background image

7 of 12

Installation Instructions

Document 800-08279, Revision A
February 2011 

© Honeywell International. All rights reserved.

8. Using the provided #8x32 screw and locknut, secure the provided ground wire (GREEN with 

YELLOW stripe) to the back of the metal plate as shown below: 

9. Take the input power cord with LED and insert the LED into the panel enclosure as shown below.

 

Note:

 LED MUST be installed BEFORE the power inlet.

10. Once the LED is installed and fully seated, install the AC power inlet into the panel. See the photo 

below:.

LED

AC
Power

Inlet

Summary of Contents for PRO32E1PS

Page 1: ...us output current at 13 8VDC with overload protection Filtered and electronically regulated outputs Built in charger for sealed lead acid batteries with a maximum charge current of 250mA Automatic switch over to stand by battery if present upon AC power failure Reverse battery polarity with a non replaceable fuse Low battery supervision when connected to a low battery input on the panel AC fail su...

Page 2: ...led lead acid maintenance free battery 712BNP or equivalent 3 List of Contents Power Supply Assembly 1 Cable Assembly 12VDC Power and Battery connections 1 Cable Assembly AC and Battery Fail connections 1 Cable Assembly AC Power Inlet and LED Power Indicator 1 Cable Assembly Ground Plate to Chassis 1 Power Supply Mounting Plate 4 keyholes 1 Machine Screw 8 32x5 16 Ground Wire to Plate 1 Kep Nut 8 ...

Page 3: ...011 Honeywell International All rights reserved Here are the three cable assemblies that connect to these pin connectors Figure 2 AC Power Inlet and LED Indicator Cable Assembly Figure 3 12VDC Power and Battery Cable Assembly Connects to CN1 LED AC Power Inlet Connects to CN2 ...

Page 4: ...al All rights reserved Figure 4 AC and Battery Fail Cable Assembly After connecting the three cable assemblies to the pin connectors CN1 CN2 and CN3 the fully connected power supply should look like the below photo Figure 5 on page 5 when viewed from the front inside the metal cabinet Connects to CN3 ...

Page 5: ...ctions 1 Use this power supply only with Honeywell PW3000 PW5000 PW6000 PRO2200 and PRO3200 series access control and proprietary alarm units 2 Secure enclosure in the desired location using appropriately sized fasteners 3 Unpack the power supply and metal plate Do not discard the packing materials until installation and checkout are successfully completed 4 Remove metal plate from packaging ...

Page 6: ...w turns in 6 Position the power supply over the 4 keyholes on the metal plate making sure that the round hole see the below figure is in the bottom left corner as shown and the power supply is positioned with the AC input terminals CN1 facing downward 7 Slide the power supply down in the keyholes until they bottom out Then tighten the four mounting screws to secure the power supply to the metal pl...

Page 7: ...re the provided ground wire GREEN with YELLOW stripe to the back of the metal plate as shown below 9 Take the input power cord with LED and insert the LED into the panel enclosure as shown below Note LED MUST be installed BEFORE the power inlet 10 Once the LED is installed and fully seated install the AC power inlet into the panel See the photo below LED AC Power Inlet ...

Page 8: ...ower Inlet and LED Indicator Cable Assembly Connecting to CN1 Pin Connector Warning Do not connect power at this time 12 Connect the 12VDC output and battery output cable to the power supply by pushing and inserting the cable connector to the pin connector CN2 Figure 7 12VDC Power and Battery Cable Assembly Connecting to CN2 Pin Connector AC Power Inlet and LED Indicator Cable connecting to CN1 CN...

Page 9: ...served 13 Connect the AC and battery fail cable to the power supply by pushing and inserting the cable connector to the pin connector CN3 This is how the pin connectors CN2 and CN3 should look like after attaching both cables AC and Battery Fail Cable Connecting to CN3 CN3 Pin Connector CN2 and CN3 connected CN3 CN2 ...

Page 10: ... proper polarity 17 Connect the battery leads to an appropriately sized battery for the application 18 Connect the low battery wires to the appropriate panel input 19 Connect the AC power fail wires to the appropriate panel input 20 Connect the supplied power cable into the power inlet on the outside of the enclosure 21 Check all power supply wiring to ensure it is installed properly 22 Power on t...

Page 11: ...ingfrom thebattery tothe powersupplyare non power limited Allthewiresthat go from the power supply to the other components in the enclosure except the battery are power limited 26 Secure and lock the cabinet door to prevent access by unauthorized persons 6 Connector Layout and Cabling Information AC Power Inlet 12VDC Power and Battery AC and Battery Fail ...

Page 12: ...r Indicator Connections CN1 Pin No Pin Assignment Wire Color 1 V Black 2 No Connect 3 V Red 4 No Connect 5 Bat Red Fast On Connector 6 No Connect 7 Bat Black Fast On Connector 8 No Connect Table 2 Cable Assembly 12VDC Power and Battery Connections CN2 Pin No Pin Assignment Wire Color Contact State 1 AC Fail White Open AC OK 2 AC Fail Black Open AC OK 3 Battery Fail Black Open Batt OK 4 Battery Fai...