Honeywell PW7K1R1E Installation And Configuration Manual Download Page 4

iv

www.honeywell.com

(This page is left blank intentionally for double-sided printing.)

Summary of Contents for PW7K1R1E

Page 1: ...September 2020 2020 Honeywell All rights reserved 800 26498 PW7K1R1E Input Output Module Installation and Configuration Guide ...

Page 2: ...the right to change any information in this document at any time without prior notice Microsoft and Windows are registered trademarks of Microsoft Corporation Windows Server is a trademark of Microsoft Corporation Ordering Information Please contact your local Honeywell Integrated Security representative or visit us on the web at www honeywellintegrated com for information about ordering Feedback ...

Page 3: ...ons 11 2 3 Jumper Configuration 12 2 4 DIP Switch Configuration 13 2 5 Factory Default Communication Parameters 14 2 6 Bulk Erase 14 2 7 Bulk Erase Steps 14 2 8 Input Power 15 2 9 Communication Wiring 15 2 10 OSDP Reader Wiring 15 2 11 Input Circuit Wiring 16 2 12 Relay Circuit Wiring 17 2 13 Status LEDs 18 2 14 IT Security 19 2 15 Specifications 20 2 16 Additional Mounting Information 23 2 17 War...

Page 4: ...iv www honeywell com This page is left blank intentionally for double sided printing ...

Page 5: ...PW7K1R1E Configuration and Installation Guide Document 800 26498 5 1 Introduction In this chapter 1 1 Overview 6 1 2 Warranty 6 1 3 Liability 7 1 4 FCC Compliance 7 ...

Page 6: ...t configuration Four inputs are provided for monitoring the door contacts exit push buttons and alarm contacts The PW7K1R1E requires power from PoE or local 12VDC The reader power should be based on peak reader power consumption The PW7K1R1E may be mounted in a 3 gang switch box a mounting plate is supplied with the unit The PW7K1R1E may be mounted in an enclosure the supplied mounting plate has m...

Page 7: ...s product is not intended for nor is rated for operation in life critical control applications Honeywell Security Access is not liable under any circumstances for loss or damage caused by or partially caused by the misapplication or malfunction of the product Honeywell Security Access s liability does not extend beyond the purchase price of the product 1 4 FCC Compliance This device complies with ...

Page 8: ...8 www honeywell com Introduction FCC Compliance This page is left blank intentionally for double sided printing ...

Page 9: ...tup In this chapter PW7K1R1E Hardware 10 Terminal Connections 11 Jumper Configuration 12 DIP Switch Configuration 13 Input Power 15 Communication Wiring 15 OSDP Reader Wiring 15 Input Circuit Wiring 16 Relay Circuit Wiring 17 Status LEDs 18 Specifications 20 Additional Mounting Information 23 ...

Page 10: ...10 www honeywell com PW7K1R1E Wiring and Setup PW7K1R1E Hardware 2 1 PW7K1R1E Hardware Figure 2 1 PW7K1R1E Control Board ...

Page 11: ...J4 D24 D19 ETHERNET STATUS LEDs RELAY K1 LED RELAY K2 LED STATUS LEDs SOLDER SIDE Table 1 PW7K1R1E Terminal Connections Terminal Acronym Description TB1 1 IN1 Input 1 TB1 2 IN1 TB1 3 IN2 Input 2 TB1 4 IN2 TB2 1 IN3 Input 3 TB2 2 IN3 TB2 3 IN4 Input 4 TB2 4 IN4 TB3 1 IN5 Input 5 TB3 2 IN5 TB3 3 IN6 Input 6 TB3 4 IN6 TB4 1 VO Auxiliary Power Output 12VDC TB4 2 GND Auxiliary Power Output Ground TB4 3...

Page 12: ...B6 1 NO Relay K3 Normally Open Contact TB6 2 3 C Relay K3 Common Contact TB6 3 NC Relay K3 Normally Closed Contact TB6 4 NO Relay K4 Normally Open Contact TB6 5 4 C Relay K4 Common Contact TB6 6 NC Relay K4 Normally Closed Contact TB7 1 GND Reader Power Ground TB7 2 TR 2 Wire RS 485 TR B See Note 1 below TB7 3 TR 2 Wire RS 485 TR A See Note 1 below TB7 4 RVO 12 Vdc Reader Power Output Table 1 PW7K...

Page 13: ...14 J4 N A RS 485 Termination install only if the MR62e is at the end of the communication bus J5 PoE MR62e powered from the Ethernet connection VIN MR62e powered from an external 12 Vdc power source connected to TB4 3 VIN TB4 4 GND J6 J13 N A Factory Use Only 1 2 3 4 Definitions OFF OFF OFF OFF Normal operating mode ON X OFF OFF After initialization enable default User Name admin and Password pass...

Page 14: ... 3 4 OFF 2 Apply power to the MR62e 3 Watch for LEDs 1 2 and 3 4 to alternately flash at a 0 5 second rate 4 Within 10 seconds from applying power change switches 1 or 2 to OFF If these switches are not changed the MR62e will power up using the OEM default communication parameters 5 LEDs 1 and 2 alternately flash at a 0 5 second rate while the memory is being erased 6 Once the memory is eased LED ...

Page 15: ...he OSDP readers Up to four OSDP readers are supported on the MR62e This 12 Vdc output is limited to 5 A maximum The OSDP reader wiring diagram below shows the use of a 2 pair cable for data and power If this cable cannot support the voltage current requirements a 1 pair cable of sufficient gauge must be used for power See specification section The RS 485 termination jumper J4 is only installed if ...

Page 16: ...t also open circuit shorted grounded and foreign voltage A supervised input circuit requires two resistors be added to the circuit to facilitate proper reporting The standard supervised circuit requires 1K Ohm 1 resistors and should be located as close to the sensor as possible Custom end of line EOL resistances may be configured via the host software Note Grounded and foreign voltage states are n...

Page 17: ... with a mag lock the Normally Closed and Common poles are used Check with local building codes for proper egress door installation Note It is possible for the MR62e to provide power for a 12 Vdc door strike providing the maximum currentis not exceeded see specification section Caution Door lock mechanisms can generate feedback to the relay circuit which can cause damage and premature failure of th...

Page 18: ... MOV Selection Clamp voltage 1 5x VAC RMS For 24VAC strike Panasonic ERZ C07DK470 typical TB6 2 C NC NC NO 1 NO 1 C O TB6 1 NO 1 C NC NC NO 2 C LED DESCRIPTION 1 On line encryption disabled 0 8 second ON 0 2 second OFF On line encryption enabled 0 1 second ON 0 1 second OFF 0 1 second ON 0 1 second OFF0 1 second ON 0 1 second OFF0 1 second ON 0 3 second OFF Off line 0 2 second ON 0 8 second OFF Wa...

Page 19: ...led Therefore it is important that at least one user account is defined and the DIP switches are set to OFF before the MR62e is commissioned It is also highly recommended not to configure the MR62e with an IP address that is accessible from the public Internet To further enhance network security options are available to disable Zeroconf discovery as well as the web configuration module itself 5 In...

Page 20: ...R 12 Vdc VO TB4 1 12 Vdc 1 A maximum RVO TB7 4 12 Vdc 5 A maximum Reader TB3 12 VDC 10 3 through 12 6 150mA maximum AUX TB5 12 VDC 10 7 through 13 0 700 mA maximum Output Four relays Form C contacts rated at 2 A 30 Vdc Inputs Six unsupervised supervised End of Line resistors 1k 1k ohm 1 watt Standard Reader Interface Reader Power 12VDC 5mA maximum RVO TB7 4 Communication 2 Wire RS 485 OSDP protoco...

Page 21: ...net Category 5 minimum Power 18 AWG 1 twisted pair Ethernet CAT 5 minimum RS 485 24AWG 120 ohm impedance 4 000ft 1 220 m maximum Twisted pair s with an overall shield 18AWG Alarm Input 1 twisted pair per input 30 ohm maximum loop resistance Reader data TTL 18AWG 6 conductors 500 foot 150 m maximum Reader data RS 485 24AWG 120 ohm impedance Twisted pair with shield 4000 foot 1 219 m maximum Environ...

Page 22: ...l Dimension 5 5 140mm W x 2 75 70mm L x 0 96 24mm H without bracket 5 5 140mm W x 3 63 92mm L x 1 33 34mm H with bracket Weight 4 oz 112g without bracket 5 oz 142g with bracket UL294 6th edition Performance Levels Feature Level Stand by Power I Endurance IV Line Security I Destructive Attack I ...

Page 23: ... Sources for the optional items shown below 3 gang stainless steel blank cover Leviton part number 84033 40 Available from Graybar part number 88158404 Magnetic switch set G R I part number 505 Figure 2 8 Stainless Steel Blank Cover FIELD WIRING PW 6K1R1E WITH INCLUDED MOUNTING PLATE TO ETHERNET NETWORK OPTIONAL 3 GANG JUNCTION BOX OPTIONAL BLANK COVER W SCREWS ...

Page 24: ...pair or replacement of the defective unit There are no expressed warranties other than set forth herein Mercury Security does not make nor intends nor does it authorize any agent or representative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose All returns must be accompanied by a ...

Page 25: ...re an alternative method for exit is available This product is not intended for nor is rated for operation in life critical control applications Mercury Security is not liable under any circumstances for loss or damage caused by or partially caused by the misapplication or malfunction of the product Mercury Security s liability does not extend beyond the purchase price of the product ...

Page 26: ...26 www honeywell com PW7K1R1E Wiring and Setup Liability This page is left blank intentionally for double sided printing ...

Page 27: ... This page is left blank intentionally for double sided printing ...

Page 28: ...y 135 W Forest Hill Avenue Oak Creek WI 53154 414 766 1700 414 766 1798 Fax European Office Boblingerstrasse 17 D 71101 Schonaich Germany 49 7031 637 782 49 7031 637 769 Fax www honeywell com Specifications subject to change without notice Honeywell All rights reserved 800 26498 ...

Reviews: