background image

PS1202A REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER

69-1136EF—01

2

Fig. 1. Remove cover from power box.

Disconnect the leads from the old power supply. See 

Fig. 2 through 5.

Fig. 2. Power supply location on F50F and F58F.

Remove and discard W8600E terminal block and 

wiring. Set aside screws for later use.

Remove and set aside the sheetmetal screws holding 

the board in place.

Discard the old power supply.

Install New Power Supply

When replacing the power supply, reuse the remaining 

leadwires in the air cleaner when removing the old 

power supply.

Install W8600E terminal block and wiring supplied with 

this kit using screws previously removed.

Align the mounting holes and mount the new power 

supply in the air cleaner, using the sheetmetal screws 

removed earlier. Orient the power supply so P1 and P2 

are toward the front (closest to the switch and neon 

light).

Route the remaining leads so the P3 and P4 leads are 

separate from the low voltage leads. Route all high 

voltage leads around, rather than over, the power 

supply board. Low voltage leads can go over the power 

supply board.

Connect leads to the terminals on the new power 

supply.

IMPORTANT

Do not splice ionizer and collector leads. These 

leads must be unbroken to avoid electrical shock 

through the connector or tape covering the 

splice.

Plug the electronic air cleaner directly into the correct 

voltage and frequency outlet or reconnect power for 

directly wired devices. See Fig. 3 or 4 for internal 

schematic. The air cleaner operates correctly at any 

fan speed on a multispeed or modulated speed system 

wired with conduit or plugged in.

NOTE: To reduce the risk of electric shock, this 

product has a grounding type plug with a 

third (grounding) pin. This plug fits only into 

a grounding type power outlet. If the plug 

does not fit into the outlet, contact a qualified 

electrician to install the proper outlet. Do not 

change the plug in any way.

CHECKOUT

IMPORTANT

The following instructions are for use only by 

qualified personnel.

With all components in place, turn on the air cleaner 

switch and energize the system blower. Check the 

following points of operation:

1.

The neon light next to the on-off switch is on. If a 

W8600E is part of the installation, check the wall 

panel and make sure the ON LED is lighted. The 

W8600E CHECK LED comes on if there is a prob-

lem with the high voltage power supply.

2.

Turn off the system blower. The neon light should 

go off after a few seconds. The neon light shows 

that the air cleaner is energized and the high volt-

age power supply is working properly.

3.

Turn on the system blower. With the air cleaner 

energized, push the test button. A snapping sound 

indicates that the collector voltage is present on the 

cell. The W8600E CHECK LED comes on when the 

test button is held down.

4.

With a multispeed blower, repeat steps 1 through 3 

for each fan speed.

5.

If operation is not as described, refer to the Trouble-

shooting and Service section.

M5676A

3

1

2

REMOVING COVER
FROM POWER BOX.

M33488

POWER 
SUPPLY

Summary of Contents for PS1202A

Page 1: ... damage the product or cause a hazard ous condition such as electrical shock 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING ELECTRICAL HAZARD Can Cause Electric...

Page 2: ...onnect power for directly wired devices See Fig 3 or 4 for internal schematic The air cleaner operates correctly at any fan speed on a multispeed or modulated speed system wired with conduit or plugged in NOTE To reduce the risk of electric shock this product has a grounding type plug with a third grounding pin This plug fits only into a grounding type power outlet If the plug does not fit into th...

Page 3: ...GOES TO TOP TERMINAL AND BLACK LEAD TO BOTTOM TERMINAL M15096B 2 4 BLACK RED CONTACT BOARD RED IONIZER BLACK COLLECTOR BLACK 5 BLACK BLACK BROWN BLACK GREEN 3 1 P4 P1 P2 J3 POWER SUPPLY J4 J8 P3 2 1mA 1 65mA 1 29mA 1 05mA 0 9mA 0 25mA P5 T1 U4 8150V 7500V P8 E6 E4 E5 E3 E1 E2 J1 J2 J1 5 3 2 1 BLACK WHITE GROUND CHOKE P4 P1 P2 J3 POWER SUPPLY J4 J1 P3 2 1mA 1 65mA 1 29mA 1 05mA 0 9mA 0 25mA P5 T1 U...

Page 4: ...mal Test Button When pushed the test button shorts from collector voltage to ground The resulting arcing sound indicates that high voltage is being supplied to the collector The solid state power supply controls current flow to the collector On air cleaners with a W8600E the CHECK LED comes on when the test button is held down Fig 6 Use an ohmmeter to check the electronic cells for short circuits ...

Page 5: ...WIRING BETWEEN W8600E AND AIR CLEANER USE MAX NO 18 4 WIRE THERMOSTAT CABLE CONNECTED 1 G TO 1 G 2 Y TO 2 Y 3 R TO 3 R AND 4 B TO 4 B WIRING OK CORRECT WIRING REPLACE W8600E 3 CHECK FOR CORRECT INPUT VOLTAGE ACROSS P1 AND P2 TERMINALS ON POWER SUPPLY INSPECT CELL S FOR BENT COLLECTOR PLATES BROKEN IONIZER WIRES DIRT ON INSULATORS DAMAGED IONIZER OR COLLECTOR CONTACT TABS YES NO YES NO FIX WIRING R...

Page 6: ...d carbon filter downstream from the air cleaner Make sure particles from the air filter cannot fall into the air cleaner WARNING ELECTRIC SHOCK HAZARD Can Cause Personal Injury Only a trained service technician should perform the following procedure 2 To reduce ozone production about 20 to 25 percent and reduce efficiency about seven to ten percent depending on actual airflow delivered by the fur ...

Page 7: ... or reinstallation costs This warranty shall not apply if it is shown by Honeywell that the defect or malfunction was caused by damage that occurred while the product was in the possession of a consumer Honeywell sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CO...

Page 8: ...C AIR CLEANER Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2012 Honeywell International Inc 69 1136EF 01 M S 03 12 Printed in United States ...

Page 9: ...ement de P5 INSTALLATION Lors de l installation de ce produit 1 Lire attentivement ces instructions Le non respect des instructions peut endommager le produit ou provoquer une situation dangereuse telle que des chocs électriques 2 Vérifier les caractéristiques nominales indiquées dans les instructions et sur le produit pour s assurer que le produit correspond bien à l appli cation prévue 3 L insta...

Page 10: ...on Brancher les fils aux bornes du nouveau bloc IMPORTANT Ne pas épisser les fils de l ionisateur et du collecteur Ces fils doivent être intacts pour éviter les chocs électriques par le connecteur ou le ruban couvrant l épissure Brancher l épurateur d air électronique directement dans la prise de tension et de fréquence correctes ou rétablir l alimentation pour les dispositifs directement câblés V...

Page 11: ... et F58F avec W8600E NOIR 1 2 3 4 1 2 3 4 BORNIER AVANT ARRIÈRE VERS PANNEAU MURAL W8600E W4 W2 W1 W3 TABLEAU DE COMMUTATEUR DE DÉBIT D AIR ORANGE GRIS VIOLET NOIR 1 INTERRUPTEUR DE VERROUILLAGE 2 CAVALIER DE RÉDUCTION D OZONE 3 CAVALIER DE DÉSACTIVATION DE COMMUTATEUR DE DÉBIT D AIR 4 UNITÉ À UNE CELLULE SIMILAIRE MAIS AVEC UNE CELLULE SEULEMENT 5 BORNES P1 P2 SUR MODÈLES 120 V SEULEMENT LES CONN...

Page 12: ...NOIR NOIR MARRON L1 L2 NOIR VERT 3 1 J1 J2 VERT JAUNE ROUGE BLEU NOIR ROUGE PLAQUE À CONTACTS IONISATEUR ROUGE COLLECTEUR NOIR J8 INDUCTEUR DE TERRE 2 NOIR B4 R3 Y2 G1 1 2 3 5 W4 W2 W1 W3 TABLEAU DE COMMUTATEUR DE DÉBIT D AIR ORANGE GRIS VIOLET NOIR 1 INTERRUPTEUR DE VERROUILLAGE 2 CAVALIER DE RÉDUCTION D OZONE 3 CAVALIER DE DÉSACTIVATION DE COMMUTATEUR DE DÉBIT D AIR 4 ENTRAÎNEMENT DE L INDICATEU...

Page 13: ...lecteur Sur les épurateurs avec W8600E la DEL Vérification s allume lorsque le bouton de test est maintenu pressé Fig 6 Utiliser un ohmmètre pour vérifier l absence de court circuit au niveau des cellules électroniques DEL Vérification épurateurs d air avec W8600E La DEL Vérification sur le W8600E s allume pour indiquer les problèmes suivants accumulation excessive de saleté supérieure à celle req...

Page 14: ... 1 G À 1 G 2 Y À 2 Y 3 R À 3 R ET 4 B À 4 B CÂBLAGE OK CÂBLAGE OK REMPLACER LE W8600E 3 VÉRIFIER QUE LA TENSION D ENTRÉE EST CORRECTE ENTRE LES BORNES P1 ET P2 DU TABLEAU D ALIMENTATION INSPECTER LA OU LES CELLULES POUR DÉTECTER LES PROBLÈMES SUIVANTS PLAQUES DE COLLECTEUR COURBÉES FILS D IONISATEUR CASSÉS SALETÉ SUR LES ISOLATEURS LANGUETTES DE CONTACT DE COLLECTEUR OU IONISATEUR ENDOMMAGÉES OUI ...

Page 15: ... l épurateur d air b Ouvrir la porte d accès c Retirer le couvercle du boîtier d alimentation Voir la Fig 1 d Repérer la tige de court circuit J8 sur le bloc d alimentation Voir la Fig 8 Retirer la tige de court circuit et la réinstaller sur une seule broche REMARQUE L ozone sera réduit et la tige de court circuit peut être réinstallée ultérieurement si nécessaire e Replacer le couvercle et la por...

Page 16: ...0 1885 Douglas Drive Golden Valley MN 55422 La présente garantie ne couvre pas les frais de retrait ou de réinstallation La présente garantie ne s appliquera pas s il est démontré par Honeywell que la panne ou le mauvais fonctionnement sont dus à un endommagement du produit alors que le consommateur l avait en sa possession La responsabilité exclusive de Honeywell se limite à réparer ou à remplace...

Reviews: