Honeywell R4795A Manual Download Page 10

60-2285—7

10

R4795A

CHECKOUT

CAUTION

Do not manually push in the relays.

4. Check that the pilot is lit and relay 2K is pulled in.
5. Open the manual main burner shutoff cock. Main

flame should light within one second. If the burner does not
light within one second, close the shutoff cock and shut off
power to the relay. Proceed to step 7.

6. If the burner lights, repeat step 5 two or three times to

verify lightoff.

7. If the lightoff is unsatisfactory, readjust the flame

detector to require a larger pilot flame to hold in the flame
relay. This usually requires:

a. Resighting a photocell or UV type detector farther

out on the axis of a pilot flame, or

b. Adjusting a flame rod detector so that a larger mini-

mum pilot is required.

8. Repeat the entire turndown test until the flame is

established promptly in step 5.

9. Turn up the pilot to full flame at the test completion.

HOT REFRACTORY HOLD-IN TEST
(PHOTOCELL OIL INSTALLATIONS ONLY)

If hot refractory holds in the flame relay at the end of the

burner-on cycle, the system cannot restart until the relay
drops out. Check for hot refractory hold-in by observing the
flame relay for immediate dropout at the end of a long
burner-on period. If the relay does not drop out, resight the
photocell so it does not sight the refractory, or decrease
photocell sensitivity using aperture disks or filters.

IGNITION SPARK RESPONSE TEST
(UV DETECTORS)

The flame relay should not respond (pull in) to ignition

spark. To determine flame detector sensitivity to ignition
spark, perform the following test:

1. Shut the pilot and main fuel manual valves.
2. Start the system by raising the controller setpoint or

pressing the START button. This should energize the igni-
tion transformer so spark is produced between the electrode
and ground.

3. Check the flame relay 2K. The relay should not pull in.

The flame signal current should not be more than one-fourth
microampere.

4. If relay 2K does pull in, resight the detector farther out

from the spark, or away from possible reflection. It may be
necessary to construct a barrier to block the ignition spark
from the detector view. Continue adjustments until flame
detector does not respond to the ignition spark.

IMPORTANT: Repeat ALL required checkout tests after all

adjustments are complete. ALL tests must be satisfac-
tory when the flame detector is in its FINAL position.

SAFE SHUTDOWN CHECKS
Limit Action

With the burner operating, lower the high limit setting to

simulate an overheated boiler or furnace. Normal shutdown
should occur. Restore the normal limit setting; the burner
should go through a normal prepurge and start.

Using manual reset limits is desirable to prevent the

system from cycling off the high limit and to assure that the
condition that caused the limit action is detected as soon as
possible.

Flame Failure

Let burner operate five minutes; then manually shut off

fuel supply to simulate flame failure. Relay should drop out
and fuel valve(s) close. The system will purge and then lock
out on safety. Let the safety switch cool for one minute;
reopen manual fuel valve, and reset safety switch. Burner
should start.

Power Failure

Let the burner run five minutes. Then simulate power

failure by opening the line switch. All relays should drop out
and the fuel valves should close. After a minimum of five
seconds, close the line switch. The R4795 should go through
a normal cycle.

IMPORTANT:  At the completion of all Checkout tests,

make sure that the R4795 is not on safety lockout, that
the pilot is turned up to its normal level, and that all
limit settings are correct. Operate the system through
one normal cycle. Replace cover and securely tighten
thumbscrew.

Summary of Contents for R4795A

Page 1: ...repurge if the flame goes out while burner is running If pilot flame is not re established safetyswitchtripsandlocksoutsystem A tripped safety switch must be manually reset to restore operation Push to resetsafetyswitchisdust resistantenclosed Optional spdt alarm contacts operate external alarm on safety switch lockout Ignition interference circuit rectification amplifier only protects electronic ...

Page 2: ...t contacts Male quick connect terminals female quick connects included See Terminal Ratings 40 F 40 C models have isolated spdt alarm contacts Ordering Information When purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor refer to the TRADELINE catalog or price sheets for complete ordering number or specify 1 Order number 3 Flame failure response tim...

Page 3: ...tion Design Certified File no 21 6 F and F1 ACCESSORIES W136A Test Meter includes 117053 Meter Connector Plug Flame Simulator 203659 Ultraviolet 121708 Rectification 123514B Ultraviolet 117053 Meter Connector Plug FSP1535 Tester for operational check Q624 Solid State Spark Generator 118702E Remote Reset Cover 120 Vac 60 Hz 202471C Reset Cover for R4795A ADDITIONAL CONTROLS Order all additional con...

Page 4: ...ng tubes can result in failure of the sensingtubetoproperlydiscriminatebetweenflame conditions For systems using R4795A with R7290 Amplifiers use C7027 C7035 and C7044 Flame Detectors only on burners that cycle On and Off at least once every 24 hours Appli ances with burners that remain on for 24 hours continuously or longer should use the C7012E Flame Detector with the R7247C Amplifier or the C70...

Page 5: ...TS BURNER MOTOR AIR FLOW SWITCH TO FLAME DETECTOR FLAME ROD OR UV DETECTOR FLAME AMPLIFIER 1K4 3K2 2K2 2K3 MAIN FUEL VALVE S IGNITION PILOT VALVE CONTROLLER LIMIT S R4795A 8 7 6 F G 5 4 3 1 2 2 3 Fig 3 Wiring hookup of oil system with interrupted ignition M8683 L1 HOT L2 1 1 2 3 4 5 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR INTERMITTENT IGNITION CONNECT IGNITION...

Page 6: ...R FLAME DETECTOR 6 8 7 6 T T F G 2 1 3 4 5 AIR FLOW SWITCH SODERLESS CONNECTION 120V 120V M8684 R4795C Replacement In most cases the R4795A can directly replace the R4795C For standing pilot applications where the pilot flame was detected during the off cycle install a relay as shown in Fig 5 Flame Detector Wiring See Fig 6 Alarm Contacts Models with alarm contacts have three male quick con nect t...

Page 7: ...wandremovethecover seeFig 8 Position the R4795 over the Q270 Subbase Start all ten mounting screws and tighten uniformly These screws com plete electrical circuits terminal 1 excepted and hold the R4795 to the subbase L1 HOT L2 1 1 2 2 IF A LINE VOLTAGE ALARM IS USED THE R4795 MUST BE MOUNTED IN A SUITABLE ENCLOSURE POWER SUPPLY MUST MATCH THE ELECTRICAL RATINGS OF THE ALARM PROVIDE DISCONNECT MEA...

Page 8: ... SAFETY SWITCH RESET BUTTON CAPTIVE MOUNTING SCREWS 10 2K 3K M8680 ST71A PLUG IN PURGE TIMER PURGE TIMER CONNECTORS PLUG IN AMPLIFIER OPTIONAL ALARM TERMINALS AMPLIFIER CONNECTORS TEST JACK ARC GAP IGNITION INTERFERENCE PROTECTION R7289 RECTIFICATION AMPLIFIER ONLY PRELIMINARY INSPECTION Make certain that 1 Wiringconnectionsarecorrectandallterminalscrews are tight Use a meter to check the continui...

Page 9: ...ge c As the control attempts to restart the pilot turn the pilot back up slowly just until relay 2K pulls back in You will have 15 seconds to complete this step before lockout occurs d Again turn the pilot down slightly but not enough so theflamerelaydropsout Iftherelaydropsout simply allow the control to complete the purge period and then turn the pilot back up to pull in the flame relay as in st...

Page 10: ...so spark is produced between the electrode and ground 3 Checktheflamerelay2K Therelayshouldnotpullin The flame signal current should not be more than one fourth microampere 4 If relay 2K does pull in resight the detector farther out from the spark or away from possible reflection It may be necessary to construct a barrier to block the ignition spark from the detector view Continue adjustments unti...

Page 11: ...e 1K relay will not pull in The result will be a continuous purge safe failure Hot Refractory Hold in Photocell Installations If hot refractory holds in the flame relay at the end of the running cycle startup is prevented until the hot refractory no longer holds in the flame relay Troubleshooting The first step in troubleshooting the R4795A is to deter mine the location of the system trouble Reset...

Page 12: ... is pulled in check for flame simulating condition 4 If the flame relay is not pulled in clean the 2K relay contacts 5 Replace the purge timer with one of the same timing If problem still continues replace the R4795 D Relay 1K pulls in but the pilot does not light ignition doesnotoccur orexpandingpilotvalvedoesnotopen 1 Make sure that all manual fuel valves are open 2 Check voltage between termina...

Page 13: ... Howeliminated tabulatedinorderofimportance 1 Provide adequate flame grounding area 2 Be sure the ignition electrode and the flame rod are on opposite sides of the grounding area 3 Check for the correct spacings on the ignition electrode Spacing should be 1 16 in 1 6 mm to 3 32 in 2 4 mm for 6 000V systems 1 8 in 3 2 mm to 3 16 in 4 8 mm for 10 000V systems 4 Eliminate any marginal spacings at oth...

Page 14: ...e reasons 1 Some had solvents that could deteriorate plastic parts and wire insulation 2 Some leave an oily residue that will collect dust and dirt The residue will also break down to form various carbonaceousproducts Eitherresultwillcauseearlycontact failure Do not use an abrasive sand paper stock file etc or a burnishing tool to clean contacts Its use can cause early contact failure for these re...

Page 15: ...15 60 2285 7 ...

Page 16: ... Control Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in Mexico www honeywell com bbc ...

Reviews: