INSTALLATION INSTRUCTIONS

® U.S. Registered Trademark
Copyright © 1996 Honeywell Inc.  •            •   All Rights Reserved

Q7300A,C,D,G Series 2000

Commercial Thermostat Subbases

APPLICATION

The Q7300 Thermostat Subbases are used with T7300
Thermostats to provide electronic control of commercial

24 Vac single or multistage heat pump or conventional
heating and cooling systems. Select models have termi-
nals for LEDs and remote temperature sensors.  Refer to
Table 1. All Q7300 Thermostat Subbases require a
common wire to the supply power.

Table 1. Description of Q7300 Subbases.

a

Depends on model.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do n

ot place your old

control in the trash

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

Location

Subbase without Remote-Mounted
Temperature Sensor

Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.

Do not install the thermostat where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Subbase with Remote-Mounted
Temperature Sensor(s)

If only the remote-mounted temperature sensor(s) is used
to sense and control room temperature, then install the
thermostat in an area that is accessible for setting and
adjusting the temperature and settings.

If both the subbase and remote-mounted temperature
sensor(s) are used to sense and control room tempera-
ture, then install the subbase about 5 ft above the floor in
an area with good air circulation.

Maximum Stages

a

Model

Applications

Thermostat Required

Heat

Cool

Hookup Drawing

Q7300A

Conventional

T7300D, F

2

2

9-12

Q7300C

Heat Pump

T7300E, F

3

2

13-15

Q7300D

Heat Pump

T7300E, F

3

2

16

Q7300G

Conventional

T7300D, F

3

3

17

62-0135

Summary of Contents for Q7300A

Page 1: ...le for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Subbase without Remote Mounted Temperature Sensor Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it ca...

Page 2: ... IMPORTANT To avoid electrical interference which can cause erratic performance keep wiring runs as short as possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems Use shielded cable Belden type 8762 or equivalent for 2 wire and Belden type 8772 or equivalent for 3 wire The cable shield must be grounded only at the controlled equipment case Fig 2 Two ...

Page 3: ...g screws Fig 7 Mounting the subbase WIRING SUBBASE All wiring must comply with local electrical codes and ordinances Follow equipment manufacturer wiring instructions when available Refer to Fig 9 through 17 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 쐃 Loosen the terminal ...

Page 4: ...POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER 1 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LED...

Page 5: ...TH ONE TRANSFORMER 1 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN THE CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X T...

Page 6: ...CONTACTOR 1 C4 C3 C5 CA1 T CA2 CA4 CA3 CA5 T T TRANSFORMER E HEAT RELAY 2 HEAT CHANGEOVER VALVE X3 X1 X4 EQUIPMENT MONITOR 2 EQUIPMENT MONITOR 1 FAN RELAY COOL CHANGEOVER VALVE A2 A1 AS AS DISCHARGE AIR SENSOR ECONOMIZER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS USE A1 AND A2 WHEN THE CONTACTS ARE NORMALLY CL...

Page 7: ... X2 L EQUIPMENT MONITOR 2 EQUIPMENT MONITOR 1 FAN RELAY COOL CHANGEOVER VALVE EM MODE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN THE CONTACTS SHOULD BE NORMALLY OPEN IN OCCUPIED MODE CONNECT GND TO EARTH GROUND INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS USE ECONOMIZ...

Page 8: ...ABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER USE A1 AND A2 WHEN THE CONTACTS SHOULD BE NORMALLY CLOSED IN OCCUPIED MODE USE A2 AND A3 WHEN CONTAC...

Reviews: