Honeywell Pro-Watch 6000 Installation Manual Download Page 5

PW-6000 Two-Reader Module Installation Guide

Document 800-01951, Revision C

 

v

Notices

Warnings and Cautions

Warning: 

Be

Before connecting the device to the power supply, verify that the output voltage is 
within specifications of the power supply.
Do not apply power to the system until 

after

 the installation has been completed. 

Personal injury or death could occur, and the equipment could be damaged beyond 
repair, if this precaution is not observed!

Warning: Fire Safety and Liability Notice

Never connect card readers to any critical entry, exit door, barrier, elevator, or gate 
without providing 

an alternative exit

 in accordance with all fire and life safety codes 

pertinent to the installation. These fire and safety codes vary from city to city and you 
must get approval from local fire officials whenever using an electronic product to 
control a door or other barrier. Use of egress buttons, for example, may be illegal in 
some cities. In most applications, single action exit without prior knowledge of what 
to do is a life safety requirement. Always make certain that any required approvals are 
obtained in writing. DO NOT ACCEPT VERBAL APPROVALS, BECAUSE THEY 
ARE NOT VALID.
Honeywell never recommends using the PW-6000 or related products for use as a 
primary warning or monitoring system. Primary warning or monitoring systems 
should always meet local fire and safety code requirements. The installer must also 
test the system on a regular basis by instructing the end user in appropriate daily 
testing procedures. Failure to test a system regularly could make the installer liable for 
damages to the end user if a problem occurs.

Note:  

See the Remote Enclosure Installation manuals for 

PW5K2ENC1/PW5K2ENC2 or PW5K1ENC3 for installation instructions.

Warning: 

EARTH GROUND all enclosures for proper installation.

Warning: 

Use suppressors on all door strikes. Use S-4 suppressors for installation. Honeywell 
recommends only DC strikes.

Summary of Contents for Pro-Watch 6000

Page 1: ...July 2010 2010 Honeywell International Inc All rights reserved 800 01951 Revision C Pro Watch 6000 Two Reader Module PW6K1R2 Installation Guide ...

Page 2: ...eserves the right to change any information in this document at any time without prior notice Pro Watch is a trademark of Honeywell Inc Ordering Information Please contact your local Honeywell representative or visit us on the web at www honeywellintegrated com for information about ordering Feedback Honeywell appreciates your comments about this manual Please visit us on the web at www honeywelli...

Page 3: ...iance viii Unpacking Procedure viii Shipping Instructions ix Installing the PW 6000 Two Reader Module Description 1 Specifications 2 Setup 3 Setting Jumpers 3 Setting DIP Switches 4 LED Operation 6 Power 8 Communications 8 Wiring 9 Reader Wiring 11 Input Wiring 12 Control Output Wiring 12 Mounting Options 13 Installing the Module 14 PW 6000 2 Reader Input Module Programming Sheet ...

Page 4: ...www honeywell com ...

Page 5: ...arrier Use of egress buttons for example may be illegal in some cities In most applications single action exit without prior knowledge of what to do is a life safety requirement Always make certain that any required approvals are obtained in writing DO NOT ACCEPT VERBAL APPROVALS BECAUSE THEY ARE NOT VALID Honeywell never recommends using the PW 6000 or related products for use as a primary warnin...

Page 6: ...used or disclosed to others for procurement or manufacture except as authorized by and with the written permission of Honeywell Inc The information contained in this document or in the product itself is considered the exclusive property and trade secrets of Honeywell Inc Copyright laws of the United States protect all information in this document or in the software product itself Note Any use of t...

Page 7: ...the limits set forth in Product manuals THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THIS PROVISION THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS IMPLIED OR STATUTORY INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE NO REPRESENTATION OR WARRANTY OF THE DISTRIBUTOR SHALL EXTEND THE LIABILITY OR RESPONSIBILITY OF THE MANUFACTURER BEYOND THE TERM...

Page 8: ...e to the shipment is noticed before unpacking a claim must be filed with the commercial carrier All containers should be opened and unpacked carefully in order to prevent damage to the contents The following steps are used to unpack equipment in preparation for installation 1 Open the container and remove the unit s and all packing material Retain the container and all packing materials They may b...

Page 9: ...or reason you are returning the equipment Your original purchase order number invoice number and if the unit is still under warranty A new purchase order number if the unit is not under warranty 2 From the customer service department obtain the Return Authorization Number RMA 3 Show the RMA number on all packages shipped Packages which are not marked with an RMA number will be refused at the facto...

Page 10: ...x www honeywell com Notices Shipping Instructions ...

Page 11: ...t two connectors provide the reader and associated I O terminals for reader 0 The last connector on the rack mount edge provides terminals for two additional general purpose inputs When the board is mounted flat two additional relay outputs and two additional general purpose inputs are available along with two dedicated inputs for cabinet tamper and power fault detection on the opposite edge of th...

Page 12: ...ical Environment Reader power 5VDC 5 6 2 150mA max each or 12VDC pass through 175mA max each Reader LED output TTL compatible high 3V low 0 5V 5mA source sink max Reader buzzer output Open collector 5VDC open circuit max 10mA sink max Reader data inputs TTL compatible inputs RS 485 9 600 to 38 400 bps Power 1 twisted pair 18AWG RS 485 24AWG 4 000 feet 1 200 m max 2 twisted pair with shield 120Ω 23...

Page 13: ...ng Jumpers Table 1 Jumper Settings Jumper Setting Default Selected J1 OFF Port 1 RS 485 EOL terminator is not active ON Port 1 RS 485 EOL terminator is active J2 OFF Reader 0 Power Terminal provides 5 VDC ON Reader 0 Power Terminal provides 12 VDC J3 OFF Reader 1 Power Terminal provides 5 VDC ON Reader 1 Power Terminal provides 12 VDC ...

Page 14: ...F ON OFF ON ADDRESS 5 OFF OFF ON ON OFF ADDRESS 6 OFF OFF ON ON ON ADDRESS 7 OFF ON OFF OFF OFF ADDRESS 8 OFF ON OFF OFF ON ADDRESS 9 OFF ON OFF ON OFF ADDRESS 10 OFF ON OFF ON ON ADDRESS 11 OFF ON ON OFF OFF ADDRESS 12 OFF ON ON OFF ON ADDRESS 13 OFF ON ON ON OFF ADDRESS 14 OFF ON ON ON ON ADDRESS 15 ON OFF OFF OFF OFF ADDRESS 16 ON OFF OFF OFF ON ADDRESS 17 ON OFF OFF ON OFF ADDRESS 18 ON OFF OF...

Page 15: ...OFF OFF OFF ADDRESS 24 ON ON OFF OFF ON ADDRESS 25 ON ON OFF ON OFF ADDRESS 26 ON ON OFF ON ON ADDRESS 27 ON ON ON OFF OFF ADDRESS 28 ON ON ON OFF ON ADDRESS 29 ON ON ON ON OFF ADDRESS 30 ON ON ON ON ON ADDRESS 31 OFF OFF Reserved OFF ON 9 600 BPS ON OFF 19 200 BPS ON ON 38 400 BPS OFF Not Used Table 2 DIP Switch Settings continued S8 S7 S6 S5 S4 S3 S2 S1 Selection ...

Page 16: ...put is energized or ON its corresponding status LED becomes ON also The LED remains ON for as long as the relay is energized Table 3 Onboard LEDs Mode LED D1 LED D2 Description Power up sequence ON OFF Start power up hardware setup OFF ON Testing RAM ON ON Testing ROM and completing initialization FLASH ON LED D1 flashes four times after power up is completed Normal Operation FLASH This is the pro...

Page 17: ...D is shown in the following table Table 4 Additional PW6000 Two Reader Module LEDs LED number Description D3 Reader 0 activity D4 Reader 1 activity D5 Input 0 D6 Input 1 D7 Input 2 D8 Input 3 D9 Input 4 D10 Input 5 D11 Input 6 D12 Input 7 D13 Tamper D14 Power D15 Relay 0 status D16 Relay 3 status D17 Relay 2 status D18 Relay 4 status D19 Relay 1 status D20 Relay 5 status ...

Page 18: ...d to 19 2Kbps or 9 6Kbps if the line conditions or receiving equipment require it see Table 1 on page 3 for jumper settings and Table 2 on page 4 for DIP switch settings For wiring to an RS 485 port 1 TR is the plus side of the transmit and receive differential signal 2 TR is the negative side of the transmit and receive differential signal 3 GND is the signal ground The wiring for this signal is ...

Page 19: ...Inside Panel Chassis GND Inside Panel Voltage is selected by Jumper J2 On Board Voltage is selected by Jumper J3 On Board RED BROWN YELLOW WHITE GREEN BLACK DRAIN RED BROWN YELLOW WHITE GREEN BLACK DRAIN BLACK RED D1 D2 D3 D4 D15 D16 D17 D20 D18 D19 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 RS 485 TR RS 485 TR RS 485 GND 12V GND READER1 V READER1 LED READER1 BZR READER1 D1 READER1 D0 READER1 GND IN3 IN3 ...

Page 20: ...criptions of LEDs D1 D20 Figure 2 PW 6000 Two Reader Module Wiring Connectors 1 7 9 Note For RS 485 Communication Connections twist the blue pair together and use as the common use the orange pair as your data pair observing polarity Connect the external drain shield to the appropriate earth ground on one end ...

Page 21: ...ch reader port can be configured via host software to support one wire single or bi colored reader LED An example of the most common configuration is shown below If Beeper Control is not used its terminal can be programmed to be the second wire for the two wire bi colored reader LED To fully utilize each reader port a 6 conductor cable 18AWG is required Reader port configuration is set via host so...

Page 22: ... indicate safe condition Input configuration including debounce and hold time is set via host software Control Output Wiring Six form C relay contacts are provided for controlling door strike or other devices Each may be assigned to door related functions or general purpose output They are configurable as standard energize to activate or fail safe de energize to activate via host software The ener...

Page 23: ... or it can be mounted flat against any surface using standoffs under the mounting holes provided in each of the four corners of this board When this board is rack mounted the connectors for two general purpose inputs two general purpose outputs and two dedicated inputs are not accessible and should not be used The most common reason for mounting a board flat is that it is being installed remotely ...

Page 24: ... Power Supply Harness Warning DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET UNTIL ALL WIRING HAS BEEN INSTALLED AND RECHECKED 4 Connect wiring to the reader interfaces as appropriate 5 Connect wiring to input sensors or install jumper wire as appropriate 6 Connect relay output wiring as appropriate 7 Connect communications wiring to the Intelligent Controller 8 Recheck wiring for correct connec...

Page 25: ...ision C 15 A PW 6000 2 Reader Input Module Programming Sheet Project Name Location Country Host IC Board 0 Board Description PW Panel RS485 Port 3 Board Address 0 Location Floor Cabinet Location Tamper Input Connected Powerfail Shunted Termination Jumper J1 Not Active ...

Page 26: ...e Cable Destination Conductor Color Power Pin 1 Power Pin 2 Inputs 4 and 5 Connected Cable Cable Destination Conductor Color Input 4 Pin 1 Input 4 Com Pin 2 Input 5 Pin 3 Input 5 Com Pin 4 Door 1 Input Output Connected Cable Cable Destination Conductor Color Input 0 Pin 1 Input 0 Com Pin 2 Input 0 Pin 3 Input 1 Com Pin 4 Relay 0 No Pin 5 Relay 0 Com Pin 6 Relay 0 NC Pin 7 Relay 1 No Pin 8 Relay 1 ...

Page 27: ...ct J2 5 Volt Connected Cable Cable Destination Conductor Color DC Out Pin 1 Red LED Pin 2 Beeper Ctrl Pin 3 Data 1 Pin 4 Data 0 Pin 5 Common Pin 6 Door 2 Input Output Connected Cable Cable Destination Conductor Color Input 2 Pin 1 Input 2 Com Pin 2 Input 3 Com Pin 3 Input 3Com Pin 4 Relay 2 No Pin 5 Relay 2 Com Pin 6 Relay 2 NC Pin 7 Relay 3 No Pin 8 Relay 3 Com Pin 9 Relay 3 NC Pin 10 ...

Page 28: ...tion Conductor Color DC Out Pin 1 Red LED Pin 2 Beeper Ctrl Pin 3 Data 1 Pin 4 Data 0 Pin 5 Common Pin 6 Inputs 6 and 7 Connected Cable Cable Destination Conductor Color Input 6 Pin 1 Input 6 Com Pin 2 Input 7 Pin 3 Input 7 Com Pin 4 Outputs 4 and 5 Connected Cable Cable Destination Conductor Color Relay 4 NC Pin 1 Relay 4 Com Pin 2 Relay 4 NO Pin 3 Relay 5 NC Pin 4 Relay 5 Com Pin 5 Relay 5 NO Pi...

Page 29: ...ity 135 W Forest Hill Avenue Oak Creek WI 53154 United States 800 323 4576 414 766 1798 Fax www honeywellintegrated com Specifications subject to change without notice Honeywell All rights reserved Document 800 01951 Revision C ...

Reviews: