PRO TH3110B Non-programmable Digital Thermostat
9
Installation Guide
8
1
5
9
14
15
System type
Heating cycle rate
(CPH: cycles/hour)
Compressor
cycle rate
(CPH)
Temperature
display
Compressor
protection
0 Gas, oil or electric heat with air conditioning
1
Heat pump (5 minute compressor off time in heating and cooling)
5 For gas or oil furnaces of less than 90% efficiency
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
9
For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
0 Fahrenheit
1
Celsius
5 Five-minute compressor off time
**See page 10
[Other options: 0, 1, 2, 3 or 4-minute off time]
Setup Function
Settings & Options
To begin, press and hold the and
buttons until the display changes
Function
number
Press
to change settings
Press
to advance to next function
Press and hold
to exit and save settings
Setting
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Setup
10
0
Test
10
30
70
Heating system
Cooling system
Thermostat
information
(for reference only)
0
Heat and fan turn off.
1
Heat turns on. Fan also turns on immediately if Fan Operation
Switch is set to Electric Heat/Heat Pump (see page 6).
0
Compressor and fan turn off.
1
Compressor and fan turn on.
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System Test
System Status
Installer system test
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
System switch
System test
number
System status
Installer system test
After completing the installer setup above, press the
button again to begin a
system test (see next page).
Press and hold both buttons
1
Set
S
SY
YS
ST
TE
EM
M
switch to Cool.
2
Press
to turn on cooling system, then check system status (see table, below).
3
Press
to turn off cooling system.
4
Set
S
SY
YS
ST
TE
EM
M
switch to Heat.
5
Press
to turn on heating system, then check system status (see table, below).
6
Press
to turn off heating system.
7
[Optional] Set
S
SY
YS
ST
TE
EM
M
switch to Off to display thermostat information (see table, below).
Press
to display 71-76.
8
Press and hold
to terminate system test at any time.
Follow the procedure below to test the heating and cooling system.