2.

Connect PWT Sensor (not included) to the PWT-BV

Bypass Valve Manifold as shown in Fig. 3. Configure

complete assembly.

Fig. 3.  Connecting PWT Sensor (not included) to the 

PWT-BV Bypass Valve Manifold.

3.

Install the PWT Sensor (not included) per the installa-

tion instructions included with that product.

4.

Commissioning

(a)Close C and D.

(b)Open B (null).

(c)Open D (bleed or purge).

(d)Slowly open A to bleed air from line.

(e)Close B, then fully open A.

(f) Slowly open C to bleed air from line.

(g)Close D, then fully open C.

Fig. 4.  Valve positions showing all valves closed.

Fig. 5.  Valve positions showing all valves open.

Fig. 6.  Valve positions showing all normal operation.

MAINTENANCE

1.

Bleed or purge: follow Commissioning

(step 4 of Installation).

2.

Equalize pressure: open B.

3.

Isolate sensors: close A and C.

DIMENSIONS

Fig. 7.  Dimensional drawing of PWT-BV Bypass Valve 

Manifold showing PWT Sensor (not included) for 

reference only.

1. Assure A & C are closed
2. Open B (null)
3. Open D (bleed or purge)
4. Slowly open A (bleed line)
5. Close B, open A fully
6. Slowly open C (bleed line)
7. Close D, open C fully

MAINTENANCE:

Bleed or Purge – See Commissioning
Equalize pressure – Open B (null)
Isolate Sensors – Close A & C

Z000185-0A

COMMISSIONING:

PWT-BV

Bypass Valve

B

A

C

D

NORMAL OPERATION

0929

M31195

WET DIFFERENTIAL PRESSURE 

B

A

C

D

VALVE POSITIONS: ALL CLOSED

M29593

B A

C

D

VALVE POSITIONS: ALL OPEN

M29594

B A

C

D

VALVE POSITIONS:

NORMAL OPERATION

M29595

1. Assure A & C are closed
2. Open B (null)
3. Open D (bleed or purge)
4. Slowly open A (bleed line)
5. Close B, open A fully
6. Slowly open C (bleed line)
7. Close D, open C fully

MAINTENANCE:

Bleed or Purge – See Commissioning
Equalize pressure – Open B (null)
Isolate Sensors – Close A & C

Z000185-0A

COMMISSIONING:

PWT-BV

Bypass Valve

B

A

C

D

NORMAL OPERATION

0929

M31196

6.75 (172)

WET DIFFERENTIAL PRESSURE 

8.7 (221)

1.5 (38)

7.75 (191)

1.5 (38)

1.8 (46)

3.5 (89)

3.5 (89)

0.5 (13)

By using this Honeywell literature, you agree that Honeywell will have no liability for any 

damages  arising  out  of  your  use  or  modification  to,  the  literature.  You  will  defend  and 

indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or 

damages, including attorneys’ fees, arising out of, or resulting from, any modification to the 

literature by you.

Reviews: