R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
60-0770—2
7
Removing and Replacing the Relay/Timer
Cover (Fig. 4)
CAUTION
If the programmer is mounted on the subbase, open
the master switch before removing or replacing the
relay/timer cover.
The relay/timer cover must be removed to install a plug-in
flame signal amplifier, to observe relay and timer operation, or
to inspect the contacts.
Removing the Cover
���
Grasp the relay/timer cover and squeeze until the V-notch
on the cover slides free of the stud on the handle.
���
Rotate the cover down and out to disengage the two tabs
from the slot in the bottom of the programmer chassis.
���
Pull out the cover.
Replacing the Cover
���
Insert the two tabs on the bottom of the cover between
the timer and the programmer chassis and engage
them with the slot in the bottom of the chassis. Make
sure the tabs are not jammed in the slot.
���
Rotate the cover up and in so the V-notch slides along
the stud on the handle. If the cover does not rotate
easily, the tabs are jammed.
���
Make sure the spring clip on the cover fits over the
plug-in amplifier.
���
Push in on the cover until the V-notch snaps into place
on the stud.
NOTE:
If installing a small amplifier, align its ends with
the two scribe marks alongside the receptacle
on the programmer.
���
Push in the amplifier until the circuit board is fully
inserted into the receptacle.
���
Make sure the amplifier is firmly in place, then replace
the relay/timer cover. Make sure the spring clip on the
cover fits over the amplifier.
NOTE:
For further information about a self-checking
amplifier, refer to the Instructions packed
with the amplifier (form 60-2358 for an
R7247B or C, form 60-2357 for an R7248B, or
form 95-8270 for an R7476A).
STUD ON
HANDLE
V-NOTCH
ON COVER
HANDLE
SPRING CLIP
ON COVER
PLUG IN
AMPLIFIER
TIMER
DIAL
TIMER
RELAY/
TIMER COVER
SLOT IN
CHASSIS
TABS (2)
ON COVER
BOTTOM OF
PROGRAMMER
CHASSIS
M7967
Fig. 4. Removing and replacing the relay/timer cover.
Installing a Plug-in Flame Signal Amplifier
(Fig. 5)
���
Remove the relay/timer cover.
���
Make sure the Honeywell monogram is on the outside,
then align the circuit board with the keyed receptacle on
the programmer.
AMPLIFIER
AMPLIFIER
HONEYWELL
MONOGRAM
HONEYWELL
MONOGRAM
ALIGNMENT
SCRIBE MARKS
FOR SMALL
AMPLIFIER
PROGRAMMER
CHASSIS
PROGRAMMER
CHASSIS
KEYED
RECEPTACLE
KEYED
RECEPTACLE
CIRCUIT
BOARD
CIRCUIT
BOARD
TIMER DIAL
TIMER
M7961
Fig. 5. Installing a plug-in flame signal amplifier.
Installation Instructions for Special Features
Some TRADELINE® models and international models (rated
for other than 120V, 60 Hz) can have one (or both) of the
following special features.