Honeywell Q7300A Installation Instructions Manual Download Page 3

62-0135

3

Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES

Fig. 5. Five T7047G Sensors providing

temperature averaging network for

T7300/Q7300 Thermostat/Subbase.

Fig. 6. Nine T7047C Sensors providing

temperature averaging network for

T7300/Q7300 Thermostat/Subbase.

Mounting Subbase

The subbase mounts horizontally on the wall or a 2 in. x 4 in.
wiring box. Position the subbase horizontally on the wall or
on a 2 in. x 4 in. wiring box.

Position and level the subbase or wallplate (for
appearance only). The thermostat functions properly
even when not level.

Use a pencil to mark the mounting holes. See Fig. 7.

Remove the subbase or wallplate from the wall and
drill two 3/16 inch holes in the wall (if drywall) as
marked. For firmer material such as plaster or wood,
drill two 7/32 inch holes. Gently tap anchors (pro-
vided) into the drilled holes until flush with the wall.

Position the subbase over the holes, pulling wires
through the wiring opening.

Loosely insert the mounting screws into the holes.

Tighten mounting screws.

Fig. 7. Mounting the subbase.

WIRING SUBBASE

All wiring must comply with local electrical codes and
ordinances. Follow equipment manufacturer wiring
instructions when available. Refer to Fig. 9 through 17 for
typical hookups. A letter code is located near each
terminal for identification.

CAUTION

Disconnect power before wiring to prevent
electrical shock or equipment damage.

Loosen the terminal screws on the subbase and
connect the system wires. See Fig. 8.

IMPORTANT

Use 18-gauge, solid-conductor color-coded
thermostat cable for proper wiring. If using 18-
gauge stranded wire, no more than ten wires can
be used. Do not use larger than 18-gauge wire.

Securely tighten each terminal screw.

Push excess wire back into the hole.

Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.

Fig. 8. Proper wiring technique.

M4841

T

T

SUBBASE

T

T

T7047G

T

T

T7047G

T

T

T7047G

T

T

T7047G

T

T

T7047G

M4842

T

T

T

T

SUBBASE

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

T

T

T7047C

M4826

FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).

FOR STRAIGHT
INSERTION STRIP
5/16 IN. (8 MM).

WIRES 
THROUGH WALL

WALL

WALL
ANCHORS
(2)

M10237

LEDS

MOUNTING 
HOLES

MOUNTING 
SCREWS

Summary of Contents for Q7300A

Page 1: ...le for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Subbase without Remote Mounted Temperature Sensor Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it ca...

Page 2: ... IMPORTANT To avoid electrical interference which can cause erratic performance keep wiring runs as short as possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems Use shielded cable Belden type 8762 or equivalent for 2 wire and Belden type 8772 or equivalent for 3 wire The cable shield must be grounded only at the controlled equipment case Fig 2 Two ...

Page 3: ...g screws Fig 7 Mounting the subbase WIRING SUBBASE All wiring must comply with local electrical codes and ordinances Follow equipment manufacturer wiring instructions when available Refer to Fig 9 through 17 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 쐃 Loosen the terminal ...

Page 4: ...POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER 1 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LED...

Page 5: ...TH ONE TRANSFORMER 1 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN THE CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X T...

Page 6: ...CONTACTOR 1 C4 C3 C5 CA1 T CA2 CA4 CA3 CA5 T T TRANSFORMER E HEAT RELAY 2 HEAT CHANGEOVER VALVE X3 X1 X4 EQUIPMENT MONITOR 2 EQUIPMENT MONITOR 1 FAN RELAY COOL CHANGEOVER VALVE A2 A1 AS AS DISCHARGE AIR SENSOR ECONOMIZER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS USE A1 AND A2 WHEN THE CONTACTS ARE NORMALLY CL...

Page 7: ... X2 L EQUIPMENT MONITOR 2 EQUIPMENT MONITOR 1 FAN RELAY COOL CHANGEOVER VALVE EM MODE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN THE CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS USE ECONOMIZ...

Page 8: ...ABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN CONTAC...

Reviews: