSE COMBUSTION VÉRIFICATION DE DÉMARRAGE DE SÉCURITÉ VÉRIFICATION DE FLAMME ALL VEILLEUSE 10 S 5 M 6...

Page 29: ... parallèle avec vanne s motorisée s pour un total de 1150 VA à rotor bloqué appel 460 VA pour ouvrir et 250 VA pour le maintien ou vanne s motorisée s pour un total de 1500 VA à rotor bloqué appel 600 VA pour ouvrir et 250 VA pour le maintien L1 L2 S2 S1 A 8 7 6 5 13 12 X P D M 3 L2 N L1 L 11 10 DÉTECTEUR DE FLAMME UV MOTEUR DE BRÛLEUR SOUFFLANTE PREUVE DE FERMETURE DE VANNE PREUVE DE FERMETURE DE...

Page 30: ... de verrouillage Circuit d allure de chauffe Prébalayage pour économie d énergie Organismes d homologation Veilleuse Principal R7120D 2000 10 s 4 ou 10 s 10 15 sa ou intermittent 15 s Préalllumage marche combustion basse Modulation 4 fils Non Modulation UL CSA R7120D 1002 10 ou 15 s Préallumage verrouillage combustion haute et basse Modulation FM IRI R7120D 3007 10 s ou intermittente Préallumage m...

Page 31: ...lleuse veilleuse intermittente n est pas sous tension d La borne de terminaison d étincelle précoce est activée après 5 secondes e Aucune flamme n est présente à la fin de la période d établissement de la veilleuse f La borne de la vanne principale est sous tension R7120D2000 R7120D3007 g Une panne du système interne est survenue h La carte de balayage est enlevée i La carte de balayage est défect...

Page 32: ...eu e Lorsque la temporisation de PRÉBALAYAGE est terminée le moteur d allure de combustion enclenche la combustion basse f Lorsque le moteur d allure de chauffe atteint la position basse combustion les bornes M à D de l interrupteur basse combustion sont activées pour passer en mode d essai d allumage REMARQUE Un maintien de 30 secondes a lieu pour un interrupteur basse combustion relié par cava l...

Page 33: ...hauffe est en position haute combustion 3 Durant la période de prébalayage de passage à la position basse combustion l interrupteur Marche Test lorsqu il est placé sur la position TEST reste en PRÉBALAYAGE lorsque le moteur d allure de chauffe est en position basse combustion 4 En période d établissement de la veilleuse l interrupteur Marche Test lorsqu il est placé sur la position TEST arrête le ...

Page 34: ...al du fabricant Limiter l essai de la veilleuse à dix secondes Limiter la tentative d allumage du brûleur principal à deux secondes après que le combustible a atteint la buse du brûleur Ne pas dépasser le temps d allumage nominal du fabricant IMPORTANT 1 Si le système ne fonctionne pas correctement noter le code de panne le message de panne le statut de l équipement et l heure de la séquence sur l...

Page 35: ... d allumage sont propres f Fermer l interrupteur principal et observer l étincelle g Après obtention d une étincelle continue ouvrir l interrupteur principal et ajouter un cavalier sur la plaque de raccordement de la borne L1 à la borne de veilleuse 3 Rebrancher le fil de vanne de veilleuse s il a été débranché à l étape b h Fermer l interrupteur principal pour activer le transformateur d allumage...

Page 36: ...DÉMARRAGE 5 Laisser la séquence avancer jusqu à PRÉBALAYAGE si applicable L étincelle d allumage doit avoir lieu lorsque la DEL Veilleuse s allume Écouter pour détecter le clic de l électrovanne de combustible de première étape Le module de relais se verrouille et la DEL Alarme s allume 6 Laisser le module de relais terminer son cycle 7 Ouvrir les vannes de coupure manuelles 8 Appuyer sur le bouto...

Page 37: ...te pas réarmer le système et s assurer que l interrupteur Marche Test est en position de test durant les premières huit secondes de la séquence PILOT IGN IMPORTANT 0 8 seconde ou 3 secondes sont disponibles en fonction de la période d établissement de la veilleuse sélectionnée pour mettre l interrupteur Marche Test en position de Test pour arrêter la séquence après le début de la période PILOT IGN...

Page 38: ...éfractaire chaud rectification des détecteurs photoélectroniques à infrarouge et à ultraviolets Cette condition peut retarder la réponse à une défaillance de flamme et peut aussi empêcher le système de se relancer si un élément réfractaire chaud est détecté Les détecteurs à infrarouge sulfure de plomb peuvent répondre aux infrarouges émis par un élément réfractaire chaud même si ce dernier a visib...

Page 39: ...du brûleur principal seule et les deux ensembles à moins de ne contrôler que la flamme de la veilleuse si une veilleuse intermittente est utilisée ou seulement le brûleur principal lors de l utilisation d un allumage par étincelle direct Vérifier le signal en positions de combustion haute et basse et le cas échéant pendant la modulation Vérifier le temps de réponse en cas d extinction de l amplifi...

Page 40: ...ales et ouvrir la ou les vannes de coupure manuelles de veilleuse b Appuyer sur le bouton de Réarmement c Démarrer le système Le démarrage doit s effectuer normalement et le brûleur principal doit s allumer normalement d Un fois la séquence en période MARCHE normale durant au moins dix secondes avec le brûleur principal allumé fermer la ou les vannes de coupure manuelles principales pour éteindre ...

Reviews: